SPEC 60509

Titan2™ Type EF Extra-Flexible Liquidtight Metal Conduit

Extra-Flexible Liquidtight Metal Conduit. General Purpose Use. Oil-Resistant. Sunlight-Resistant. Temperature Rated -10°C to 60°C.

...

Construction:

  1. Armor:Titan2™ Type EF is manufactured with a spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steel.
  2. Jacket:A flame retardant, flexible PVC jacket is extruded over the metal core. The gray jacket resists oils, mild acids and exposure to sunlight. Black jacket available but subject to economic order quantity.

Applications and Features:

Titan2™ Extra-Flexible Liquidtight Flexible Metallic Conduit is suitable of the following installations:
  • Delivers wiring protection where listed products are not required
  • Seals out abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated fixed alkaline, petroleum oils, salt air spray, water and weather.
  • Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment where UL listing is not required
  • Applications requiring movement, crossover connections, or tight bends

  • Features
  • Resistant to weather, heat, oil, and chemical breakdown
  • Smooth metal interior for easy wire pulling
  • Requires standard liquid-tight fittings
  • Rated for temperature range of -10°C to 60°C (14°F to 140°F)
  • Sample Print Legend:

    {SQFTG_DUAL} {SOUTHWIRE} {TITAN2_TM} ALFLEX-C - X" - (TYPE EF) - SUNLIGHT RESISTANT

    Titan2™ Type EF Extra-Flexible Gray

    Trade SizeInner Diam (Min/Max)Outer Diam (Min/Max)WeightMinimum Bend Radius
    InchInchInchLb/100ftInch
    3/80.484/0.5040.690/0.710163*
    1/20.622/0.6420.820/0.840194
    3/40.820/0.8401.030/1.050275
    11.041/1.0661.290/1.315438
    1-1/41.380/1.4101.630/1.6605610
    1-1/21.575/1.6001.865/1.9008312
    22.020/2.0452.340/2.37511016
    2-1/22.480/2.5052.840/2.87513720
    33.070/3.1003.460/3.50016324
    3-1/23.500/3.5403.960/4.00020228
    44.000/4.0404.460/4.50023532

    * Suggestion only. Non-NEC requirement

    Titan2™ Type EF Extra-Flexible Black

    Trade SizeInner Diam (Min/Max)Outer Diam (Min/Max)WeightMinimum Bend Radius
    InchInchInchLb/100ftInch
    1/20.622/0.6420.820/0.840194
    3/40.820/0.8401.030/1.050275
    1-1/21.575/1.6001.865/1.9008312

    Put Ups

    TRADE SIZE (Inch)25 ft50 ft100 ft150 ft250 ft300ft400 ft500 ft600 ft1000 ft
    Trade Size (Inch)25 ft50 ft100 ft150 ft250 ft300 ft400 ft500 ft600 ft1000 ft
    3/8550937035509370155093704
    1/2550938015509380555093802
    3/4550940035509400555094002
    15510680255106803
    1-1/45510700255107004
    1-1/25510710255107103
    25510720255107203
    2-1/25510730155107303
    35510740155107403
    3-1/25510750155107503
    45510760155107603