SPEC 25040
CSA TECK 90 600V PVC CONTROL CABLE
600V Multi Conductor, 14-10 AWG Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

Construction:
- Conductor:Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
- Insulation:Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; For 5/C cables or more, the insulation is black and numbered
- Grounding Conductors:Uninsulated Class B stranded grounding conductor
- Inner Jacket:Black Polyvinyl Chloride (PVC)
- Armor:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black PVC (optional colours available)
Applications and Features:
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
- -40°C - CSA Cold Bend and Impact Temperature
- -40°C - Min. Installation Temperature
- 90°C - Max. Continuous Operating Temperature
Specifications:
Sample Print Legend:
{SQMTR} SOUTHWIRE {CSA} LL90458 X/C XX AWG CU TECK 90 XLPE -40°C FT4 AG14 SUN RES 90°C 600V HL USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | No. x AWG | AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | |
| 562239 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 50 | 0.374 | 0.573 | 45 | 0.663 | 38 | 197 |
| 561780 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 50 | 0.395 | 0.594 | 45 | 0.684 | 51 | 220 |
| 561781 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 50 | 0.43 | 0.628 | 45 | 0.718 | 64 | 248 |
| 561788 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 50 | 0.468 | 0.667 | 45 | 0.757 | 77 | 276 |
| 562248 | 14 | 7 | 0.071 | 0.133 | 30 | 1x14 | 14 | 50 | 0.505 | 0.703 | 45 | 0.793 | 90 | 304 |
| 561789 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 50 | 0.508 | 0.707 | 45 | 0.797 | 103 | 325 |
| 562254 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 65 | 0.58 | 0.78 | 45 | 0.87 | 115 | 377 |
| 562258 | 14 | 7 | 0.071 | 0.133 | 30 | 1x14 | 14 | 65 | 0.668 | 0.866 | 45 | 0.956 | 141 | 440 |
| 561790 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 65 | 0.693 | 0.893 | 45 | 0.983 | 167 | 484 |
| 562263 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 65 | 0.767 | 0.954 | 45 | 1.044 | 205 | 555 |
| 561791 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 65 | 0.806 | 1.116 | 45 | 1.206 | 256 | 699 |
| 562269 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 85 | 0.888 | 1.136 | 45 | 1.226 | 269 | 724 |
| 561778 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 85 | 0.98 | 1.286 | 45 | 1.376 | 334 | 902 |
| 562275 | 14 | 7 | 0.071 | 0.134 | 30 | 1x14 | 14 | 85 | 1.035 | 1.347 | 45 | 1.437 | 399 | 1014 |
| 561792 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 50 | 0.41 | 0.609 | 45 | 0.699 | 54 | 224 |
| 561793 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 50 | 0.434 | 0.633 | 45 | 0.723 | 74 | 257 |
| 561794 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 50 | 0.474 | 0.672 | 45 | 0.762 | 94 | 294 |
| 589296 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 50 | 0.516 | 0.715 | 45 | 0.805 | 115 | 333 |
| 567116 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 65 | 0.592 | 0.792 | 45 | 0.882 | 135 | 395 |
