SPEC 10090

CU 150V HVAC Wire Unshielded Thermostat CL2/CMH

CU 150V HDPE Insulation PVC Jacket CL2/CMH Power Limited Unshielded Thermostat Wire

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:High Density Polyethylene HDPE
  3. Rip Cord:Rip cord for ease of jacket strip ability
  4. Overall Jacket:Polyvinyl Chloride (PVC) Jacket in Brown

Applications and Features:

  • 150 Voltage
  • rating per NEC® Article 725
  • ETL listed to UL 13 and UL 444
  • Meets UL 1581 Vertical Tray Flame Test (FT-1)
  • Type CL2
  • C22.2 214 TYPE CMH
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • UL 13 Power-Limited Circuit Cables
  • UL 444 CM/CL2
  • Sample Print Legend:

    TYPE CL2 C{ETL}US XX AWG XX/C BAROSTAT II SUN RES -- TYPE CMH FT1 -- {MM/DD/YY} {HH:MM}
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insulation ColorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinch
    20 AWG
    55202◊202SOLID0.032RD,WE5140.1146910.50312.6550.0270.5BN
    55203◊203SOLID0.032RD,WE,GN5140.12191310.50312.6550.0270.5BN
    55204◊204SOLID0.032RD,WE,GN,BE5140.132121610.50312.6550.0270.5BN
    55205◊205SOLID0.032RD,WE,GN,BE,YW5150.147152010.50312.6550.0270.6BN
    55206◊206SOLID0.032RD,WE,GN,BE,YW,BN5150.16182410.50312.6550.0270.6BN
    55207◊207SOLID0.032RD,WE,GN,BE,YW,BN,OE5150.16182710.50312.6550.0270.6BN
    55210◊2010SOLID0.032RD,WE,GN,BE,YW,BN,OE,BK,PK,GY5150.202303810.50312.6550.0270.8BN
    55212◊2012SOLID0.032RD,WE,GN,BE,YW,BN,OE,BK,PK,GY,TN,PE5150.209364210.50312.6550.0270.8BN
    18 AWG
    55302◊182SOLID0.04RD,WE5140.13210146.6598.2650.0360.5BN
    55303◊183SOLID0.04RD,WE,GN5140.1415196.6598.2650.0360.6BN
    55304◊184SOLID0.04RD,WE,GN,BE5140.15419256.6598.2650.0360.6BN
    55305◊185SOLID0.04RD,WE,GN,BE,YW5150.1724306.6598.2650.0360.7BN
    55306◊186SOLID0.04RD,WE,GN,BE,YW,BN5150.18629376.6598.2650.0360.74BN
    55307◊187SOLID0.04RD,WE,GN,BE,YW,BN,OE5150.18634416.6598.2650.0360.7BN
    55308◊188SOLID0.04RD,WE,GN,BE,YW,BN,OE,BK5150.20229486.6598.2650.0360.8BN
    55310◊1810SOLID0.04RD,WE,GN,BE,YW,BN,OE,BK,PK,GY5150.23848586.6598.2650.0361BN
    55312◊1812SOLID0.04RD,WE,GN,BE,YW,BN,OE,BK,PK,GY,TN,PE5150.24558696.6598.2650.0361BN
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.010

    Updated On: April 1, 2025, 11:18 p.m. UTC