SPEC 25070
DURATRAY™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA
Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90ºC MAX, -40ºC Min for Cold Bend and Impact Rating, Gasoline & Oil Resistant

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE)
Applications and Features:
Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. -40ºC min for cold bend and impact rating. Green Duraground™ also available.
Specifications:
Sample Print Legend:
SOUTHWIRE E30117 {UL} XX AWG CU RHH-RHW-2 600V FOR CT USE FT4 SR PR I OR PR II 90°C WET OR DRY -40°C --- {CSA} LL90458 XX AWG (XX.Xmm2) RW90 600V FT4 SR -40°C XLPE --- RoHS {MM/DD/YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | |
| TBA | 8 | 7 | 60 | 0.262 | 72 | 1 | 132 | 0.653 | 0.81 | 0.052 | 55 |
| 649069 | 6 | 7 | 60 | 0.304 | 109 | 1.2 | 209 | 0.411 | 0.51 | 0.051 | 75 |
| 457921 | 4 | 7 | 60 | 0.351 | 163 | 1.4 | 333 | 0.258 | 0.32 | 0.048 | 95 |
| 649077 | 2 | 7 | 60 | 0.409 | 246 | 1.6 | 530 | 0.162 | 0.201 | 0.045 | 130 |
| 649139 | 1/0 | 19 | 80 | 0.528 | 396 | 2.1 | 844 | 0.102 | 0.127 | 0.044 | 170 |
| 649136 | 1/0 | 19 | 80 | 0.528 | 396 | 2.1 | 844 | 0.102 | 0.127 | 0.044 | 170 |
| 649134 | 1/0 | 19 | 80 | 0.528 | 396 | 2.1 | 844 | 0.102 | 0.127 | 0.044 | 170 |
| 649132 | 1/0 | 19 | 80 | 0.528 | 396 | 2.1 | 844 | 0.102 | 0.127 | 0.044 | 170 |
| 649088◊ | 2/0 | 19 | 80 | 0.572 | 488 | 2.3 | 1064 | 0.082 | 0.102 | 0.043 | 195 |
| 649085◊ | 2/0 | 19 | 80 | 0.572 | 488 | 2.3 | 1064 | 0.082 | 0.102 | 0.043 | 195 |
| 649083◊ | 2/0 | 19 | 80 | 0.572 | 488 | 2.3 | 1064 | 0.082 | 0.102 | 0.043 | 195 |
| 649081◊ | 2/0 | 19 | 80 | 0.572 | 488 | 2.3 | 1064 | 0.082 | 0.102 | 0.043 | 195 |
| 649148 | 3/0 | 19 | 80 | 0.622 | 603 | 2.5 | 1342 | 0.064 | 0.079 | 0.042 | 225 |
| 649141 | 3/0 | 19 | 80 | 0.622 | 603 | 2.5 | 1342 | 0.064 | 0.079 | 0.042 | 225 |
| 649143 | 3/0 | 19 | 80 | 0.622 | 603 | 2.5 | 1342 | 0.064 | 0.079 | 0.042 | 225 |
| 649146 | 3/0 | 19 | 80 | 0.622 | 603 | 2.5 | 1342 | 0.064 | 0.079 | 0.042 | 225 |
| 649097◊ | 4/0 | 19 | 80 | 0.666 | 745 | 2.7 | 1692 | 0.051 | 0.063 | 0.041 | 260 |
| 649090◊ | 4/0 | 19 | 80 | 0.666 | 745 | 2.7 | 1692 | 0.051 | 0.063 | 0.041 | 260 |
| 649092◊ | 4/0 | 19 | 80 | 0.666 | 745 | 2.7 | 1692 | 0.051 | 0.063 | 0.041 | 260 |
| 649094◊ | 4/0 | 19 | 80 | 0.666 | 745 | 2.7 | 1692 | 0.051 | 0.063 | 0.041 | 260 |
| TBA | 250 | 37 | 95 | 0.748 | 882 | 3 | 2000 | 0.043 | 0.053 | 0.041 | 290 |
| 649107◊ | 350 | 37 | 95 | 0.841 | 1219 | 3.4 | 2800 | 0.031 | 0.039 | 0.04 | 350 |
| 649109◊ | 350 | 37 | 95 | 0.841 | 1219 | 3.4 | 2800 | 0.031 | 0.039 | 0.04 | 350 |
| 649102◊ | 350 | 37 | 95 | 0.841 | 1219 | 3.4 | 2800 | 0.031 | 0.039 | 0.04 | 350 |
| 649105◊ | 350 | 37 | 95 | 0.841 | 1219 | 3.4 | 2800 | 0.031 | 0.039 | 0.04 | 350 |
| 649115◊ | 500 | 37 | 95 | 0.966 | 1706 | 3.9 | 4000 | 0.021 | 0.027 | 0.039 | 430 |
| 649113◊ | 500 | 37 | 95 | 0.966 | 1706 | 3.9 | 4000 | 0.021 | 0.027 | 0.039 | 430 |