| 584397 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 65 | 0.592 | 0.792 | 45 | 0.882 | 155 | 425 |
| 568599 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 65 | 0.639 | 0.839 | 45 | 0.929 | 176 | 464 |
| 563506 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 65 | 0.744 | 0.944 | 45 | 1.034 | 216 | 550 |
| 561796 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 65 | 0.768 | 0.954 | 45 | 1.044 | 257 | 604 |
| 563511 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 85 | 0.892 | 1.204 | 45 | 1.294 | 318 | 818 |
| 563515 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 85 | 0.983 | 1.295 | 45 | 1.385 | 420 | 984 |
| 589299 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 85 | 1.088 | 1.4 | 45 | 1.49 | 524 | 1159 |
| 587679 | 12 | 7 | 0.089 | 0.152 | 30 | 1x14 | 14 | 85 | 1.15 | 1.425 | 45 | 1.515 | 627 | 1298 |
| 562290 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 50 | 0.458 | 0.657 | 45 | 0.747 | 85 | 273 |
| 561797 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 50 | 0.486 | 0.685 | 45 | 0.775 | 117 | 320 |
| 561798 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 65 | 0.562 | 0.73 | 45 | 0.82 | 150 | 372 |
| 567109 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 65 | 0.664 | 0.864 | 45 | 0.954 | 215 | 505 |
| 584443 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 65 | 0.719 | 0.925 | 45 | 1.015 | 279 | 609 |
| 567096 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 85 | 0.88 | 1.184 | 45 | 1.274 | 344 | 816 |
| 589343 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 85 | 0.908 | 1.22 | 45 | 1.31 | 409 | 913 |
| 567102 | 10 | 7 | 0.113 | 0.176 | 30 | 1x12 | 12 | 85 | 1.005 | 1.317 | 45 | 1.407 | 506 | 1069 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Use Table 5C in the 2015 Canadian Electrical Code to derate this ampacity as per Rules 4-004 & 12-2210
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|
| AWG/Kcmil | inch | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp |
| 14 | 4.6 | 2.631 | 3.265 | 0.058 | 25 |
| 14 | 4.8 | 2.631 | 3.265 | 0.058 | 25 |
| 14 | 5 | 2.631 | 3.265 | 0.058 | 20 |
| 14 | 5.3 | 2.631 | 3.265 | 0.058 | 20 |
| 14 | 5.6 | 2.631 | 3.265 | 0.058 | 20 |
| 14 | 5.6 | 2.631 | 3.265 | 0.058 | 18 |
| 14 | 6.1 | 2.631 | 3.265 | 0.058 | 18 |
| 14 | 6.7 | 2.631 | 3.265 | 0.058 | 12 |
| 14 | 6.9 | 2.631 | 3.265 | 0.058 | 12 |
| 14 | 7.3 | 2.631 | 3.265 | 0.058 | 12 |
| 14 | 8.4 | 2.631 | 3.265 | 0.058 | 12 |
| 14 | 8.6 | 2.631 | 3.265 | 0.058 | 12 |
| 14 | 9.6 | 2.631 | 3.265 | 0.058 | 11 |
| 14 | 10.1 | 2.631 | 3.265 | 0.058 | 11 |
| 12 | 4.9 | 1.662 | 2.063 | 0.054 | 30 |
| 12 | 5.1 | 1.662 | 2.063 | 0.054 | 30 |
| 12 | 5.3 | 1.662 | 2.063 | 0.054 | 24 |
| 12 | 5.6 | 1.662 | 2.063 | 0.054 | 24 |
| 12 | 6.2 | 1.662 | 2.063 | 0.054 | 24 |
| 12 | 6.2 | 1.662 | 2.063 | 0.054 | 21 |
| 12 | 6.5 | 1.662 | 2.063 | 0.054 | 21 |
| 12 | 7.2 | 1.662 | 2.063 | 0.054 | 15 |
| 12 | 7.3 | 1.662 | 2.063 | 0.054 | 15 |
| 12 | 9.1 | 1.662 | 2.063 | 0.054 | 15 |
| 12 | 9.7 | 1.662 | 2.063 | 0.054 | 15 |
| 12 | 10.4 | 1.662 | 2.063 | 0.054 | 14 |
| 12 | 10.6 | 1.662 | 2.063 | 0.054 | 14 |
| 10 | 5.2 | 1.04 | 1.291 | 0.05 | 40 |
