SPEC 48322

Tinned CU Unshielded Signal Cable 1000V

Unshielded Signal cables 1000 Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. For Direct Burial

...

Construction:

  1. Conductor:Stranded tinned copper per ASTM B33 and ASTM B8
  2. Insulation:Ethylene Propylene Rubber (EPR)
  3. Separator:Silicone polymer tape
  4. Overall Jacket:Black, Thermoset, SOLONON® Low Smoke Zero Halogen (LSZH-TS)

Applications and Features:

Southwire’s Unshielded Signal cables 1000 Volt conform to requirements in AREMA Signal Manual Part 10.3.16 and are suited for use in air, non-plenum ducts, or directly buried.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE XX AWG 90C EPR XX MILS SOLONON® 1000V SUN. RES. YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Cond. SizeStrand ClassStrand CountCond. CmilDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMax Pull Tension
    AWG/kcmilNo. of Strandscmilinchmilmilinchlb/1000ftΩ/1000ftΩ/1000ftlb
    14C1941100.07362310.275392.6313.17033
    9C19130900.13162470.365880.8250.994105
    6C19262400.17978470.4411550.4110.495209
    4C19417400.22678470.4922070.2580.310333
    2C19663600.28678630.5242230.1620.195530
    1/0B191056000.36194630.7034750.1020.122844
    2/0B191331000.40594630.7505740.0810.0971064
    3/0B191678000.45694780.8317200.0640.0781342
    350B373500000.661109781.07113740.0310.0392800
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.007