SPEC 83354
Covered Line Wire With Thermoplastic Polyethylene (PE)
Aluminum Conductor Covered with Black Polyethylene (PE)

Construction:
- Conductor:Conductors are solid or stranded compressed aluminum
- Covering:Black Polyethylene (PE)
Applications and Features:
Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with Black Polyethylene (PE). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Black Polyethylene (PE) covered line wires have the below temperature ratings:
Normal Service temperature of 75ºC Emergency Overload of 95ºC Short Circuit temperature of 150ºC
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Phase Insul. Thickness | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | ||
| TBA | Apple | 6 | Solid | 30 | 0.222 | 31 |
| TBA | Plum | 6 | 7 | 30 | 0.238 | 56 |
| TBA | Pear | 4 | Solid | 30 | 0.264 | 47 |
| 102145 | Apricot | 4 | 7 | 30 | 0.285 | 51 |
| 102442 | Hornbeam | 4 | 7 | 30 | 0.310 | 60 |
| TBA | Cherry | 2 | Solid | 45 | 0.348 | 78 |
| 102152 | Peach | 2 | 7 | 45 | 0.373 | 84 |
| TBA | Linden | 2 | 7 | 45 | 0.406 | 99 |
| TBA | Nectarine | 1 | 7 | 45 | 0.408 | 104 |
| 102160 | Quince | 1/0 | 7 | 60 | 0.477 | 136 |
| 102467 | Oilnut | 1/0 | 7 | 60 | 0.518 | 159 |
| TBA | Orange | 2/0 | 7 | 60 | 0.522 | 167 |
| TBA | Waterash | 2/0 | 7 | 60 | 0.567 | 195 |
| 102186 | Fig | 3/0 | 7 | 60 | 0.570 | 205 |
| TBA | Shellbark | 3/0 | 7 | 60 | 0.622 | 240 |
| 102194 | Olive | 4/0 | 7 | 60 | 0.626 | 253 |
| TBA | Pomegranate | 4/0 | 19 | 60 | 0.632 | 247 |
| 102491 | Planetree | 4/0 | 7 | 60 | 0.683 | 297 |
| TBA | Mulberry | 266.8 | 19 | 60 | 0.694 | 305 |
| 621974 | Annona | 336.4 | 19 | 60 | 0.765 | 377 |
| 102228 | Annona | 336.4 | 19 | 60 | 0.765 | 377 |
| 102236 | Molles | 397.5 | 19 | 80 | 0.861 | 462 |
| 102244 | Huckleberry | 477 | 37 | 80 | 0.931 | 538 |
| TBA | Paw Paw | 556.5 | 37 | 80 | 0.992 | 619 |
| TBA | Breadfruit | 636 | 61 | 95 | 1.081 | 715 |
| 102269 | Persimmon | 795 | 61 | 95 | 1.186 | 877 |
| TBA | Grapefruit | 1033.5 | 61 | 95 | 1.326 | -- |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | Allowable Ampacity In Air 75/90°C |
|---|---|---|---|
| AWG/Kcmil | lb | Amp | |
| Apple | 6 | 445 | 83 |
| Plum | 6 | 510 | 84 |
| Pear | 4 | 710 | 110 |
| Apricot | 4 | 790 | 111 |
| Hornbeam | 4 | 1360 | 116 |
| Cherry | 2 | 1100 | 146 |
| Peach | 2 | 1220 | 146 |
| Linden | 2 | 2160 | 152 |
| Nectarine | 1 | 1470 | 169 |
| Quince | 1/0 | 1790 | 193 |
| Oilnut | 1/0 | 3440 | 201 |
| Orange | 2/0 | 2260 | 223 |
| Waterash | 2/0 | 4160 | 231 |
| Fig | 3/0 | 2740 | 256 |
| Shellbark | 3/0 | 5240 | 266 |
| Olive | 4/0 | 3450 | 295 |
| Pomegranate | 4/0 | 3620 | 296 |
| Planetree | 4/0 | 6610 | 306 |
| Mulberry | 266.8 | 4470 | 340 |
| Annona | 336.4 | 5540 | 392 |
| Annona | 336.4 | 5540 | 392 |
| Molles | 397.5 | 6400 | 429 |
| Huckleberry | 477 | 7820 | 479 |
| Paw Paw | 556.5 | 8950 | 526 |
| Breadfruit | 636 | 10500 | 565 |
| Persimmon | 795 | 12900 | 646 |
| Grapefruit | 1033.5 | 16500 | 755 |
* Ampacity ratings based on 75ºC conductor temperature 40ºC ambient temperature. Wind speed 2 ft./sec. in sun.
* Diameter equivalent to ACSR construction or 1350 aluminum equivalent.
* Diameter equivalent to ACSR construction or 1350 aluminum equivalent.
Revision: 1.000.009
Updated On: Feb. 5, 2025, 2:48 a.m. UTC
