SPEC 83353
Covered Line Wire With Crosslinked Polyethylene (XLPE)
Aluminum Conductor Covered with Black Crosslinked Polyethylene

Construction:
- Conductor:Solid 1350-H19 aluminum per ASTM B230, compressed stranded 1350-H19 aluminum per ASTM B230 and B231, or concentrically stranded 6201-T81 aluminum-alloy per ASTM B398 and B399
- Covering:Black Crosslinked Polyethylene (XLPE)
Applications and Features:
Aluminum alloy 1350-H19 or 6201-T81 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:
• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC
• Normal Service temperature of 90ºC
• Emergency Overload of 130ºC
• Short Circuit temperature of 250ºC
Specifications:
Sample Print Legend:
Solid Conductor:
SOUTHWIRE AWG X AL {MMM/DD/YYYY}
AAC Conductor:
SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP
AAAC Conductor:
SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
SOUTHWIRE AWG X AL {MMM/DD/YYYY}
AAC Conductor:
SOUTHWIRE® XXX.X AWG or KCMIL AAC XX MILS XLP
AAAC Conductor:
SOUTHWIRE® XXX.X KCMIL AAAC XX MILS XLP
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Phase Insul. Thickness | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | ||
| TBA | Apple | 6 | Solid | 30 | 0.222 | 31 |
| TBA | Plum | 6 | 7 | 30 | 0.238 | 56 |
| 457350 | Pear | 4 | Solid | 30 | 0.264 | 47 |
| 663570 | Apricot | 4 | 7 | 30 | 0.285 | 51 |
| TBA | Cherry | 2 | Solid | 45 | 0.348 | 78 |
| 104240 | Peach | 2 | 7 | 45 | 0.373 | 84 |
| TBA | Nectarine | 1 | 7 | 45 | 0.408 | 104 |
| 104257 | Quince | 1/0 | 7 | 60 | 0.477 | 136 |
| TBA | Orange | 2/0 | 7 | 60 | 0.522 | 167 |
| 104273 | Fig | 3/0 | 7 | 60 | 0.57 | 205 |
| 104281 | Olive | 4/0 | 7 | 60 | 0.626 | 248 |
| 104299 | Pomegranate | 4/0 | 19 | 60 | 0.632 | 247 |
| TBA | Mulberry | 266.8 | 19 | 60 | 0.694 | 305 |
| 104315 | Annona | 336.4 | 19 | 60 | 0.765 | 377 |
| 148130 | Chinquapin | 350 | 19 | 60 | 0.778 | 390 |
| TBA | Molles | 397.5 | 19 | 80 | 0.861 | 462 |
| 104331 | Huckleberry | 477 | 37 | 80 | 0.931 | 538 |
| 104349 | Paw Paw | 556.5 | 37 | 80 | 0.992 | 619 |
| 202127 | Breadfruit | 636 | 61 | 95 | 1.081 | 715 |
| 148460 | Persimmon | 795 | 61 | 95 | 1.186 | 877 |
| 202135 | Grapefruit | 1033.5 | 61 | 95 | 1.326 | 1128 |
| TBA | Hornbeam | 4 | 7 | 30 | 310 | 60 |
| 104547 | Linden | 2 | 7 | 45 | 406 | 99 |
| 104554 | Oilnut | 1/0 | 7 | 60 | 518 | 159 |
| TBA | Waterash | 2/0 | 7 | 60 | 567 | 195 |
| 104570 | Shellbark | 3/0 | 7 | 60 | 622 | 240 |
| TBA | Planetree | 4/0 | 7 | 60 | 683 | 297 |
All dimensions are nominal and subject to normal manufacturing tolerances
• TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | Allowable Ampacity In Air 75/90°C |
|---|---|---|---|
| AWG/Kcmil | lb | Amp | |
| Apple | 6 | 445 | 105 |
| Plum | 6 | 510 | 105 |
| Pear | 4 | 710 | 135 |
| Apricot | 4 | 790 | 140 |
| Cherry | 2 | 1100 | 180 |
| Peach | 2 | 1220 | 180 |
| Nectarine | 1 | 1470 | 210 |
| Quince | 1/0 | 1790 | 240 |
| Orange | 2/0 | 2260 | 280 |
| Fig | 3/0 | 2740 | 320 |
| Olive | 4/0 | 3450 | 370 |
| Pomegranate | 4/0 | 3620 | 370 |
| Mulberry | 266.8 | 4470 | 430 |
| Annona | 336.4 | 5540 | 495 |
| Chinquapin | 350 | 5751 | 506 |
| Molles | 397.5 | 6400 | 545 |
| Huckleberry | 477 | 7820 | 610 |
| Paw Paw | 556.5 | 8950 | 670 |
| Breadfruit | 636 | 10500 | 720 |
| Persimmon | 795 | 12900 | 825 |
| Grapefruit | 1033.5 | 16500 | 970 |
| Hornbeam | 4 | 1360 | 145 |
| Linden | 2 | 2160 | 190 |
| Oilnut | 1/0 | 3440 | 250 |
| Waterash | 2/0 | 4160 | 290 |
| Shellbark | 3/0 | 5240 | 335 |
| Planetree | 4/0 | 6610 | 385 |
Revision: 1.000.013
Updated On: Aug. 31, 2026, 10:15 p.m. UTC