SPEC 45313
AL 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.
Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} E96627 4/C XXX KCMIL COMPACT AL.--- {ALUMAFLEX}® AA8176 XX MILS XLP 600 VOLTS GW 1 X X/0 AWG 3E AL TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
TBA | 8 | 4 | 7 | 0.134 | 45 | 1 x 8 | 0.754 | 50 | 0.854 | 162 | 295 |
TBA | 6 | 4 | 7 | 0.169 | 45 | 1 x 8 | 0.839 | 50 | 0.939 | 213 | 364 |
TBA | 1/0 | 4 | 19 | 0.336 | 55 | 1 x 4 | 1.291 | 50 | 1.391 | 609 | 883 |
TBA | 2/0 | 4 | 19 | 0.376 | 55 | 1 x 4 | 1.388 | 50 | 1.488 | 727 | 1024 |
TBA | 3/0 | 4 | 19 | 0.422 | 55 | 1 x 4 | 1.599 | 60 | 1.719 | 877 | 1246 |
TBA | 4/0 | 4 | 19 | 0.474 | 55 | 1 x 2 | 1.725 | 60 | 1.845 | 1119 | 1521 |
644656 | 250 | 4 | 22 | 0.52 | 65 | 1 x 2 | 1.887 | 65 | 2.019 | 1318 | 1869 |
644652 | 350 | 4 | 35 | 0.615 | 65 | 1 x 2 | 2.118 | 65 | 2.250 | 1784 | 2432 |
644649 | 500 | 4 | 35 | 0.735 | 65 | 1 x 2/0 | 2.408 | 80 | 2.574 | 2403 | 3232 |
TBA | 600 | 4 | 61 | 0.812 | 80 | 1 x 1 | 2.664 | 75 | 2.814 | 2922 | 3795 |
640988 | 750 | 4 | 58 | 0.908 | 80 | 1 x 1/0 | 2.896 | 80 | 3.062 | 3409 | 4356 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Amp | Amp | ||
TBA | 8 | 4 | 6.0 | 316 | 1.072 | 1.290 | 0.034 | 0.052 | 32 | 36 |
TBA | 6 | 4 | 6.6 | 503 | 0.674 | 0.812 | 0.029 | 0.051 | 40 | 44 |
TBA | 1/0 | 4 | 9.7 | 2027 | 0.168 | 0.201 | 0.019 | 0.044 | 96 | 108 |
TBA | 2/0 | 4 | 10.4 | 2555 | 0.133 | 0.160 | 0.017 | 0.043 | 108 | 120 |
TBA | 3/0 | 4 | 12.0 | 3221 | 0.105 | 0.126 | 0.015 | 0.042 | 124 | 140 |
TBA | 4/0 | 4 | 12.9 | 4062 | 0.084 | 0.100 | 0.014 | 0.041 | 144 | 164 |
644656 | 250 | 4 | 14.1 | 4800 | 0.071 | 0.086 | 0.015 | 0.041 | 164 | 184 |
644652 | 350 | 4 | 15.8 | 6720 | 0.050 | 0.062 | 0.012 | 0.040 | 200 | 224 |
644649 | 500 | 4 | 18.0 | 9600 | 0.035 | 0.044 | 0.010 | 0.039 | 248 | 280 |
TBA | 600 | 4 | 19.7 | 11520 | 0.029 | 0.037 | 0.012 | 0.039 | 272 | 308 |
640988 | 750 | 4 | 21.4 | 14400 | 0.024 | 0.031 | 0.011 | 0.038 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.004
Updated On: July 3, 2024, 10:13 p.m. UTC