| 649110◊ | 500 | 37 | 95 | 0.966 | 1706 | 3.9 | 4000 | 0.021 | 0.027 | 0.039 | 430 |
| 649045◊ | 500 | 37 | 95 | 0.966 | 1706 | 3.9 | 4000 | 0.021 | 0.027 | 0.039 | 430 |
| 649048◊ | 750 | 61 | 110 | 1.2 | 2550 | 6 | 6000 | 0.014 | 0.019 | 0.038 | 535 |
| 649119◊ | 750 | 61 | 110 | 1.2 | 2550 | 6 | 6000 | 0.014 | 0.019 | 0.038 | 535 |
| 649121◊ | 750 | 61 | 110 | 1.2 | 2550 | 6 | 6000 | 0.014 | 0.019 | 0.038 | 535 |
| 649117◊ | 750 | 61 | 110 | 1.2 | 2550 | 6 | 6000 | 0.014 | 0.019 | 0.038 | 535 |
| 649130◊ | 1000 | 61 | 110 | 1.349 | 3354 | 6.7 | 8000 | 0.011 | 0.016 | 0.037 | 615 |
| 649123◊ | 1000 | 61 | 110 | 1.349 | 3354 | 6.7 | 8000 | 0.011 | 0.016 | 0.037 | 615 |
| 649125◊ | 1000 | 61 | 110 | 1.349 | 3354 | 6.7 | 8000 | 0.011 | 0.016 | 0.037 | 615 |
| 649127◊ | 1000 | 61 | 110 | 1.349 | 3354 | 6.7 | 8000 | 0.011 | 0.016 | 0.037 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Ampacities derived from the 2015 Canadian Electrical Code
- Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
- TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
- Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
- TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Insul. Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | kg/km | mm | newton | Ω/km | Ω/km | Ω/km | Amp | |
| TBA | 8 | 7 | 1.52 | 6.65 | 107 | 25.40 | 587 | 2.14 | 2.66 | 0.1706 | 55 |
| 649069 | 6 | 7 | 1.52 | 7.72 | 162 | 30.48 | 930 | 1.35 | 1.67 | 0.1673 | 75 |
| 457921 | 4 | 7 | 1.52 | 8.92 | 243 | 35.56 | 1482 | 0.85 | 1.05 | 0.1575 | 95 |
| 649077 | 2 | 7 | 1.52 | 10.39 | 366 | 40.64 | 2359 | 0.53 | 0.66 | 0.1476 | 130 |
| 649139 | 1/0 | 19 | 2.03 | 13.41 | 589 | 53.34 | 3756 | 0.33 | 0.42 | 0.1444 | 170 |
| 649136 | 1/0 | 19 | 2.03 | 13.41 | 589 | 53.34 | 3756 | 0.33 | 0.42 | 0.1444 | 170 |
| 649134 | 1/0 | 19 | 2.03 | 13.41 | 589 | 53.34 | 3756 | 0.33 | 0.42 | 0.1444 | 170 |
| 649132 | 1/0 | 19 | 2.03 | 13.41 | 589 | 53.34 | 3756 | 0.33 | 0.42 | 0.1444 | 170 |
| 649088◊ | 2/0 | 19 | 2.03 | 14.53 | 726 | 58.42 | 4735 | 0.27 | 0.33 | 0.1411 | 195 |
| 649085◊ | 2/0 | 19 | 2.03 | 14.53 | 726 | 58.42 | 4735 | 0.27 | 0.33 | 0.1411 | 195 |
| 649083◊ | 2/0 | 19 | 2.03 | 14.53 | 726 | 58.42 | 4735 | 0.27 | 0.33 | 0.1411 | 195 |
| 649081◊ | 2/0 | 19 | 2.03 | 14.53 | 726 | 58.42 | 4735 | 0.27 | 0.33 | 0.1411 | 195 |
| 649148 | 3/0 | 19 | 2.03 | 15.80 | 897 | 63.50 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
| 649141 | 3/0 | 19 | 2.03 | 15.80 | 897 | 63.50 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
| 649143 | 3/0 | 19 | 2.03 | 15.80 | 897 | 63.50 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
| 649146 | 3/0 | 19 | 2.03 | 15.80 | 897 | 63.50 | 5972 | 0.21 | 0.26 | 0.1378 | 225 |
| 649097◊ | 4/0 | 19 | 2.03 | 16.92 | 1109 | 68.58 | 7529 | 0.17 | 0.21 | 0.1345 | 260 |
| 649090◊ | 4/0 | 19 | 2.03 | 16.92 | 1109 | 68.58 | 7529 | 0.17 | 0.21 | 0.1345 | 260 |
