SPEC 60208

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Neutral Per Phase

Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable Neutral-per-phase products comply with NEC 200.4 requirements (added in the 2011 NEC) for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder). See NEC 200.4 for complete requirements.

Southwire Armorlite® Type MC Cable - Neutral per phase is suitable for use as follow:
- Applications affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment, and office equipment.
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire Armorlite® Type MC Cable -Neutral per phase meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    14 AWG | Solid
    674349142BK,RD,WE/BK,WE/RD,GNSolid201x142x140.50062116
    12 AWG | Solid
    554669124BE,RD,WE/BE,WE/RD,GNSolid201x122x120.5499159
    554992124BE,RD,WE/BE,WE/RD,GNSolid201x122x120.54199158
    554993124BK,BE,WE/BK,WE/BE,GNSolid201x122x120.54199158
    580818124BN,YW,GY/BN,GY/YW,GNSolid201x122x120.54199158
    580816124OE,YW,GY/OE,GY/YW,GNSolid201x122x120.54199158
    583558124RD,BE,WE/RD,WE/BE,GNSolid201x122x120.5499159
    568571128BK,RD,BE,OR,GN,GN/YW,WT,WT/BK,WT/RD,WT/BESolid202x124x120.7199293
    643572128BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GNSolid201x124x120.661179266
    6743211214BK,RD,BE,BN,OR,YW,WT/BK,WT/RD,WT/BE,WT/BN,WT/OR,WTSolid201x107x120.856332494
    556287122BK,RD,WE/BK,WE/RD,GNSolid151x122x120.5599236
    12 AWG | 19 Strands
    643872124BN,YW,GY/BN,GY/YW,GN19201x122x120.567100166
    566804124BE,RD,WE/BE,WE/RD,GN19201x122x120.567100166
    566806124BK,BE,WE/BK,WE/BE,GN19201x122x120.567100166
    589310124BN,OE,GN,GY/BN,GY/OE19201x122x120.567100166
    643875124OE,YW,GY/OE,GY/YW,GN19201x122x120.567100166
    586630124BK,BE,GN,GN/YW,WE/BE,WE/BK19202x122x120.608120194
    586628124RD,BE,GN,GN/YW,WE/BE,WE/RD19202x122x120.608120194
    551354128BK,BK/WE,WE,WE/BK,RD,RD/WE,BE,GN,BE/WE19201x122x120.688180276
    567272128BK,RD,BE,BK/WE,WE/BK,WE/RD,WE/BE,WE,GN19201x124x120.688180275
    10 AWG | Solid
    573933104OE,YW,GN,GY/OE,GY/YWSolid251x102x100.624154231
    578270104RD,BE,WE/RD,WE/BE,GNSolid251x102x100.624154232
    586593104BK,BE,WE/BK,WE/BE,GNSolid251x102x100.624154231
    587191106BK,RD,BE,OE,GN,GN/YW,WE,WE/RDSolid252x102x100.777247382
    592357108BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GNSolid251x104x100.823278424
    674302108BK,RD,BE,PK,WE/BK,WE/RD,WE/BE,WE/PK,GNSolid251x104x100.823278425
    643574108BK,RD,BE,PE,WE/BK,WE/RD,WE/BE,WE/PE,GNSolid251x104x100.823278425
    6419111010BK,RD,BE,BK/WT,RD/BK,WT,WT/BK,WT/RD,WT/BE,WT/YW,GNSolid251x105x100.883340506
    6791551012RD,WT/RD,BE,WT/BE,BK/WT,WT/BK,RD/YW,WT/YW,BE/BK,BKSolid251x105x100.951402590
    6743641012BN,BN,OR,OR,YW,YW,GY/BN,GY/BN,GY/OR,GY/OR,GY/YW,GYSolid251x106x100.946402587
    6798261012BK,BK,RD,RD,BE,BE,WT/BK,WT/BK,WT/RD,WT/RD,WT/BE,WTSolid251x106x100.946402590
    5888811012BK,RD,BE,OR,YW,BN,WT/BK,WT/RD,WT/BE,WT/OR,WT/YW,WTSolid252x106x100.946434626
    643903102BK,RD,WE/BK,WE/RD,GNSolid201x102x100.634154322
    10 AWG | 19 Strands
    646772102TAN,GY/TAN,GN19251x101x100.57197161
    587542102YW,GY/YW,GN19251x101x100.57497162
    646774102PK,GY/PK,GN19251x101x100.57197161
    646770102PE,GY/PE,GN19251x101x100.57497162
    587544102OE,GY/OE,GN19251x101x100.57497162
    597927104RD,BE,GN,WE/RD,WE/BE19251x102x100.665161250
    587183104OE,YW,GY/OE,GY/YW,GN19251x102x100.665161250
    587185104BN,YW,GY/BN,GY/YW,GN19251x102x100.665161250
    597925104BK,BE,GN,WE/BK,WE/BE19251x102x100.665161250
    674430106BK,RD,BK/BE,RD/BE,WE,WE/BE,GN19251x102x100.775226365
    679451109BK,BK,RD,RD,BE,BE,WT/BK,WT/RD,WT/BE,GN19251x103x100.944323505
    6495881010BK,RD,BK/WT,BK/RD,RD/WT,WT,WT/RD,WT/BE,WT/BK,WT/PK19251x105x100.944355544
