SPEC 25070

DURATRAY™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90ºC MAX, -40ºC Min for Cold Bend and Impact Rating, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. -40ºC min for cold bend and impact rating. Green Duraground™ also available.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res I & Sun Res
  • Sample Print Legend:

    SOUTHWIRE E30117 {UL} XX AWG CU RHH-RHW-2 600V FOR CT USE FT4 SR PR I OR PR II 90°C WET OR DRY -40°C --- {CSA} LL90458 XX AWG (XX.Xmm2) RW90 600V FT4 SR -40°C XLPE --- RoHS {MM/DD/YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA87600.2627211320.6530.810.05255
    64906967600.3041091.22090.4110.510.05175
    45792147600.3511631.43330.2580.320.04895
    64907727600.4092461.65300.1620.2010.045130
    6491391/019800.5283962.18440.1020.1270.044170
    6491361/019800.5283962.18440.1020.1270.044170
    6491341/019800.5283962.18440.1020.1270.044170
    6491321/019800.5283962.18440.1020.1270.044170
    649088◊2/019800.5724882.310640.0820.1020.043195
    649085◊2/019800.5724882.310640.0820.1020.043195
    649083◊2/019800.5724882.310640.0820.1020.043195
    649081◊2/019800.5724882.310640.0820.1020.043195
    6491483/019800.6226032.513420.0640.0790.042225
    6491413/019800.6226032.513420.0640.0790.042225
    6491433/019800.6226032.513420.0640.0790.042225
    6491463/019800.6226032.513420.0640.0790.042225
    649097◊4/019800.6667452.716920.0510.0630.041260
    649090◊4/019800.6667452.716920.0510.0630.041260
    649092◊4/019800.6667452.716920.0510.0630.041260
    649094◊4/019800.6667452.716920.0510.0630.041260
    TBA25037950.748882320000.0430.0530.041290
    649107◊35037950.84112193.428000.0310.0390.04350
    649109◊35037950.84112193.428000.0310.0390.04350
    649102◊35037950.84112193.428000.0310.0390.04350
    649105◊35037950.84112193.428000.0310.0390.04350
    649115◊50037950.96617063.940000.0210.0270.039430
    649113◊50037950.96617063.940000.0210.0270.039430
    649110◊50037950.96617063.940000.0210.0270.039430
    649045◊50037950.96617063.940000.0210.0270.039430
    649048◊750611101.22550660000.0140.0190.038535
    649119◊750611101.22550660000.0140.0190.038535
    649121◊750611101.22550660000.0140.0190.038535
    649117◊750611101.22550660000.0140.0190.038535
    649130◊1000611101.34933546.780000.0110.0160.037615
    649123◊1000611101.34933546.780000.0110.0160.037615
    649125◊1000611101.34933546.780000.0110.0160.037615
    649127◊1000611101.34933546.780000.0110.0160.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities derived from the 2015 Canadian Electrical Code
    - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
    - TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA871.526.6510725.405872.142.660.170655
    649069671.527.7216230.489301.351.670.167375
    457921471.528.9224335.5614820.851.050.157595
    649077271.5210.3936640.6423590.530.660.1476130
    6491391/0192.0313.4158953.3437560.330.420.1444170
    6491361/0192.0313.4158953.3437560.330.420.1444170
    6491341/0192.0313.4158953.3437560.330.420.1444170
    6491321/0192.0313.4158953.3437560.330.420.1444170
    649088◊2/0192.0314.5372658.4247350.270.330.1411195
    649085◊2/0192.0314.5372658.4247350.270.330.1411195
    649083◊2/0192.0314.5372658.4247350.270.330.1411195
    649081◊2/0192.0314.5372658.4247350.270.330.1411195
    6491483/0192.0315.8089763.5059720.210.260.1378225
    6491413/0192.0315.8089763.5059720.210.260.1378225
    6491433/0192.0315.8089763.5059720.210.260.1378225
    6491463/0192.0315.8089763.5059720.210.260.1378225
    649097◊4/0192.0316.92110968.5875290.170.210.1345260
    649090◊4/0192.0316.92110968.5875290.170.210.1345260
    649092◊4/0192.0316.92110968.5875290.170.210.1345260
    649094◊4/0192.0316.92110968.5875290.170.210.1345260
    TBA250372.4119.00131376.2089000.140.170.1345290
    649107◊350372.4121.36181486.36124600.100.130.1312350
    649109◊350372.4121.36181486.36124600.100.130.1312350
    649102◊350372.4121.36181486.36124600.100.130.1312350
    649105◊350372.4121.36181486.36124600.100.130.1312350
    649115◊500372.4124.54253999.06178000.070.090.1280430
    649113◊500372.4124.54253999.06178000.070.090.1280430
    649110◊500372.4124.54253999.06178000.070.090.1280430
    649045◊500372.4124.54253999.06178000.070.090.1280430
    649048◊750612.7930.483795152.40267000.050.060.1247535
    649119◊750612.7930.483795152.40267000.050.060.1247535
    649121◊750612.7930.483795152.40267000.050.060.1247535
    649117◊750612.7930.483795152.40267000.050.060.1247535
    649130◊1000612.7934.264991170.18356000.040.050.1214615
    649123◊1000612.7934.264991170.18356000.040.050.1214615
    649125◊1000612.7934.264991170.18356000.040.050.1214615
    649127◊1000612.7934.264991170.18356000.040.050.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities derived from the 2015 Canadian Electrical Code
    - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C.
    - TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Stock Codes and Colors

    SizeBlackWhiteRedBlueYellowBrownOrangeGrey
    1/0649139649132649134649136TBATBATBATBA
    2/0649088649081649083649085TBATBATBATBA
    3/0649148649141649143649146TBATBATBATBA
    4/0649097649090649092649094TBATBATBATBA
    250KcmilTBATBATBATBATBATBATBATBA
    350Kcmil649107649109649102649105TBATBATBATBA
    500Kcmil649045649110649113649115TBATBATBATBA
    750Kcmil649048649117649119649121TBATBATBATBA
    1000Kcmil649130649123649125649127TBATBATBATBA
    ♢Cable marked with this symbol is a standard stock item