SPEC 60208

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Neutral Per Phase

Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strands class C compressed copper per ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable Neutral-per-phase products comply with NEC 200.4 requirements (added in the 2011 NEC) for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder). See NEC 200.4 for complete requirements.

Southwire Armorlite® Type MC Cable (neutral per phase) is suitable for use as follow:
• Applications affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment, and office equipment
• Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Type THHN/THWN rated 90ºC dry

Southwire Armorlite® Type MC Cable (neutral per phase) meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    14 AWG | SOLID Strands
    674349144BK,RD,WE/BK,WE/RD,GN0.064SOLID151x142x140.563116
    12 AWG | SOLID Strands
    554994122RD,WE/RD,GN0.081SOLID151x121x120.47460105
    554992124BE,RD,WE/BE,WE/RD,GN0.081SOLID151x122x120.541100159
    552795124BK,RD,WE/BK,WE/RD,GN0.081SOLID151x122x120.55100160
    554669124BE,RD,WE/BE,WE/RD,GN0.081SOLID151x122x120.541100159
    610666124SEE TABLE0.081SOLID152x122x120.578120186
    554993124BK,BE,WE/BK,WE/BE,GN0.081SOLID151x122x120.541100159
    580818124BN,YW,GY/BN,GY/YW,GN0.081SOLID151x122x120.541100159
    580816124OE,YW,GY/OE,GY/YW,GN0.081SOLID151x122x120.541100159
    583558124RD,BE,WE/RD,WE/BE,GN0.081SOLID151x122x120.541100159
    554991124BK,RD,GN,WE/BK,WE/RD0.081SOLID151x122x120.541100159
    610669126SEE TABLE0.081SOLID152x123x120.616160237
    554990126SEE TABLE0.081SOLID151x123x120.578140210
    568571128BK,RD,BE,OR,GN,GN/YW,WT,WT/BK,WT/RD,WT/BE0.081SOLID152x124x120.7200294
    643570128SEE TABLE0.081SOLID151x124x120.661180266
    566811128SEE TABLE0.081SOLID151x124x120.653180265
    5808501212SEE TABLE0.081SOLID151x126x120.81259401
    6436541212SEE TABLE0.081SOLID151x126x120.81259402
    6743211214BK,RD,BE,BN,OE,YW,WT/BK,WT/RD,WT/BE,WT/BN0.081SOLID151x107x120.856332494
    6743131214SEE TABLE0.081SOLID151x127x120.846299453
    556287124BK,RD,WE/BK,WE/RD,GN0.081SOLID151x122x120.55100237
    643572128BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GN0.081SOLID151x124x120.661180266
    12 AWG | 19 Strands
    566804124BE,RD,WE/BE,WE/RD,GN0.08919151x122x120.568100167
    566806124BK,BE,WE/BK,WE/BE,GN0.08919151x122x120.568100167
    589310124BN,OE,GN,GY/BN,GY/OE0.08919151x122x120.568100166
    643872124BN,YW,GY/BN,GY/YW,GN0.08919151x122x120.568100167
    643875124OE,YW,GY/OE,GY/YW,GN0.08919151x122x120.568100167
    586630124BK,BE,GN,GN/YW,WE/BE,WE/BK0.08919152x122x120.608121194
    586628124RD,BE,GN,GN/YW,WE/BE,WE/RD0.08919152x122x120.608121194
    567272128BK,RD,BE,BK/WE,WE/BK,WE/RD,WE/BE,WE,GN0.08919151x124x120.688181276
    551322124SEE TABLE0.0919152x122x120.607121195
    566801124BK,RD,GN,WE/BK,WE/RD0.0919151x122x120.568100166
    562687126SEE TABLE0.0919151x123x120.608141219
    551324126SEE TABLE0.0919152x123x120.649161248
    10 AWG | SOLID Strands
    567063104BK,RD,WE/BK,WE/RD,GN0.102SOLID201x102x100.625155232
    552996104SEE TABLE0.102SOLID202x102x100.671186274
    641220104SEE TABLE0.102SOLID202x102x100.671186274
    586593104BK,BE,WE/BK,WE/BE,GN0.102SOLID201x102x100.624155232
    573933104OE,YW,GN,GY/OE,GY/YW0.102SOLID201x102x100.624155232
    578270104RD,BE,WE/RD,WE/BE,GN0.102SOLID201x102x100.624155232
    610673106SEE TABLE0.102SOLID202x103x100.777248383
    556259106SEE TABLE0.102SOLID201x103x100.671217311
    643574108BK,RD,BE,PE,WE/BK,WE/RD,WE/BE,WE/PE,GN0.102SOLID201x104x100.824278425