    12 AWG | Solid
    554994121RD,WE/RD,GNSolid201x121x120.47459105
    552795122BK,RD,WE/BK,WE/RD,GNSolid201x122x120.55099159
    610666122See TableSolid202x122x120.577119187
    554991122BK,RD,GN,WE/BK,WE/RDSolid201x122x120.54199159
    610669123See TableSolid202x123x120.616159238
    554990123See TableSolid201x123x120.577139211
    566811124See TableSolid201x124x120.652179266
    643570124See TableSolid201x124x120.661179266
    643654126See TableSolid201x126x120.810259402
    580850126See TableSolid201x126x120.810259401
    674313127See TableSolid201x127x120.846299453
    641211129See TableSolid201x129x120.812369494
    10 AWG | Solid
    567063102BK,RD,WE/BK,WE/RD,GNSolid251x102x100.625154232
    552996102See TableSolid252x102x100.671185274
    641220102See TableSolid252x102x100.671185274
    556259103See TableSolid251x103x100.671216311
    610673103See TableSolid252x103x100.777247382
    554852104See TableSolid252x104x100.884309469
    567269104See TableSolid251x104x100.824278425
    677655105See TableSolid251x105x100.884340506
    590115105See TableSolid251x105x100.884340506
    585848105See TableSolid251x105x100.884342508
    566546106See TableSolid251x106x100.884340505
    679158107See TableSolid251x107x100.924468652
    12 AWG | 19 Strands
    551322122See Table19202x122x120.607120195
    566801122BK,RD,GN,WE/BK,WE/RD19201x122x120.568100167
    551324123See Table19202x123x120.649160249
    562687123See Table19201x123x120.607140220
    10 AWG | 19 Strands
    586636102See Table19252x102x100.776194325
    563822102BK,RD,GN,WE/BK,WE/RD19251x102x100.666161251
    553238103See Table19251x103x100.776226365
    587625103See Table19251x103x100.780226368
    562456103See Table19251x103x100.776226365
    551336103See Table19252x103x100.828258411
    566698104See Table19251x104x100.879291457
    647335108See Table19251x108x101.023549768
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include neutrals and green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberNeutral StrandingMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | Solid
    14223.62.6313.1700.0581620
    12 AWG | Solid
    12423.81.6622.0020.0542024
    12423.81.6622.0020.0542024
    12423.81.6622.0020.0542024
    12423.81.6622.0020.0542024
    12423.81.6622.0020.0542024
    12423.81.6622.0020.0542024
    12844.91.6622.0020.0541215
    12844.61.6622.0020.0541215
    1214761.6622.0020.0541113
    12224.61.6622.0020.0542024
    12 AWG | 19 Strands
    124241.6622.0020.0542024
    124241.6622.0020.0542024
    124241.6622.0020.0542024
    124241.6622.0020.0542024
    124241.6622.0020.0542024
    12424.31.6622.0020.0542024
    12424.31.6622.0020.0542024
    12824.81.6622.0020.0541215
    12844.81.6622.0020.0541215
    10 AWG | Solid
    10424.41.041.2530.052832
    10424.41.041.2530.052832
    10424.41.041.2530.052832
    10625.41.041.2530.052428
    10845.81.041.2530.051720
    10845.81.041.2530.051720
    10845.81.041.2530.051720
    101056.21.041.2530.051720
    101256.71.041.2530.051720
    101266.61.041.2530.051720
    101266.61.041.2530.051720
    101266.61.041.2530.051720
    10225.21.041.2530.052832
    10 AWG | 19 Strands
    102141.041.2530.053540
    102141.041.2530.053540
    102141.041.2530.053540
    102141.041.2530.053540
    102141.041.2530.053540
    10424.71.041.2530.052832
    10424.71.041.2530.052832
    10424.71.041.2530.052832
    10424.71.041.2530.052832
    10625.41.041.2530.052428
    10936.61.041.2530.051720
    101056.61.041.2530.051720
    12 AWG | Solid
    12113.41.6622.0020.0542530
    12223.81.6622.0020.0542024
    12224.11.6622.0020.0542024
    12223.81.6622.0020.0542024
    12334.41.6622.0020.0542024
    12334.11.6622.0020.0542024
