SPEC 25055

3/C CSA TECK 90 1000V ALUMINUM POWER CABLE

Three Conductor 1000V Multi Conductor, FT4 - Flame Retardancy Rating, Direct Burial, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40ºC Min, 90ºC Max, Rated HL (Hazardous Locations)

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series Aluminum.
  2. Insulation:Cross-Linked Polyethylene (XLPE), Color Code: Black and numbered
  3. Grounding Conductors:Uninsulated Aluminum Class B stranded grounding conductor
  4. Assembly:Polypropylene tape
  5. Inner Jacket:Black Polyvinyl Chloride (PVC)
  6. Armor:Aluminum Interlocked Armour (AIA)
  7. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Voltage 1000V CSA / 600V UL.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 1569 Metal-Clad Cables
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQMTR_DUAL} SOUTHWIRE® {CSA} LL90458 X/C XX AWG 8000 TECK 90 XLPE -40°C FT4 SUN RES 90°C 1000V HL USA {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90°C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ft
    584846^670.1690.295601x66650.7731.09551.20537
    674938^470.2130.339601x66850.9081.227551.3370685
    584848^260.2680.394601x66851.0271.346551.4560819
    584852180.2990.467801x44851.1851.503651.63501031
    5848731/0180.3360.504801x44851.2651.583651.71501144
    5848762/0120.3760.544801x44851.3511.67651.80201294
    5848833/0160.4230.591801x44851.4531.771651.90301459
    5848914/0180.4750.643801x44851.5651.893652.02501717
    583957250350.520.709901x221151.7672.099652.23102105
    615167350350.6160.805901x221151.9752.306752.45602593
    583961500350.7360.927901x111152.2382.566802.73203285
    668789750530.9081.097901x1/01/01152.6062.937803.10304318
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    68.44720.6740.840.05155
    49.47510.4240.5280.04875
    210.211940.2660.3310.045100
    111.415060.2110.2630.046115
    1/01219000.1670.2080.044135
    2/012.623950.1330.1660.043150
    3/013.330200.1050.1310.042175
    4/014.238080.0840.1050.041205
    25015.645000.070.0870.041230
    35017.263000.0510.0640.04280
    50019.190000.0360.0450.039350
    75021.7135000.0230.030.038435
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/km
    584846^674.297.491.521x661.6519.6327.691.4030.480799
    674938^475.418.611.521x662.1623.0631.171.4033.9601019
    584848^266.8110.011.521x662.1626.0934.191.4036.9801219
    584852187.5911.862.031x442.1630.1038.181.6541.5301534
    5848731/0188.5312.802.031x442.1632.1340.211.6543.5601702
    5848762/0129.5513.822.031x442.1634.3242.421.6545.7701926
    5848833/01610.7415.012.031x442.1636.9144.981.6548.3402171
    5848914/01812.0716.332.031x442.1639.7548.081.6551.4302555
    5839572503513.2118.012.291x222.9244.8853.311.6556.6703133
    6151673503515.6520.452.291x222.9250.1758.571.9162.3803859
    5839615003518.6923.552.291x112.9256.8565.182.0369.3904889
    6687897505323.0627.862.291x1/01/02.9266.1974.602.0378.8206426
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmp
    6213.3621002.21132.760.167355
    4238.7633421.39111.730.157575
    2259.0853130.87271.090.1476100
    1289.5667020.69230.860.1509115
    1/0304.8084550.54790.680.1444135
    2/0320.04106580.43640.540.1411150
    3/0337.82134390.34450.430.1378175
    4/0360.68169460.27560.340.1345205
    250396.24200250.22970.290.1345230
    350436.88280350.16730.210.1312280
    500485.14400500.11810.150.1280350
    750551.18600750.07550.100.1247435
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.011

    Updated On: Oct. 23, 2026, 11:19 a.m. UTC