SPEC 45260

FLEXTOR™ CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable Flexible 600Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Green Insulated CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

...

Construction:

  1. Conductor:Class C compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN. Colors: Gray, Brown, Orange, Yellow.
  3. Grounding Conductor:Green insulated THHN Class C compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER flexible power cables are made with class C copper stranding for extra flexibilty suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessInsulation ColorGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA84190.14335BN,OE,YW,GY1 x 10600.641238343BK
    TBA64190.17935BN,OE,YW,GY1 x 8600.729378502BK
    66936744190.22640BN,OE,YW,GY1 x 8801.019572864BK
    64369724190.28640BN,OE,YW,GY1 x 6801.1589091243BK
    TBA14370.33360BN,OE,YW,GY1 x 6801.26211231457BK
    TBA1/04370.37460BN,OE,YW,GY1 x 6801.36113981764BK
    TBA2/04370.4260BN,OE,YW,GY1 x 6801.47317412142BK
    TBA3/04370.47160BN,OE,YW,GY1 x 4801.59622212661BK
    TBA4/04370.52960BN,OE,YW,GY1 x 41101.79727673345BK
    TBA2504610.57670BN,OE,YW,GY1 x 41101.95932473928BK
    TBA3504610.68170BN,OE,YW,GY1 x 31102.21345305312BK
    TBA5004610.81570BN,OE,YW,GY1 x 21102.53764427353BK
    TBA7504910.99980BN,OE,YW,GY1 x 11403.091961410957BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA842.65280.6530.810.0524044
    TBA642.98390.4110.510.0515260
    669367445.113350.2580.320.0486876
    643697245.821230.1620.2010.04592104
    TBA146.326780.1280.1590.046104116
    TBA1/046.833790.1020.1270.044120136
    TBA2/047.442590.0820.1020.043140156
    TBA3/04853690.0640.0790.042160180
    TBA4/04967710.0510.0630.041184208
    TBA25049.880000.0430.0530.041204232
    TBA350413.3112000.0310.0390.04248280
    TBA500415.2160000.0210.0270.039304344
    TBA750418.5240000.0140.0190.038380428
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.005

    Updated On: Feb. 11, 2025, 12:09 p.m. UTC