SPEC 45260
FLEXTOR™ CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable Flexible 600Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Green Insulated CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Construction:
- Conductor:Class C compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN. Colors: Gray, Brown, Orange, Yellow.
- Grounding Conductor:Green insulated THHN Class C compressed stranded bare copper per ASTM B3 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER flexible power cables are made with class C copper stranding for extra flexibilty suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Insulation Color | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | ||||
| TBA | 8 | 4 | 19 | 0.143 | 35 | BN,OE,YW,GY | 1 x 10 | 60 | 0.641 | 238 | 343 | BK |
| TBA | 6 | 4 | 19 | 0.179 | 35 | BN,OE,YW,GY | 1 x 8 | 60 | 0.729 | 378 | 502 | BK |
| 669367 | 4 | 4 | 19 | 0.226 | 40 | BN,OE,YW,GY | 1 x 8 | 80 | 1.019 | 572 | 864 | BK |
| 643697 | 2 | 4 | 19 | 0.286 | 40 | BN,OE,YW,GY | 1 x 6 | 80 | 1.158 | 909 | 1243 | BK |
| TBA | 1 | 4 | 37 | 0.333 | 60 | BN,OE,YW,GY | 1 x 6 | 80 | 1.262 | 1123 | 1457 | BK |
| TBA | 1/0 | 4 | 37 | 0.374 | 60 | BN,OE,YW,GY | 1 x 6 | 80 | 1.361 | 1398 | 1764 | BK |
| TBA | 2/0 | 4 | 37 | 0.42 | 60 | BN,OE,YW,GY | 1 x 6 | 80 | 1.473 | 1741 | 2142 | BK |
| TBA | 3/0 | 4 | 37 | 0.471 | 60 | BN,OE,YW,GY | 1 x 4 | 80 | 1.596 | 2221 | 2661 | BK |
| TBA | 4/0 | 4 | 37 | 0.529 | 60 | BN,OE,YW,GY | 1 x 4 | 110 | 1.797 | 2767 | 3345 | BK |
| TBA | 250 | 4 | 61 | 0.576 | 70 | BN,OE,YW,GY | 1 x 4 | 110 | 1.959 | 3247 | 3928 | BK |
| TBA | 350 | 4 | 61 | 0.681 | 70 | BN,OE,YW,GY | 1 x 3 | 110 | 2.213 | 4530 | 5312 | BK |
| TBA | 500 | 4 | 61 | 0.815 | 70 | BN,OE,YW,GY | 1 x 2 | 110 | 2.537 | 6442 | 7353 | BK |
| TBA | 750 | 4 | 91 | 0.999 | 80 | BN,OE,YW,GY | 1 x 1 | 140 | 3.091 | 9614 | 10957 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 4 | 2.6 | 528 | 0.653 | 0.81 | 0.052 | 40 | 44 |
| TBA | 6 | 4 | 2.9 | 839 | 0.411 | 0.51 | 0.051 | 52 | 60 |
| 669367 | 4 | 4 | 5.1 | 1335 | 0.258 | 0.32 | 0.048 | 68 | 76 |
| 643697 | 2 | 4 | 5.8 | 2123 | 0.162 | 0.201 | 0.045 | 92 | 104 |
| TBA | 1 | 4 | 6.3 | 2678 | 0.128 | 0.159 | 0.046 | 104 | 116 |
| TBA | 1/0 | 4 | 6.8 | 3379 | 0.102 | 0.127 | 0.044 | 120 | 136 |
| TBA | 2/0 | 4 | 7.4 | 4259 | 0.082 | 0.102 | 0.043 | 140 | 156 |
| TBA | 3/0 | 4 | 8 | 5369 | 0.064 | 0.079 | 0.042 | 160 | 180 |
| TBA | 4/0 | 4 | 9 | 6771 | 0.051 | 0.063 | 0.041 | 184 | 208 |
| TBA | 250 | 4 | 9.8 | 8000 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| TBA | 350 | 4 | 13.3 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| TBA | 500 | 4 | 15.2 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
| TBA | 750 | 4 | 18.5 | 24000 | 0.014 | 0.019 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.005
Updated On: Feb. 11, 2025, 12:09 p.m. UTC