    12444.61.6622.0020.0541721
    12444.61.6622.0020.0541721
    12665.71.6622.0020.0541215
    12665.71.6622.0020.0541215
    12775.91.6622.0020.0541215
    12995.71.6622.0020.0541215
    10 AWG | Solid
    10224.41.0401.2530.0502832
    10224.81.0401.2530.0502832
    10224.81.0401.2530.0502832
    10334.81.0401.2530.0502832
    10335.41.0401.2530.0502832
    10446.21.0401.2530.0502428
    10445.81.0401.2530.0502428
    10556.21.0401.2530.0501720
    10556.21.0401.2530.0501720
    10556.21.0401.2530.0501720
    10666.21.0401.2530.0501720
    10776.51.0401.2530.0501720
    12 AWG | 19 Strands
    12224.31.6622.0020.0542024
    12224.01.6622.0020.0542024
    12334.61.6622.0020.0542024
    12334.31.6622.0020.0542024
    10 AWG | 19 Strands
    10225.41.0401.2530.0502832
    10224.71.0401.2530.0502832
    10335.41.0401.2530.0502832
    10335.51.0401.2530.0502832
    10335.41.0401.2530.0502832
    10335.81.0401.2530.0502832
    10446.11.0401.2530.0502428
    10887.21.0401.2530.0501720
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - Conductor number = number of phase conductors. Does not include neutrals and green ground. ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond NumberStock CodeColor
    14 (Solid)2674349BK, RD, WE/BK, WE/RD, GN
    12 (Solid)1554994RD, WE/RD, GN
    12 (Solid)2554991BK, RD, GN, WE/BK, WE/RD
    12 (Solid)2610666BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (Solid)2552795BK, RD, WE/BK, WE/RD, GN
    12 (Solid)3554990BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    12 (Solid)3610669BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    12 (Solid)4566811BK, RD, BE, BK/WE, WE, WE/RD, WE/BE, WE/BK, GN
    12 (Solid)4643570BK, RD, BE, PE, WE/BK, WE/RD, WE/BE, WE/PE, GN
    12 (Solid)6643654BK, RD, BE, PK, PE, YW, GN, WE/BK, WE/RD, WE/BE, WE/PK, WE/PE, WE/YW
    12 (Solid)6580850BK, RD, BE, BK/RD, RD/BE, BE/BK, GN, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD
    12 (Solid)7674313BK, RD, BE, BK/YW, RD/YW, BE/YW, BK/RD, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD, WE/BE, GN
    12 (Solid)9641211BK, BK, BK, RD, RD, RD, BE, BE, BE, WE, WE, WE, WE, WE, WE, WE, WE, WE, GN
    10 (Solid)2567063BK, RD, WE/BK, WE/RD, GN
    10 (Solid)2641220BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (Solid)2552996BK, RD, WE, WE/BE, GN, GN/YW
    10 (Solid)3556259BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (Solid)3610673BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (Solid)4567269BK, RD, BE, BK/WE, GN, WE/BK, WE/RD, WE/BE, WE
    10 (Solid)4554852BK, RD, BE, BK/RD, WE, WE/BK, WE/RD, GN, GN/YW, WE/BE
    10 (Solid)5590115BK, BK, RD, RD, BE, WE/BK, WE/BK, WE/RD, WE/RD, WE/BE, GN
    10 (Solid)5677655BK, RD, BE, BK/RD, RD/BK, WE, WE/BK, WE/RD, WE/BE, WE/PK, GN
    10 (Solid)5585848BK, RD, BE, WE/BK, WE/RD, WE/BE, BK/BN, RD/OE, WE/BN, WE/OE, GN
    10 (Solid)7679158BK, WE, RD, WE/RD, BE, WE/BE, BK/WE, WE/BK, RD/YW, WE/YW, BE/OE, WE/OE, PE, WE/PE, GN
    12 (19)2566801BK, RD, GN, WE/BK, WE/RD
    12 (19)2551322BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (19)3562687BK, RD, BE, WE/BK, WE/RD, WE/BE, GN
    12 (19)3551324BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)2563822BK, RD, GN, WE/BK, WE/RD
    10 (19)2586636BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (19)3553238BK, RD, BE, WE, WE/BK, GN, WE/RD
    10 (19)3562456BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (19)3551336BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)3587625BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (19)4566698BK, BK/WE, RD, BE, GN, WE, WE/BK, WE/RD, WE/BE
    10 (19)8647335BK, BK, BK, BK, BK, BK, BK, BK, WE, WE, WE, WE, WE, WE, WE, WE, GN

    Revision: 1.000.021

    Updated On: April 4, 2025, 6:59 p.m. UTC