    674302108BK,RD,BE,PK,WE/BK,WE/RD,WE/BE,WE/PK,GN0.102SOLID201x104x100.824278425
    567269108SEE TABLE0.102SOLID201x104x100.824278425
    592357108BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GN0.102SOLID201x104x100.824278425
    554852108SEE TABLE0.102SOLID202x104x100.884309469
    6419111010BK,RD,BE,BK/WT,RD/BK,WT,WT/BK,WT/RD,WT/BE,WT/YW,GN0.102SOLID201x105x100.884340506
    5901151010SEE TABLE0.102SOLID201x105x100.884340506
    5858481010SEE TABLE0.102SOLID201x105x100.884343509
    6776551010SEE TABLE0.102SOLID201x105x100.884340506
    5665461012SEE TABLE0.102SOLID201x106x100.947402588
    5888811012BK,RD,BE,OR,YW,BN,WT/BK,WT/RD,WT/BE,WT/OR,WT/YW,WT0.102SOLID202x106x100.947435626
    6798261012BK,BK,RD,RD,BE,BE,WT/BK,WT/BK,WT/RD,WT/RD,WT/BE,WT0.102SOLID201x106x100.947402591
    6743641012BN,BN,OR,OR,YW,YW,GY/BN,GY/BN,GY/OR,GY/OR,GY/YW,GY0.102SOLID201x106x100.947402587
    6791581014SEE TABLE0.102SOLID201x107x100.993465669
    643903104BK,RD,WE/BK,WE/RD,GN0.102SOLID201x102x100.634155322
    10 AWG | 19 Strands
    646772102TAN,GY/TAN,GN0.11319201x101x100.57297162
    587544102OE,GY/OE,GN0.11319201x101x100.57497163
    646770102PE,GY/PE,GN0.11319201x101x100.57497163
    646774102PK,GY/PK,GN0.11319201x101x100.57297162
    587542102YW,GY/YW,GN0.11319201x101x100.57497163
    597925104BK,BE,GN,WE/BK,WE/BE0.11319201x102x100.666162251
    587185104BN,YW,GY/BN,GY/YW,GN0.11319201x102x100.666162251
    587183104OE,YW,GY/OE,GY/YW,GN0.11319201x102x100.666162251
    597927104RD,BE,GN,WE/RD,WE/BE0.11319201x102x100.666162251
    6495881010BK,RD,BK/WT,BK/RD,RD/WT,WT,WT/RD,WT/BE,WT/BK,WT/PK0.11319201x105x100.945356545
    563822104BK,RD,GN,WE/BK,WE/RD0.11719201x102x100.666162251
    586636104SEE TABLE0.11719202x102x100.776194326
    562456106SEE TABLE0.11719201x103x100.775226366
    553238106SEE TABLE0.11719201x103x100.776226366
    551336106SEE TABLE0.11719202x103x100.828259412
    566698108SEE TABLE0.11719201x104x100.879291457
    6473351016SEE TABLE0.11719201x108x101.117550804
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • Note: Conductor number = number of phase conductors and neutral. Does not include green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | SOLID Strands
    1443.52.6313.2650.0581620
    12 AWG | SOLID Strands
    1223.31.6622.0630.0542530
    1243.81.6622.0630.0542024
    1243.91.6622.0630.0542024
    1243.81.6622.0630.0542024
    12441.6622.0630.0542024
    1243.81.6622.0630.0542024
    1243.81.6622.0630.0542024
    1243.81.6622.0630.0542024
    1243.81.6622.0630.0542024
    1243.81.6622.0630.0542024
    1264.31.6622.0630.0542024
    12641.6622.0630.0542024
    1284.91.6622.0630.0541821
    1284.61.6622.0630.0541821
    1284.61.6622.0630.0541821
    12125.71.6622.0630.0541215
    12125.71.6622.0630.0541215
    121461.6622.0630.0541215
    12145.91.6622.0630.0541215
    1244.61.6622.0630.0542024
    1284.61.6622.0630.0541821
    12 AWG | 19 Strands
    12441.6622.0630.0542024
    12441.6622.0630.0542024
    12441.6622.0630.0542024
    12441.6622.0630.0542024
    12441.6622.0630.0542024
    1244.31.6622.0630.0542024
    1244.31.6622.0630.0542024
    1284.81.6622.0630.0541821
    1244.21.6622.0630.0542024
    12441.6622.0630.0542024
    1264.31.6622.0630.0542024
    1264.51.6622.0630.0542024
    10 AWG | SOLID Strands
    1044.41.041.2910.052832
    1044.71.041.2910.052832
    1044.71.041.2910.052832
    1044.41.041.2910.052832
    1044.41.041.2910.052832
    1044.41.041.2910.052832
    1065.41.041.2910.052832
    1064.71.041.2910.052832
    1085.81.041.2910.052428
    1085.81.041.2910.052428
