SPEC 45313
AL 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} E96627 4/C XXX KCMIL COMPACT AL.--- {ALUMAFLEX}® AA8176 XX MILS XLP 600 VOLTS GW 1 X X/0 AWG 3E AL TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | |||
| TBA | 8 | 4 | 7 | 0.134 | 45 | 1 x 8 | 0.755 | 50 | 0.855 | 352 | BK |
| TBA | 6 | 4 | 7 | 0.169 | 45 | 1 x 8 | 0.84 | 50 | 0.94 | 427 | BK |
| TBA | 1/0 | 4 | 19 | 0.336 | 55 | 1 x 4 | 1.292 | 50 | 1.392 | 978 | BK |
| TBA | 2/0 | 4 | 19 | 0.376 | 55 | 1 x 4 | 1.389 | 50 | 1.489 | 1131 | BK |
| TBA | 3/0 | 4 | 19 | 0.423 | 55 | 1 x 4 | 1.603 | 50 | 1.703 | 1492 | BK |
| TBA | 4/0 | 4 | 19 | 0.475 | 55 | 1 x 2 | 1.729 | 50 | 1.829 | 1758 | BK |
| 644656 | 250 | 4 | 22 | 0.52 | 65 | 1 x 1 | 1.911 | 60 | 2.037 | 1856 | BK |
| 644652 | 350 | 4 | 35 | 0.616 | 65 | 1 x 2/0 | 2.143 | 60 | 2.269 | 2408 | BK |
| 644649 | 500 | 4 | 34 | 0.736 | 65 | 1 x 2/0 | 2.433 | 75 | 2.59 | 3203 | BK |
| TBA | 600 | 4 | 61 | 0.813 | 80 | 1 x 1 | 2.668 | 75 | 2.818 | 4094 | BK |
| 640988 | 750 | 4 | 58 | 0.908 | 80 | 1 x 1/0 | 2.899 | 75 | 3.057 | 4397 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 4 | 6 | 396 | 1.071 | 1.334 | 0.052 | 32 | 36 |
| TBA | 6 | 4 | 6.6 | 629 | 0.674 | 0.84 | 0.051 | 40 | 44 |
| TBA | 1/0 | 4 | 9.7 | 2534 | 0.167 | 0.208 | 0.044 | 96 | 108 |
| TBA | 2/0 | 4 | 10.4 | 3194 | 0.133 | 0.166 | 0.043 | 108 | 120 |
| TBA | 3/0 | 4 | 11.9 | 4027 | 0.105 | 0.131 | 0.042 | 124 | 140 |
| TBA | 4/0 | 4 | 12.8 | 5078 | 0.084 | 0.105 | 0.041 | 144 | 164 |
| 644656 | 250 | 4 | 14.3 | 6000 | 0.07 | 0.087 | 0.041 | 164 | 184 |
| 644652 | 350 | 4 | 15.9 | 8400 | 0.051 | 0.064 | 0.04 | 200 | 224 |
| 644649 | 500 | 4 | 18.1 | 12000 | 0.036 | 0.045 | 0.039 | 248 | 280 |
| TBA | 600 | 4 | 19.7 | 14400 | 0.03 | 0.038 | 0.039 | 272 | 308 |
| 640988 | 750 | 4 | 21.4 | 18000 | 0.023 | 0.03 | 0.038 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.