SPEC 10028

Romex® Brand SIMpull® Copper Type NM-B Cable

Nonmetallic-Sheathed Cable. 600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. PVC Jacket with SIMpull® Technology for Easier Pulling.

...

Construction:

  1. Conductor: Bare copper per ASTM B3. Sizes #14 AWG - #10 AWG are solid. Sizes #8 AWG - #2 AWG are Class B compressed stranded per ASTM B8
  2. Insulation: All phases and neutral(s) are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
    Color Code:
    2/C: Black, White
    3/C: Black, Red, White
    4/C: Black, Red, Blue, White
  3. Ground: Solid soft drawn bare copper with kraft paper wrap
  4. Binder: Kraft paper
  5. Jacket: Polyvinyl Chloride (PVC) jacket utilizing SIMpull® Technology

Applications and Features:

Southwire Romex® Brand SIMpull® Type NM-B (nonmetallic-sheathed) cable may be used for both exposed and concealed work in dry locations as specified in the National Electrical Code®. NM-B cable is primarily used in residential wiring as branch circuits for outlets, switches, and other loads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B cable is 600 volts.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 719 Nonmetallic-Sheathed Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • Federal Specification A-A-59544
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    E18679 (UL) ROMEX® SIMpull{TM} XX AWG (X.XXmm2) CU X CDR WITH XX AWG (mm2) GROUND TYPE NM-B 600 VOLTS NOM-ANCE PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    288274142Solid0.064151 x 14250.372x0.1763761
    639469143Solid0.064151 x 14250.478x0.1764981
    550482*144Solid0.064201 x 14300.3506296
    550539144Solid0.064151 x 14300.3506295
    288282122Solid0.080151 x 12250.422x0.1905987
    639478123Solid0.080151 x 12250.524x0.19079115
    550542124Solid0.080151 x 12300.39599138
    550484*124Solid0.080201 x 12300.39599138
    288290102Solid0.101201 x 10250.505x0.21891126
    639485103Solid0.101201 x 10250.630x0.220122168
    555832104Solid0.101201 x 10300.479154206
    5518888270.141301 x 10300.628x0.278132190
    2889368270.141301 x 10300.628x0.278132190
    6394928370.141301 x 10300.585185260
    2889446270.177301 x 10300.700x0.314192260
    6395006370.177301 x 10300.672276365
    6396824370.225401 x 8300.843440575
    6397082370.282401 x 8300.887671830
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * 2x2 construction
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    2882741420.8652.6313.1700.0582025
    6394691430.9982.6313.1700.0582025
    550482*1441.41052.6313.1700.0581620
    5505391441.41052.6313.1700.0581620
    2882821221.01041.6622.0020.0542530
    6394781231.11561.6622.0020.0542530
    5505421241.61671.6622.0020.0542024
    550484*1241.61671.6622.0020.0542024
    2882901021.21661.0401.2530.0503540
    6394851031.32491.0401.2530.0503540
    5558321041.92651.0401.2530.0502832
    551888821.72640.6530.7860.0525055
    288936821.72640.6530.7860.0525055
    639492832.33960.6530.7860.0525055
    288944622.04190.4110.4950.0516575
    639500632.76290.4110.4950.0516575
    639682433.410010.2580.3100.0488595
    639708233.515920.1620.1950.045115130
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.036

    Updated On: Nov. 22, 2024, 9:04 p.m. UTC