    1085.81.041.2910.052428
    1085.81.041.2910.052428
    1086.21.041.2910.052428
    10106.21.041.2910.051820
    10106.21.041.2910.051820
    10106.21.041.2910.051820
    10106.21.041.2910.051820
    10126.61.041.2910.051820
    10126.61.041.2910.051820
    10126.71.041.2910.051820
    10126.61.041.2910.051820
    101471.041.2910.051820
    1045.21.041.2910.052832
    10 AWG | 19 Strands
    10241.041.2910.053540
    10241.041.2910.053540
    10241.041.2910.053540
    10241.041.2910.053540
    10241.041.2910.053540
    1044.71.041.2910.052832
    1044.71.041.2910.052832
    1044.71.041.2910.052832
    1044.71.041.2910.052832
    10106.61.041.2910.051820
    1044.71.041.2910.052832
    1045.41.041.2910.052832
    1065.41.041.2910.052832
    1065.41.041.2910.052832
    1065.81.041.2910.052832
    1086.21.041.2910.052428
    10167.81.041.2910.051820
    • Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - Conductor number = number of phase conductors. Does not include neutrals and green ground. ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond NumberStock CodeColor
    14 (Solid)2674349BK, RD, WE/BK, WE/RD, GN
    12 (Solid)1554994RD, WE/RD, GN
    12 (Solid)2554991BK, RD, GN, WE/BK, WE/RD
    12 (Solid)2610666BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (Solid)2552795BK, RD, WE/BK, WE/RD, GN
    12 (Solid)3554990BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    12 (Solid)3610669BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    12 (Solid)4566811BK, RD, BE, BK/WE, WE, WE/RD, WE/BE, WE/BK, GN
    12 (Solid)4643570BK, RD, BE, PE, WE/BK, WE/RD, WE/BE, WE/PE, GN
    12 (Solid)6643654BK, RD, BE, PK, PE, YW, GN, WE/BK, WE/RD, WE/BE, WE/PK, WE/PE, WE/YW
    12 (Solid)6580850BK, RD, BE, BK/RD, RD/BE, BE/BK, GN, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD
    12 (Solid)6674321BK, RD, BE, BN, OE, YW, WE/BK, WE/RD, WE/BE, WE/BN, WE/OE, WE/YW, BK, WE/BK, GN
    12 (Solid)7674313BK, RD, BE, BK/YW, RD/YW, BE/YW, BK/RD, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD, WE/BE, GN
    10 (Solid)2567063BK, RD, WE/BK, WE/RD, GN
    10 (Solid)2641220BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (Solid)2552996BK, RD, WE, WE/BE, GN, GN/YW
    10 (Solid)3556259BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (Solid)3610673BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (Solid)4567269BK, RD, BE, BK/WE, GN, WE/BK, WE/RD, WE/BE, WE
    10 (Solid)4554852BK, RD, BE, BK/RD, WE, WE/BK, WE/RD, GN, GN/YW, WE/BE
    10 (Solid)5590115BK, BK, RD, RD, BE, WE/BK, WE/BK, WE/RD, WE/RD, WE/BE, GN
    10 (Solid)5677655BK, RD, BE, BK/RD, RD/BK, WE, WE/BK, WE/RD, WE/BE, WE/PK, GN
    10 (Solid)6566546BK, BK/WE, BE, BE/WE, RD, RD/WE, WE/RD, WE/RD, WE/BE, WE/BE, WE/BK, WE/BK, GN
    10 (Solid)7679158BK, WE, RD, WE/RD, BE, WE/BE, BK/WE, WE/BK, RD/YW, WE/YW, BE/OE, WE/OE, PE, WE/PE, GN
    12 (19)2566801BK, RD, GN, WE/BK, WE/RD
    12 (19)2551322BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (19)3562687BK, RD, BE, WE/BK, WE/RD, WE/BE, GN
    12 (19)3551324BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)2563822BK, RD, GN, WE/BK, WE/RD
    10 (19)2586636BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (19)3553238BK, RD, BE, WE, WE/BK, GN, WE/RD
    10 (19)3562456BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (19)3551336BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)4566698BK, BK/WE, RD, BE, GN, WE, WE/BK, WE/RD, WE/BE
    10 (19)8647335BK, BK, BK, BK, BK, BK, BK, BK, WE, WE, WE, WE, WE, WE, WE, WE, GN

    Revision: 1.000.029

    Updated On: Oct. 13, 2026, 8:41 p.m. UTC