| 10 | 5.4 | 1.04 | 1.291 | 0.05 | 40 |
| 10 | 5.7 | 1.04 | 1.291 | 0.05 | 32 |
| 10 | 6.7 | 1.04 | 1.291 | 0.05 | 32 |
| 10 | 7.1 | 1.04 | 1.291 | 0.05 | 28 |
| 10 | 8.9 | 1.04 | 1.291 | 0.05 | 20 |
| 10 | 9.2 | 1.04 | 1.291 | 0.05 | 20 |
| 10 | 9.8 | 1.04 | 1.291 | 0.05 | 20 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | No. x AWG | AWG | mm | mm | mm | mm | mm | kg/km | kg/km | |
| 562239 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.27 | 9.50 | 14.55 | 1.14 | 16.84 | 57 | 293 |
| 561780 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.27 | 10.03 | 15.09 | 1.14 | 17.37 | 76 | 327 |
| 561781 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.27 | 10.92 | 15.95 | 1.14 | 18.24 | 95 | 369 |
| 561788 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.27 | 11.89 | 16.94 | 1.14 | 19.23 | 115 | 411 |
| 562248 | 14 | 7 | 1.80 | 3.38 | 0.76 | 1x14 | 14 | 1.27 | 12.83 | 17.86 | 1.14 | 20.14 | 134 | 452 |
| 561789 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.27 | 12.90 | 17.96 | 1.14 | 20.24 | 153 | 484 |
| 562254 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.65 | 14.73 | 19.81 | 1.14 | 22.10 | 171 | 561 |
| 562258 | 14 | 7 | 1.80 | 3.38 | 0.76 | 1x14 | 14 | 1.65 | 16.97 | 22.00 | 1.14 | 24.28 | 210 | 655 |
| 561790 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.65 | 17.60 | 22.68 | 1.14 | 24.97 | 249 | 720 |
| 562263 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.65 | 19.48 | 24.23 | 1.14 | 26.52 | 305 | 826 |
| 561791 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 1.65 | 20.47 | 28.35 | 1.14 | 30.63 | 381 | 1040 |
| 562269 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 2.16 | 22.56 | 28.85 | 1.14 | 31.14 | 400 | 1077 |
| 561778 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 2.16 | 24.89 | 32.66 | 1.14 | 34.95 | 497 | 1342 |
| 562275 | 14 | 7 | 1.80 | 3.40 | 0.76 | 1x14 | 14 | 2.16 | 26.29 | 34.21 | 1.14 | 36.50 | 594 | 1509 |
| 561792 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.27 | 10.41 | 15.47 | 1.14 | 17.75 | 80 | 333 |
| 561793 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.27 | 11.02 | 16.08 | 1.14 | 18.36 | 110 | 382 |
| 561794 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.27 | 12.04 | 17.07 | 1.14 | 19.35 | 140 | 438 |
| 589296 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.27 | 13.11 | 18.16 | 1.14 | 20.45 | 171 | 496 |
| 567116 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.65 | 15.04 | 20.12 | 1.14 | 22.40 | 201 | 588 |
| 584397 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.65 | 15.04 | 20.12 | 1.14 | 22.40 | 231 | 632 |
| 568599 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.65 | 16.23 | 21.31 | 1.14 | 23.60 | 262 | 691 |
| 563506 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.65 | 18.90 | 23.98 | 1.14 | 26.26 | 321 | 818 |
| 561796 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 1.65 | 19.51 | 24.23 | 1.14 | 26.52 | 382 | 899 |
| 563511 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 2.16 | 22.66 | 30.58 | 1.14 | 32.87 | 473 | 1217 |
