SPEC 10028

Romex® Brand SIMpull® Copper Type NM-B Cable

Nonmetallic-Sheathed Cable. 600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. PVC Jacket with SIMpull® Technology for Easier Pulling.

...

Construction:

  1. Conductor: Bare copper per ASTM B3. Sizes #14 AWG - #10 AWG are solid. Sizes #8 AWG - #2 AWG are Class B compressed stranded per ASTM B8
  2. Insulation: All phases and neutral(s) are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
    Color Code:
    2/C: Black, White
    3/C: Black, Red, White
    4/C: Black, Red, Blue, White
  3. Ground: Solid soft drawn bare copper with kraft paper wrap
  4. Binder: Kraft paper
  5. Jacket: Polyvinyl Chloride (PVC) jacket utilizing SIMpull® Technology

Applications and Features:

Southwire Romex® Brand SIMpull® (nonmetallic-sheathed) Cable may be used for both exposed and concealed work in dry locations with ampacity limited to that for 60°C conductors as specified in the National Electrical Code® (NEC). Individual conductor insulation is rated 90°C as required by the NEC and by the UL product standard (UL 719) for terminations in lighting fixtures. NM-B cable is primarily used in residential wiring as branch circuits for outlets, switches, and other loads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B cable is 600 volts. Individual conductors within Type NM-B Cable are not listed or marked as THHN conductors (or any other NEC recognized conductor type) and are not permitted to be installed apart from the complete Type NM-B Cable. Conductors routed inside panelboards and boxes (without the cable jacket) for termination therein are considered part of the complete Type NM-B Cable.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 719 Nonmetallic-Sheathed Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • Federal Specification A-A-59544
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    E18679 (UL) ROMEX® SIMpull{TM} XX AWG (X.XXmm2) CU X CDR WITH XX AWG (mm2) GROUND TYPE NM-B 600 VOLTS NOM-ANCE PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessInsulation ColorDiameter Over InsulationGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    550482◊*144SOLID0.06416BK, WE, RD, WE/RD0.0941 x 14300.356396WE
    288274◊142SOLID0.06416BK, WE0.0941 x 14250.372x0.1763760WE
    639469◊143SOLID0.06416BK, WE, RD0.0941 x 14250.478x0.1765082BE
    550542◊124SOLID0.08116BK, WE, RD, BE0.1111 x 12300.396100138YW
    288282◊122SOLID0.08116BK, WE0.1111 x 12250.422x0.1905986YW
    639478◊123SOLID0.08116BK, WE, RD0.1111 x 12250.524x0.19079115PE
    555832◊104SOLID0.10221BK, WE, RD, BE0.1421 x 10300.48155207OE
    288290◊102SOLID0.10221BK, WE0.1421 x 10250.505x0.21892127OE
    639485◊103SOLID0.10221BK, WE, RD0.1421 x 10250.630x0.220123169PK
    639492◊8370.14231BK, WE, RD0.2021 x 10300.585185260BK
    288936◊8270.14231BK,WE0.2021 x 10300.628x0.278133191BK
    639500◊6370.17831BK, WE, RD0.2381 x 10300.672276365BK
    288944◊6270.17831BK, WE0.2381 x 10300.700x0.314193260BK
    639682◊4370.22542BK, WE, RD0.3051 x 8300.844441576BK
    639708◊2370.28342BK, WE, RD0.3631 x 8300.887671830BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * 2x2 construction
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 90°C
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    550482◊*1441.42.6313.2650.0581520
    288274◊1420.72.6313.2650.0581525
    639469◊1430.72.6313.2650.0581525
    550542◊1241.61.6622.0630.0542024
    288282◊1220.81.6622.0630.0542030
    639478◊1230.81.6622.0630.0542030
    555832◊1041.91.041.2910.053032
    288290◊1020.91.041.2910.053040
    639485◊1030.91.041.2910.053040
    639492◊832.30.6530.810.0524055
    288936◊821.10.6530.810.0524055
    639500◊632.70.4110.510.0515575
    288944◊621.30.4110.510.0515575
    639682◊433.40.2580.320.0487095
    639708◊233.50.1620.2010.04595130
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.052

    Updated On: Oct. 7, 2025, 7:02 p.m. UTC

    Award Winning Patent Pending Building Wire Selector
    QR Code
    Wire Strippers and Cutters
    QR Code