SPEC 60208

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Neutral Per Phase

Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Contact Southwire SPEED™ Services to request a quote.

Applications and Features:

Southwire Armorlite® Type MC Cable Neutral-per-phase products comply with NEC 200.4 requirements (added in the 2011 NEC) for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder). See NEC 200.4 for complete requirements.

Southwire Armorlite® Type MC Cable - Neutral per phase is suitable for use as follow:
  • Applications affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment, and office equipment.
  • Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.

  • Southwire Armorlite® Type MC Cable -Neutral per phase meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    10 AWG | Solid
    5672691040.101Solid251x104x100.823278425
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include neutrals and green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    10 AWG | Solid
    1045.81.0401.2530.0502428
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table

    Stock Num.Cond. SizeCond. Num.1234567891011121314151617
    674349142BlackRedGreenWhite/BlackWhite/Red            
    554994122RedGreenWhite/Red              
    551322122BlackRedGreenWhite/BlackWhite/RedGreen/Yellow           
    552795124BlackRedGreenWhite/BlackWhite/Red            
    554991122BlackRedGreenWhite/BlackWhite/Red            
    566801122BlackRedGreenWhite/BlackWhite/Red            
    610666122BlackRedGreenWhite/BlackWhite/RedGreen/Yellow           
    551324123BlackRedBlueGreenWhite/BlackWhite/RedWhite/BlueGreen/Yellow         
    551353124BlackRedWhiteBlack/WhiteGreenWhite/BlackWhite/Red          
    554990123BlackRedBlueGreenWhite/BlackWhite/RedWhite/Blue          
    562687123BlackRedBlueGreenWhite/BlackWhite/RedWhite/Blue          
    610669123BlackRedBlueGreenWhite/BlackWhite/RedWhite/BlueGreen/Yellow         
    566811124BlackRedBlueWhiteBlack/WhiteGreenWhite/BlackWhite/RedWhite/Blue        
    643570124BlackRedBluePurpleWhite/BlackWhite/RedWhite/BlueWhite/Purple         
    589122126BlackRedBlueWhiteBlack/WhiteRed/WhiteBlue/WhiteGreenWhite/BlackWhite/RedWhite/Blue      
    580850126BlackRedBlueWhiteBlack/RedRed/BlueBlue/BlackGreen2XWhite/Black2XWhite/RedWhite/Blue      
    643654126BlackRedBlueYellowPinkPurpleGreenWhite/BlackWhite/RedWhite/BlueWhite/YellowWhite/PinkWhite/Purple    
    674313127BlackRedBlueWhiteBlack/RedRed/YellowBlue/YellowGreen2XWhite/Black2XWhite/Red2XWhite/Blue      
    67937012103XBlackRed3XWhiteBlack/WhiteBlack/RedRed/BlackRed/WhiteBlue/WhiteBlue/RedGreenWhite/BlackWhite/RedWhite/Blue    
    6412111293XBlack3XRed3XBlue9XWhiteGreen            
    552996102BlackRedWhiteGreenWhite/BlueGreen/Yellow           
    563822102BlackRedGreenWhite/BlackWhite/Red            
    567063102BlackRedGreenWhite/BlackWhite/Red            
    586636102BlackRedGreenWhite/BlackWhite/RedGreen/Yellow           
    641220102BlackRedGreenWhite/BlackWhite/RedGreen/Yellow           
    551336103BlackRedBlueGreenWhite/BlackWhite/RedWhite/BlueGreen/Yellow         
    553238103BlackRedBlueWhiteGreenWhite/BlackWhite/Red          
    556259103BlackRedBlueGreenWhite/BlackWhite/RedWhite/Blue          
    562456103BlackRedBlueGreenWhite/BlackWhite/RedWhite/Blue          
    592678103BlackRedBlueGreenWhite/BlackWhite/RedWhite/Blue          
    610673103BlackRedBlueGreenWhite/BlackWhite/RedWhite/BlueGreen/Yellow         
    674737104BlackRedWhiteBlack/WhiteRed/WhiteGreenWhite/Black          
    551356108BlackRedBlueWhiteBlack/WhiteRed/WhiteBlue/WhiteGreenWhite/Black        
    554852104BlackRedBlueWhiteBlack/RedGreenWhite/BlackWhite/RedWhite/BlueGreen/Yellow       
    566698104BlackRedBlueWhiteBlack/WhiteGreenWhite/BlackWhite/RedWhite/Blue        
    640523105BlackRedBlueOrangeYellowGreenWhite/BlackWhite/RedWhite/OrangeWhite/Yellow       
    585848105BlackRedBlueBlack/BrownRed/OrangeGreenWhite/BlackWhite/RedWhite/BlueWhite/BrownWhite/Orange      
    5901151052XBlack2XRedBlueGreen2XWhite/Black2XWhite/RedWhite/Blue          
    598031106BlackRedBlueWhiteBlack/WhiteRed/WhiteBlue/WhiteGreenWhite/BlackWhite/RedWhite/Blue      
    677655105BlackRedBlueWhiteBlack/RedRed/BlackGreenWhite/BlackWhite/RedWhite/BlueWhite/Pink      
    6474881066XBlack6XWhiteGreen              
    679158107BlackRedBlueWhitePurpleBlack/WhiteRed/YellowBlue/OrangeWhite/BlackWhite/RedWhite/BlueWhite/OrangeWhite/YellowWhite/Purple   
    6473351088XBlack8XWhiteGreen              
    6791611016BlackRedBlueWhitePinkPurpleBlack/WhiteRed/YellowBlue/OrangeGreenWhite/BlackWhite/RedWhite/BlueWhite/OrangeWhite/YellowWhite/PinkWhite/Purple

    Revision: 1.000.010

    Updated On: July 3, 2024, 10:13 p.m. UTC