| 649092◊ | 4/0 | 19 | 2.03 | 16.92 | 1109 | 68.58 | 7529 | 0.17 | 0.21 | 0.1345 | 260 |
| 649094◊ | 4/0 | 19 | 2.03 | 16.92 | 1109 | 68.58 | 7529 | 0.17 | 0.21 | 0.1345 | 260 |
| TBA | 250 | 37 | 2.41 | 19.00 | 1313 | 76.20 | 8900 | 0.14 | 0.17 | 0.1345 | 290 |
| 649107◊ | 350 | 37 | 2.41 | 21.36 | 1814 | 86.36 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
| 649109◊ | 350 | 37 | 2.41 | 21.36 | 1814 | 86.36 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
| 649102◊ | 350 | 37 | 2.41 | 21.36 | 1814 | 86.36 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
| 649105◊ | 350 | 37 | 2.41 | 21.36 | 1814 | 86.36 | 12460 | 0.10 | 0.13 | 0.1312 | 350 |
| 649115◊ | 500 | 37 | 2.41 | 24.54 | 2539 | 99.06 | 17800 | 0.07 | 0.09 | 0.1280 | 430 |
| 649113◊ | 500 | 37 | 2.41 | 24.54 | 2539 | 99.06 | 17800 | 0.07 | 0.09 | 0.1280 | 430 |
| 649110◊ | 500 | 37 | 2.41 | 24.54 | 2539 | 99.06 | 17800 | 0.07 | 0.09 | 0.1280 | 430 |
| 649045◊ | 500 | 37 | 2.41 | 24.54 | 2539 | 99.06 | 17800 | 0.07 | 0.09 | 0.1280 | 430 |
| 649048◊ | 750 | 61 | 2.79 | 30.48 | 3795 | 152.40 | 26700 | 0.05 | 0.06 | 0.1247 | 535 |
| 649119◊ | 750 | 61 | 2.79 | 30.48 | 3795 | 152.40 | 26700 | 0.05 | 0.06 | 0.1247 | 535 |
| 649121◊ | 750 | 61 | 2.79 | 30.48 | 3795 | 152.40 | 26700 | 0.05 | 0.06 | 0.1247 | 535 |
| 649117◊ | 750 | 61 | 2.79 | 30.48 | 3795 | 152.40 | 26700 | 0.05 | 0.06 | 0.1247 | 535 |
| 649130◊ | 1000 | 61 | 2.79 | 34.26 | 4991 | 170.18 | 35600 | 0.04 | 0.05 | 0.1214 | 615 |
| 649123◊ | 1000 | 61 | 2.79 | 34.26 | 4991 | 170.18 | 35600 | 0.04 | 0.05 | 0.1214 | 615 |
| 649125◊ | 1000 | 61 | 2.79 | 34.26 | 4991 | 170.18 | 35600 | 0.04 | 0.05 | 0.1214 | 615 |
| 649127◊ | 1000 | 61 | 2.79 | 34.26 | 4991 | 170.18 | 35600 | 0.04 | 0.05 | 0.1214 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Ampacities derived from the 2015 Canadian Electrical Code
- Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
- TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
- Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
- TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Stock Codes and Colors
| Size | Black | White | Red | Blue | Yellow | Brown | Orange | Grey |
|---|---|---|---|---|---|---|---|---|
| 1/0 | 649139 | 649132 | 649134 | 649136 | TBA | TBA | TBA | TBA |
| 2/0 | 649088 | 649081 | 649083 | 649085 | TBA | TBA | TBA | TBA |
| 3/0 | 649148 | 649141 | 649143 | 649146 | TBA | TBA | TBA | TBA |
| 4/0 | 649097 | 649090 | 649092 | 649094 | TBA | TBA | TBA | TBA |
| 250Kcmil | TBA | TBA | TBA | TBA | TBA | TBA | TBA | TBA |
| 350Kcmil | 649107 | 649109 | 649102 | 649105 | TBA | TBA | TBA | TBA |
| 500Kcmil | 649045 | 649110 | 649113 | 649115 | TBA | TBA | TBA | TBA |
| 750Kcmil | 649048 | 649117 | 649119 | 649121 | TBA | TBA | TBA | TBA |
| 1000Kcmil | 649130 | 649123 | 649125 | 649127 | TBA | TBA | TBA | TBA |
Revision: 1.000.005
Updated On: April 15, 2025, 10:28 p.m. UTC