SPEC 83354

Covered Line Wire With Thermoplastic Polyethylene (PE)

Aluminum Conductor Covered with Black Polyethylene (PE)

...

Construction:

  1. Conductor:Conductors are solid or stranded compressed aluminum
  2. Covering:Black Polyethylene (PE)

Applications and Features:

Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with Black Polyethylene (PE). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Black Polyethylene (PE) covered line wires have the below temperature ratings:

  • Normal Service temperature of 75ºC
  • Emergency Overload of 95ºC
  • Short Circuit temperature of 150ºC
  • Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandPhase Insul. ThicknessDia. Over Phase InsulationApprox. ODApprox. Weight
    AWG/KcmilNo.milinchinchlb/1000ft
    102442HORNBEAM48.697300.250.3159
    102467OILNUT123.37600.3980.518158
    102491PLANETREE246.97600.5630.683295
    TBAMULBERRY266.8600.5740.694305
    102236MOLLES397.519800.7010.861459
    102244HUCKLEBERRY47737800.7710.931540
    TBAPAW PAW556.5800.8320.992619
    TBABREADFRUIT636950.8911.081715
    102269PERSIMMON79561950.9971.187885
    TBAGRAPEFRUIT1033.5951.1361.326
    TBAAPPLE6Solid450.2520.252
    TBAPLUM67450.2680.268
    102145APRICOT47300.2250.28550
    TBAPEAR4Solid450.3150.315
    TBACHERRY2Solid450.3480.348
    102152PEACH27450.2830.37383
    TBALINDEN27450.3730.373
    TBANECTARINE17600.4420.442
    102160QUINCE1/07600.3570.477134
    TBAWATERASH2/07600.5250.525
    TBAORANGE2/07600.5250.525
    102186FIG3/07600.450.57202
    TBASHELLBARK3/07600.5760.576
    102194OLIVE4/07600.5060.626248
    TBAPOMEGRANATE4/019600.6320.632
    102228ANNONA336.419600.6460.766375
    621974ANNONA336.419600.6660.786388
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. Size
    AWG/Kcmil
    HORNBEAM48.69
    OILNUT123.3
    PLANETREE246.9
    MULBERRY266.8
    MOLLES397.5
    HUCKLEBERRY477
    PAW PAW556.5
    BREADFRUIT636
    PERSIMMON795
    GRAPEFRUIT1033.5
    APPLE6
    PLUM6
    APRICOT4
    PEAR4
    CHERRY2
    PEACH2
    LINDEN2
    NECTARINE1
    QUINCE1/0
    WATERASH2/0
    ORANGE2/0
    FIG3/0
    SHELLBARK3/0
    OLIVE4/0
    POMEGRANATE4/0
    ANNONA336.4
    ANNONA336.4
    * Ampacity ratings based on 75ºC conductor temperature 40ºC ambient temperature. Wind speed 2 ft./sec. in sun.
    * Diameter equivalent to ACSR construction or 1350 aluminum equivalent.

    Revision: 1.000.009

    Updated On: Feb. 5, 2025, 2:48 a.m. UTC