SPEC 13143

Category 6A CMR-LP

...

Construction:

  1. Conductor:Bare solid copper
  2. Insulation:High density polyethylene HDPE
  3. Separator:Spline separator cabled and jacketed
  4. Tape:Non-continuous aluminum tape
  5. Jacket:Fire Resistant Polyvinyl Chloride FR PVC.

Applications and Features:

Southwire Cat 6A unshielded twisted pair cable is a high performance data communication cable. This ethernet cable is designed for indoor and riser network installations type CMR (Riser rated communication cable), may be used in Ethernet Networking system, PoE applications, Video MPEG4 / M-JPEG / Digital / Analog / Baseband / Broadband and other Multimedia Voice applications.

  • DC Resistance: <9.38 ohm/100m
  • DC Resistance Unbalance: Max 4.00%
  • Mutual Capacitance: 56 pF/m
  • Capacitance Unbalance (Pair to Ground): 3.3 pF/m
  • Insulation Resistance: >1000 MOhm-km
  • Impedance (mean): 100+/- 15% (1 < freq < 500MHz)
  • Specifications:

  • UL 444 Listed CMR
  • IEEE 802.3 and IEC 61156-5 Ed. 2.0
  • RoHS-3 Complies with European Directive 2015/863
  • NFPA 262
  • TIA/EIA 568-D.2 (Cat. 6A) Standard
  • NEC Article 800
  • Sample Print Legend:

    6AR AUGMENTED - CAT 6A SOUTHWIRE (R) TAPPAN (TM) I99980 - E160837 23AWG 4PR U/UTP TYPE CMR-LP (0.5A) 75°C C(UL)US LISTED -- ETL VERIFIED TO TIA-568.2-D CATEGORY 6A ROHS-2 COMPLIANT ZYYMMDDHHmm(*) (**)FT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeNumber of PairsJacket ThicknessApprox. ODApprox. Weight
    AWG/Kcmilpairmilinchlb/1000ft
    I99980234180.30726
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeNumber of PairsJacket ThicknessApprox. ODApprox. Weight
    AWG/Kcmilpairmmmmlb/km
    I999802340.467.8039

    Electrical Performance

    MHzRLILNEXTPSNEXTPSELFEXTPSANEXTPSAACRFSkew
    (Min-dB)(Max-dB)(Min-dB)(Min-dB)(Min-dB)(Min-dB)(Min-dB)(Max-ns)
    1202.174.372.372.3676745
    4233.865.363.363.36766.245
    824.55.360.858.858.86760.145
    10255.959.357.357.36758.245
    16257.556.254.254.26754.145
    20258.454.852.852.86752.245
    2524.39.453.351.351.36750.245
    31.2523.610.551.949.949.96748.345
    62.521.51547.445.445.465.642.345
    10020.119.144.342.342.362.538.245
    2001827.639.837.837.85832.245
    25017.331.138.336.336.356.530.245
    30016.834.337.135.135.155.328.745
    40015.940.135.333.333.353.526.245
    50015.245.333.831.831.85224.245

    Revision: 1.000.137

    Updated On: Dec. 13, 2024, 5:44 p.m. UTC