SPEC 25070

DURATRAY™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90ºC MAX, -40ºC Min for Cold Bend and Impact Rating, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. -40ºC min for cold bend and impact rating. Green Duraground™ also available.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res I & Sun Res
  • Sample Print Legend:

    SOUTHWIRE E30117 {UL} XX AWG CU RHH-RHW-2 600V FOR CT USE FT4 SR PR I OR PR II 90°C WET OR DRY -40°C --- {CSA} LL90458 XX AWG (XX.Xmm2) RW90 600V FT4 SR -40°C XLPE --- RoHS {MM/DD/YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA8760Black0.261691.01320.6530.7860.05255
    6490696760Black0.3041091.12090.4110.4950.05175
    4579214760Black0.3511621.43330.2580.3100.04895
    6490772760Black0.4092451.65300.1620.1950.045130
    6491391/01980Black0.5283952.18440.1020.1220.044170
    6491361/01980BE0.5283952.18440.1020.1220.044170
    6491341/01980RD0.5283952.18440.1020.1220.044170
    6491321/01980WE0.5283952.18440.1020.1220.044170
    6490882/01980Black0.5724872.210640.0810.0970.043195
    6490852/01980BE0.5724872.210640.0810.0970.043195
    6490832/01980RD0.5724872.210640.0810.0970.043195
    6490812/01980WE0.5724872.210640.0810.0970.043195
    6491483/01980Black0.6226022.413420.0640.0780.042225
    6491413/01980WE0.6226022.413420.0640.0780.042225
    6491433/01980RD0.6226022.413420.0640.0780.042225
    6491463/01980BE0.6226022.413420.0640.0780.042225
    6490974/01980Black0.6667452.616920.0510.0620.041260
    6490904/01980WE0.6667452.616920.0510.0620.041260
    6490924/01980RD0.6667452.616920.0510.0620.041260
    6490944/01980BE0.6667452.616920.0510.0620.041260
    TBA2503795Black0.7488722.920000.0430.0530.041290
    6491073503795Black0.84112183.328000.0310.0390.040350
    6491093503795WE0.84112183.328000.0310.0390.040350
    6491023503795RD0.84112183.328000.0310.0390.040350
    6491053503795BE0.84112183.328000.0310.0390.040350
    6491155003795BE0.96617053.840000.0220.0290.039430
    6491135003795RD0.96617053.840000.0220.0290.039430
    6491105003795WE0.96617053.840000.0220.0290.039430
    6490455003795Black0.96617053.840000.0220.0290.039430
    64904875061110Black1.20025496.060000.0140.0220.038535
    64911975061110RD1.20025496.060000.0140.0220.038535
    64912175061110BE1.20025496.060000.0140.0220.038535
    64911775061110WE1.20025496.060000.0140.0220.038535
    649130100061110Black1.34933546.780000.0110.0180.037615
    649123100061110WE1.34933546.780000.0110.0180.037615
    649125100061110RD1.34933546.780000.0110.0180.037615
    649127100061110BE1.34933546.780000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities derived from the 2015 Canadian Electrical Code
    - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
    - TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA871.52Black6.6310325.405872.142.580.170655
    649069671.52Black7.7216227.949301.351.620.167375
    457921471.52Black8.9224135.5614820.851.020.157595
    649077271.52Black10.3936540.6423590.530.640.1476130
    6491391/0192.03Black13.4158853.3437560.330.400.1444170
    6491361/0192.03BE13.4158853.3437560.330.400.1444170
    6491341/0192.03RD13.4158853.3437560.330.400.1444170
    6491321/0192.03WE13.4158853.3437560.330.400.1444170
    6490882/0192.03Black14.5372555.8847350.270.320.1411195
    6490852/0192.03BE14.5372555.8847350.270.320.1411195
    6490832/0192.03RD14.5372555.8847350.270.320.1411195
    6490812/0192.03WE14.5372555.8847350.270.320.1411195
    6491483/0192.03Black15.8089660.9659720.210.260.1378225
    6491413/0192.03WE15.8089660.9659720.210.260.1378225
    6491433/0192.03RD15.8089660.9659720.210.260.1378225
    6491463/0192.03BE15.8089660.9659720.210.260.1378225
    6490974/0192.03Black16.92110966.0475290.170.200.1345260
    6490904/0192.03WE16.92110966.0475290.170.200.1345260
    6490924/0192.03RD16.92110966.0475290.170.200.1345260
    6490944/0192.03BE16.92110966.0475290.170.200.1345260
    TBA250372.41Black19.00129873.6689000.140.170.1345290
    649107350372.41Black21.36181383.82124600.100.130.1312350
    649109350372.41WE21.36181383.82124600.100.130.1312350
    649102350372.41RD21.36181383.82124600.100.130.1312350
    649105350372.41BE21.36181383.82124600.100.130.1312350
    649115500372.41BE24.54253796.52178000.070.100.1280430
    649113500372.41RD24.54253796.52178000.070.100.1280430
    649110500372.41WE24.54253796.52178000.070.100.1280430
    649045500372.41Black24.54253796.52178000.070.100.1280430
    649048750612.79Black30.483793152.40267000.050.070.1247535
    649119750612.79RD30.483793152.40267000.050.070.1247535
    649121750612.79BE30.483793152.40267000.050.070.1247535
    649117750612.79WE30.483793152.40267000.050.070.1247535
    6491301000612.79Black34.264991170.18356000.040.060.1214615
    6491231000612.79WE34.264991170.18356000.040.060.1214615
    6491251000612.79RD34.264991170.18356000.040.060.1214615
    6491271000612.79BE34.264991170.18356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities derived from the 2015 Canadian Electrical Code
    - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
    - TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Stock Codes and Colors

    SizeBLACKWHITEREDBLUEYELLOWBROWNORANGEGREY
    1/0649139649132649134649136TBATBATBATBA
    2/0649088649081649083649085TBATBATBATBA
    3/0649148649141649143649146TBATBATBATBA
    4/0649097649090649092649094TBATBATBATBA
    250KcmilTBATBATBATBATBATBATBATBA
    350Kcmil649107649109649102649105TBATBATBATBA
    500Kcmil649045649110649113649115TBATBATBATBA
    750Kcmil649048649117649119649121TBATBATBATBA
    1000Kcmil649130649123649125649127TBATBATBATBA
    Cable marked with this symbol is a standard stock item

    Revision: 1.000.005

    Updated On: April 15, 2025, 10:28 p.m. UTC