| 563515 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 2.16 | 24.97 | 32.89 | 1.14 | 35.18 | 625 | 1464 |
| 589299 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 2.16 | 27.64 | 35.56 | 1.14 | 37.85 | 780 | 1725 |
| 587679 | 12 | 7 | 2.26 | 3.86 | 0.76 | 1x14 | 14 | 2.16 | 29.21 | 36.20 | 1.14 | 38.48 | 933 | 1932 |
| 562290 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 1.27 | 11.63 | 16.69 | 1.14 | 18.97 | 126 | 406 |
| 561797 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 1.27 | 12.34 | 17.40 | 1.14 | 19.69 | 174 | 476 |
| 561798 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 1.65 | 14.27 | 18.54 | 1.14 | 20.83 | 223 | 554 |
| 567109 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 1.65 | 16.87 | 21.95 | 1.14 | 24.23 | 320 | 752 |
| 584443 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 1.65 | 18.26 | 23.50 | 1.14 | 25.78 | 415 | 906 |
| 567096 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 2.16 | 22.35 | 30.07 | 1.14 | 32.36 | 512 | 1214 |
| 589343 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 2.16 | 23.06 | 30.99 | 1.14 | 33.27 | 609 | 1359 |
| 567102 | 10 | 7 | 2.87 | 4.47 | 0.76 | 1x12 | 12 | 2.16 | 25.53 | 33.45 | 1.14 | 35.74 | 753 | 1591 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Use Table 5C in the 2015 Canadian Electrical Code to derate this ampacity as per Rules 4-004 & 12-2210
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|
| AWG/Kcmil | mm | Ω/km | Ω/km | Ω/km | Amp |
| 14 | 116.84 | 8.6319 | 10.71 | 0.1903 | 25 |
| 14 | 121.92 | 8.6319 | 10.71 | 0.1903 | 25 |
| 14 | 127.00 | 8.6319 | 10.71 | 0.1903 | 20 |
| 14 | 134.62 | 8.6319 | 10.71 | 0.1903 | 20 |
| 14 | 142.24 | 8.6319 | 10.71 | 0.1903 | 20 |
| 14 | 142.24 | 8.6319 | 10.71 | 0.1903 | 18 |
| 14 | 154.94 | 8.6319 | 10.71 | 0.1903 | 18 |
| 14 | 170.18 | 8.6319 | 10.71 | 0.1903 | 12 |
| 14 | 175.26 | 8.6319 | 10.71 | 0.1903 | 12 |
| 14 | 185.42 | 8.6319 | 10.71 | 0.1903 | 12 |
| 14 | 213.36 | 8.6319 | 10.71 | 0.1903 | 12 |
| 14 | 218.44 | 8.6319 | 10.71 | 0.1903 | 12 |
| 14 | 243.84 | 8.6319 | 10.71 | 0.1903 | 11 |
| 14 | 256.54 | 8.6319 | 10.71 | 0.1903 | 11 |
| 12 | 124.46 | 5.4528 | 6.77 | 0.1772 | 30 |
| 12 | 129.54 | 5.4528 | 6.77 | 0.1772 | 30 |
| 12 | 134.62 | 5.4528 | 6.77 | 0.1772 | 24 |
| 12 | 142.24 | 5.4528 | 6.77 | 0.1772 | 24 |
| 12 | 157.48 | 5.4528 | 6.77 | 0.1772 | 24 |
| 12 | 157.48 | 5.4528 | 6.77 | 0.1772 | 21 |
| 12 | 165.10 | 5.4528 | 6.77 | 0.1772 | 21 |
| 12 | 182.88 | 5.4528 | 6.77 | 0.1772 | 15 |
| 12 | 185.42 | 5.4528 | 6.77 | 0.1772 | 15 |
| 12 | 231.14 | 5.4528 | 6.77 | 0.1772 | 15 |
| 12 | 246.38 | 5.4528 | 6.77 | 0.1772 | 15 |
| 12 | 264.16 | 5.4528 | 6.77 | 0.1772 | 14 |
| 12 | 269.24 | 5.4528 | 6.77 | 0.1772 | 14 |
| 10 | 132.08 | 3.4121 | 4.24 | 0.1640 | 40 |
| 10 | 137.16 | 3.4121 | 4.24 | 0.1640 | 40 |
| 10 | 144.78 | 3.4121 | 4.24 | 0.1640 | 32 |
| 10 | 170.18 | 3.4121 | 4.24 | 0.1640 | 32 |
| 10 | 180.34 | 3.4121 | 4.24 | 0.1640 | 28 |
| 10 | 226.06 | 3.4121 | 4.24 | 0.1640 | 20 |
| 10 | 233.68 | 3.4121 | 4.24 | 0.1640 | 20 |
| 10 | 248.92 | 3.4121 | 4.24 | 0.1640 | 20 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.