SPEC 45263

3/C AL 600V PVC THHN PVC Power Cable With Ground. Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 3 AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA870.134351 x 8600.57261164
    671383670.169301 x 8600.66390220
    TBA470.212501 x 6600.805142324
    675613270.268401 x 6800.945214569
    675618180.298501 x 6801.052263661
    588023180.298501 x 4801.104278599
    6756201/0100.336501 x 4801.132341763
    6756222/0120.376501 x 3801.218429880
    6756243/0150.422501 x 4801.3195181001
    5782184/030.474501 x 2801.4326671145
    6732534/0190.474501 x 2801.4326671140
    583386250220.52601 x 2801.5777761363
    675626250220.52601 x 2801.5777761366
    TBA300370.569701 x 21101.7639141632
    TBA350370.615701 x 21101.86210561829
    678099500340.735601 x 11102.10315062464
    673497600410.812701 x 6001102.49822833358
    599317600410.865701 x 4/01102.31819142925
    677400750580.908701 x 3/01102.52223003580
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA82.22971.0721.290.052354045
    67138362.64720.6740.8120.051405055
    TBA43.27510.4240.510.048556575
    67561323.711940.2670.3210.0457590100
    67561815.215060.2110.2540.04685100115
    58802315.515060.2110.2540.04685100115
    6756201/05.619000.1680.2010.044100120135
    6756222/06.023950.1330.160.043115135150
    6756243/06.530200.1050.1260.042130155175
    5782184/07.138080.0840.10.041150180205
    6732534/07.138080.0840.10.041150180205
    5833862507.845000.0710.0860.041170205230
    6756262507.845000.0710.0860.041170205230
    TBA3008.854000.0590.0710.041195230260
    TBA3509.363000.050.0620.040210250280
    67809950012.690000.0350.0440.039260310350
    67349760014.9108000.0290.0370.039285340385
    59931760013.9108000.0290.0370.039285340385
    67740075015.1135000.0240.0310.038320385435
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C