SPEC 83353

Covered Line Wire With Crosslinked Polyethylene (XLPE)

Aluminum Conductor Covered with Black Crosslinked Polyethylene

...

Construction:

  1. Conductor:Solid 1350-H19 aluminum per ASTM B230, compressed stranded 1350-H19 aluminum per ASTM B230 and B231, or concentrically stranded 6201-T81 aluminum-alloy per ASTM B398 and B399
  2. Covering:Black Crosslinked Polyethylene (XLPE)

Applications and Features:

Aluminum alloy 1350-H19 or 6201-T81 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:

• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
  • ASTM B399 Standard Specification for Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Sample Print Legend:

    Solid Conductor:
    SOUTHWIRE AWG X AL {MMM/DD/YYYY}

    AAC Conductor:
    SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP

    AAAC Conductor:
    SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
    Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandPhase Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.milinchlb/1000ft
    TBAApple6Solid300.22231
    TBAPlum67300.23856
    457350Pear4Solid300.26447
    663570Apricot47300.28551
    TBACherry2Solid450.34878
    104240Peach27450.37384
    TBANectarine17450.408104
    104257Quince1/07600.477136
    TBAOrange2/07600.522167
    104273Fig3/07600.57205
    104281Olive4/07600.626248
    104299Pomegranate4/019600.632247
    TBAMulberry266.819600.694305
    104315Annona336.419600.765377
    148130Chinquapin35019600.778390
    TBAMolles397.519800.861462
    104331Huckleberry47737800.931538
    104349Paw Paw556.537800.992619
    202127Breadfruit63661951.081715
    148460Persimmon79561951.186877
    202135Grapefruit1033.561951.3261128
    TBAHornbeam473031060
    104547Linden274540699
    104554Oilnut1/0760518159
    TBAWaterash2/0760567195
    104570Shellbark3/0760622240
    TBAPlanetree4/0760683297
    All dimensions are nominal and subject to normal manufacturing tolerances
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthAllowable Ampacity In Air 75/90°C
    AWG/KcmillbAmp
    Apple6445105
    Plum6510105
    Pear4710135
    Apricot4790140
    Cherry21100180
    Peach21220180
    Nectarine11470210
    Quince1/01790240
    Orange2/02260280
    Fig3/02740320
    Olive4/03450370
    Pomegranate4/03620370
    Mulberry266.84470430
    Annona336.45540495
    Chinquapin3505751506
    Molles397.56400545
    Huckleberry4777820610
    Paw Paw556.58950670
    Breadfruit63610500720
    Persimmon79512900825
    Grapefruit1033.516500970
    Hornbeam41360145
    Linden22160190
    Oilnut1/03440250
    Waterash2/04160290
    Shellbark3/05240335
    Planetree4/06610385

    Revision: 1.000.013

    Updated On: Aug. 31, 2026, 10:15 p.m. UTC