SPEC 60320

Armorlite® Type MC THHN/THWN Aluminum Conductor Feeder Cable with Green Insulated Ground 120/208V Colors

Aluminum THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Green Insulated AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground: Green Insulated aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Environmental air-handling spaces per NEC 300.22 (C).
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet

Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC AWG XX THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    4577201/03BK,RD,WE,GN0.33610601x41.568928
    4577151/03BK,RD,WE,GN0.33610601x21.329698
    4577131/03BK,RD,WE,GN0.33610601x41.302665
    6496002/03BK,RD,WE,GN0.37612601x41.318704
    4577232/03BK,RD,WE,GN0.37612601x21.406802
    4568293/03BK,RD,WE,GN0.42216601x2/01.581081
    4568273/03BK,RD,WE,GN0.42216601x31.502969
    5833824/03BK,RD,WE0.47419601x11.5841130
    4568184/03BK,RD,WE,GN0.47419601x21.6161149
    4568164/03BK,RD,WE,GN0.47419601x11.6421181
    5808934/04BK,RD,BE,WE,GN0.47419601x21.7861429
    4577632503BK,RD,WE,GN0.5222701x21.7451335
    4577652503BK,RD,WE,GN0.5222701x11.7711366
    5567932504BK,RD,BE,WE0.5222701x3/01.9621791
    5929132504BK,RD,BE,WE,GN0.5222701x1/01.9781780
    6407332504BK,RD,BE,WE,GN0.5222701x11.961731
    4577853003BK,RD,WE,GN0.56921701x11.8681552
    4577873003BK,RD,WE,GN0.56921701x21.8421521
    4577933503BK,RD,WE,GN0.61535701x11.9561727
    4577973503BK,RD,WE,GN0.61535701x4/02.0421886
    4577953503BK,RD,WE,GN0.61535701x1/01.9741755
    5980353504BK,RD,BE,WE,GN0.61535701x1/02.192262
    5612853504BK,RD,BE,WE0.61535701x4/02.22319
    5840234003BK,RD,WE0.65935701x3/02.0411943
    4578014003BK,RD,WE,GN0.65935701x3/02.12011
    4577994003BK,RD,WE,GN0.65935701x12.0391903
    4578155003BK,RD,WE,GN0.73534701x2/02.2252313
    4578175003BK,RD,WE,GN0.73534701x12.1882250
    4578155003BK,RD,WE,GN0.73534701x2/02.2212300
    5649875004BK,RD,BE,WE0.73534701x2/02.4162926
    4568816003BK,RD,WE,GN0.81258801x1/02.3852683
    4577796003BK,RD,WE,GN0.81258801x4002.5493096
    5525436004BK,RD,BE,WE0.81258801x2502.6883634
    4568587503BK,RD,WE,GN0.90853801x7502.883980
    5612627504BK,RD,BE,WE,0.90853801x6003.0594657
    1390211/04BK,RD,BE,WE,GN0.33619601x41.430840
    4577252/04BK,RD,WE,BE,GN0.37612601x41.541035
    4568203/04BK,RD,BE,WE,GN0.42216601x1/01.7151290
    4568223/04BK,RD,BE,WE0.42216601x41.6441196
    4577732504BK,RD,BE,WE,GN0.5222701x3/02.0211859
    4577752504BK,RD,BE,WE,GN0.5222701x2/01.9981815
    4577913004BK,RD,BE,WE,GN0.56921701x1/02.0891991
    4568463504BK,RD,BE,WE,GN0.61535701x4/02.2592392
    4568443504BK,RD,BE,WE,GN0.61535701x3/02.2332340
    4578074004BK,RD,BE,WE,GN0.65935701x4/02.3532625
    4578054004BK,RD,BE,WE,GN0.65935701x3502.4342803
    4578034004BK,RD,BE,WE,GN0.65935701x3/02.3282573
    4578315004BK,RD,BE,WE,GN0.73534701x3502.6043260
    4578295004BK,RD,BE,WE,GN0.73534701x3/02.4983030
    4578255004BK,RD,BE,WE,GN0.73534701x2/02.4752986
    4578135004BK,RD,BE,WE,GN0.73534701x2502.5563142
    4568696004BK,RD,BE,WE,GN0.81258801x4/02.7253621
    4568716004BK,RD,BE,WE,GN0.81258801x4002.8263858
    4568736004BK,RD,BE,WE,GN0.81258801x2502.7573681
    4568756004BK,RD,BE,WE,GN0.81258801x3502.8053798
    4568676004BK,RD,BE,WE,GN0.81258801x6002.9124106
    4568656004BK,RD,BE,WE,GN0.81258801x3/02.6993569
    4568547504BK,RD,BE,WE,GN0.90853801x3/02.9264279
    4568527504BK,RD,BE,WE,GN0.90853801x3503.0324509
    4568507504BK,RD,BE,WE,GN0.90853801x4003.0534568
    4568487504BK,RD,BE,WE,GN0.90853801x6003.144817
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Note: Conductor number = number of phase conductors. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1/031119000.1680.2010.044120135
    1/039.319000.1680.2010.044120135
    1/039.119000.1680.2010.044120135
    2/039.223950.1330.160.043135150
    2/039.823950.1330.160.043135150
    3/0311.130200.1050.1260.042155175
    3/0310.530200.1050.1260.042155175
    4/0311.138080.0840.10.041180164
    4/0311.338080.0840.10.041180205
    4/0311.538080.0840.10.041180205
    4/0412.540620.0840.10.041144164
    250312.245000.0710.0860.041205230
    250312.445000.0710.0860.041205230
    250413.748000.0710.0860.041164184
    250413.848000.0710.0860.041164184
    250413.748000.0710.0860.041164184
    300313.154000.0590.0710.041230260
    300312.954000.0590.0710.041230260
    350313.763000.050.0620.04250280
    350314.363000.050.0620.04250280
    350313.863000.050.0620.04250280
    350415.384000.050.0620.04200224
    350415.484000.050.0620.04200224
    400314.372000.0440.0540.04270305
    400314.772000.0440.0540.04270305
    400314.372000.0440.0540.04270305
    500315.690000.0350.0440.039310350
    500315.390000.0350.0440.039310350
    500315.590000.0350.0440.039310350
    500416.9120000.0350.0440.039248280
    600316.7108000.0290.0370.039340385
    600317.8108000.0290.0370.039340385
    600418.8144000.0290.0370.039272308
    750320.2135000.0240.0310.038385435
    750421.4180000.0240.0310.038308348
    1/0410.020270.1680.2010.04496108
    2/0410.825550.1330.160.043108120
    3/041232210.1050.1260.042124140
    3/0411.532210.1050.1260.042124140
    250414.148000.0710.0860.041164184
    25041448000.0710.0860.041164184
    300414.657600.0590.0710.041184208
    350415.867200.050.0620.04200224
    350415.667200.050.0620.04200224
    400416.576800.0440.0540.04216244
    40041776800.0440.0540.04216244
    400416.376800.0440.0540.04216244
    500418.296000.0350.0440.039248280
    500417.596000.0350.0440.039248280
    500417.396000.0350.0440.039248280
    500417.996000.0350.0440.039248280
    600419.1115200.0290.0370.039272308
    600419.8115200.0290.0370.039272308
    600419.3115200.0290.0370.039272308
    600419.6115200.0290.0370.039272308
    600420.4115200.0290.0370.039272308
    600418.9115200.0290.0370.039272308
    750420.5144000.0240.0310.038308348
    750421.2144000.0240.0310.038308348
    750421.4144000.0240.0310.038308348
    750422144000.0240.0310.038308348
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.