SPEC 83353

Covered Line Wire With Crosslinked Polyethylene (XLPE)

Aluminum Conductor Covered with Black Crosslinked Polyethylene

...

Construction:

  1. Conductor:Solid 1350-H19 aluminum per ASTM B230, compressed stranded 1350-H19 aluminum per ASTM B230 and B231, or concentrically stranded 6201-T81 aluminum-alloy per ASTM B398 and B399
  2. Covering:Black Crosslinked Polyethylene (XLPE)

Applications and Features:

Aluminum alloy 1350-H19 or 6201-T81 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:

• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
  • ASTM B399 Standard Specification for Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Sample Print Legend:

    Solid Conductor:
    SOUTHWIRE AWG X AL {MMM/DD/YYYY}

    AAC Conductor:
    SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP

    AAAC Conductor:
    SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
    Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandPhase Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.milinchlb/1000ft
    104547LINDEN77.477450.40698
    104554OILNUT123.37600.518158
    104570SHELLBARK195.77600.622239
    104331HUCKLEBERRY47737800.931540
    104349PAW PAW556.537800.992622
    202127BREADFRUIT63661951.081721
    148460PERSIMMON79561951.187885
    202135GRAPEFRUIT1033.561951.3271128
    TBAAPPLE6SOLID450.25241
    TBAPLUM67450.26842
    457350PEAR4SOLID300.26447
    663570APRICOT47300.28550
    TBAHORNBEAM47450.31560
    TBACHERRY2SOLID450.34885
    104240PEACH27450.37383
    TBANECTARINE17600.442118
    104257QUINCE1/07600.477134
    TBAORANGE2/07600.525171
    TBAWATERASH2/07600.525171
    104273FIG3/07600.57202
    104281OLIVE4/07600.626248
    TBAPLANETREE4/07600.632255
    104299POMEGRANATE4/019600.632246
    104315ANNONA336.419600.766375
    148130CHINQUAPIN35019600.778390
    All dimensions are nominal and subject to normal manufacturing tolerances
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. Size
    AWG/Kcmil
    LINDEN77.47
    OILNUT123.3
    SHELLBARK195.7
    HUCKLEBERRY477
    PAW PAW556.5
    BREADFRUIT636
    PERSIMMON795
    GRAPEFRUIT1033.5
    APPLE6
    PLUM6
    PEAR4
    APRICOT4
    HORNBEAM4
    CHERRY2
    PEACH2
    NECTARINE1
    QUINCE1/0
    ORANGE2/0
    WATERASH2/0
    FIG3/0
    OLIVE4/0
    PLANETREE4/0
    POMEGRANATE4/0
    ANNONA336.4
    CHINQUAPIN350

    Revision: 1.000.013

    Updated On: Aug. 31, 2026, 10:15 p.m. UTC