SPEC 45263
AL 600V PVC-Nylon Insulation PVC Jacket. THHN/THWN-2
Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 3 AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 8 | 7 | 0.134 | 35 | 1 x 8 | 60 | 0.572 | 61 | 164 |
671383 | 6 | 7 | 0.169 | 30 | 1 x 8 | 60 | 0.663 | 90 | 220 |
TBA | 4 | 7 | 0.212 | 50 | 1 x 6 | 60 | 0.805 | 142 | 324 |
675613 | 2 | 7 | 0.268 | 40 | 1 x 6 | 80 | 0.945 | 214 | 569 |
675618 | 1 | 8 | 0.298 | 50 | 1 x 6 | 80 | 1.052 | 263 | 661 |
588023 | 1 | 8 | 0.298 | 50 | 1 x 4 | 80 | 1.104 | 278 | 599 |
675620 | 1/0 | 10 | 0.336 | 50 | 1 x 4 | 80 | 1.132 | 341 | 763 |
675622 | 2/0 | 12 | 0.376 | 50 | 1 x 3 | 80 | 1.218 | 429 | 880 |
675624 | 3/0 | 15 | 0.422 | 50 | 1 x 4 | 80 | 1.319 | 518 | 1001 |
578218 | 4/0 | 19 | 0.474 | 50 | 1 x 2 | 80 | 1.432 | 667 | 1145 |
673253 | 4/0 | 19 | 0.474 | 50 | 1 x 2 | 80 | 1.432 | 667 | 1140 |
583386 | 250 | 22 | 0.520 | 60 | 1 x 2 | 80 | 1.577 | 776 | 1363 |
675626 | 250 | 22 | 0.520 | 60 | 1 x 2 | 80 | 1.577 | 776 | 1366 |
TBA | 300 | 37 | 0.569 | 70 | 1 x 2 | 110 | 1.763 | 914 | 1632 |
TBA | 350 | 37 | 0.615 | 70 | 1 x 2 | 110 | 1.862 | 1056 | 1829 |
678099 | 500 | 34 | 0.735 | 60 | 1 x 1 | 110 | 2.103 | 1506 | 2464 |
673497 | 600 | 41 | 0.812 | 70 | 1 x 600 | 110 | 2.498 | 2283 | 3358 |
599317 | 600 | 41 | 0.865 | 70 | 1 x 4/0 | 110 | 2.318 | 1914 | 2925 |
677400 | 750 | 58 | 0.908 | 70 | 1 x 3/0 | 110 | 2.522 | 2300 | 3580 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
TBA | 8 | 2.2 | 297 | 1.072 | 1.290 | 0.052 | 35 | 40 | 45 |
671383 | 6 | 2.6 | 472 | 0.674 | 0.812 | 0.051 | 40 | 50 | 55 |
TBA | 4 | 3.2 | 751 | 0.424 | 0.510 | 0.048 | 55 | 65 | 75 |
675613 | 2 | 3.7 | 1194 | 0.267 | 0.321 | 0.045 | 75 | 90 | 100 |
675618 | 1 | 5.2 | 1506 | 0.211 | 0.254 | 0.046 | 85 | 100 | 115 |
588023 | 1 | 5.5 | 1506 | 0.211 | 0.254 | 0.046 | 85 | 100 | 115 |
675620 | 1/0 | 5.6 | 1900 | 0.168 | 0.201 | 0.044 | 100 | 120 | 135 |
675622 | 2/0 | 6.0 | 2395 | 0.133 | 0.160 | 0.043 | 115 | 135 | 150 |
675624 | 3/0 | 6.5 | 3020 | 0.105 | 0.126 | 0.042 | 130 | 155 | 175 |
578218 | 4/0 | 7.1 | 3808 | 0.084 | 0.100 | 0.041 | 150 | 180 | 205 |
673253 | 4/0 | 7.1 | 3808 | 0.084 | 0.100 | 0.041 | 150 | 180 | 205 |
583386 | 250 | 7.8 | 4500 | 0.071 | 0.086 | 0.041 | 170 | 205 | 230 |
675626 | 250 | 7.8 | 4500 | 0.071 | 0.086 | 0.041 | 170 | 205 | 230 |
TBA | 300 | 8.8 | 5400 | 0.059 | 0.071 | 0.041 | 195 | 230 | 260 |
TBA | 350 | 9.3 | 6300 | 0.050 | 0.062 | 0.040 | 210 | 250 | 280 |
678099 | 500 | 12.6 | 9000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
673497 | 600 | 14.9 | 10800 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
599317 | 600 | 13.9 | 10800 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
677400 | 750 | 15.1 | 13500 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C