SPEC 13060

Multi Conductor CL3R/ FPLR/ CMR/ CMG Non-Shielded

300V, 75°C, Multi-Conductor, Non-Shielded, Stranded Copper, CL3R/FPLR/CMR/CMG

...

Construction:

  1. Conductor:Stranded bare copper per ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC)
  3. Rip Cord:Rip cord for ease of jacket removal
  4. Jacket: Gray Polyvinyl Chloride (PVC)

Applications and Features:

For use in Remote Control, Signaling, and Power-Limited circuits per NEC Article 725. Sizes 22 AWG - 16 AWG can also be used as communication circuits per NEC Article 800. Can be used in security, sound and audio, speaker cable, public address, intercom, sound reinforcement, alarm and access control circuits and power-limited controls. The conductors are cabled together; lay length varies depending on conductor count and gauge size.

  • Flame Test: UL 1666
  • Cable Type: CL3R, also, CMR where UL permits (Sizes 16 AWG and smaller)
  • Voltage: 300 Volts
  • Temperature: 75ºC
  • Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 13 Power-Limited Circuit Cables
  • UL 444 Communications Cables (90ºC, 300V)
  • Sample Print Legend:

    XX AWG XX/C E57497 c{UL}US CMR/CL3R/FPLR -- CMG FT4 MADE IN USA ROHS-2 COMPLIANT -- {MM/DD/YY} {HH:MM} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Jacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive Rectance
    AWGNo.strandsinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ft
    22 AWG
    R20004-122270.022150.1204816.7220.150.030
    R20045-122470.022150.14981516.7220.150.030
    R20047-122670.022150.157132016.7220.150.030
    R20025-122870.022150.181172616.7220.150.030
    R20051-1221070.022150.194213216.7220.150.030
    R20487-1221270.022150.225263816.7220.150.030
    20 AWG
    R30017-120270.036150.13261110.5012.650.027
    18 AWG
    R40001-118270.045150.14410146.6698.0350.036
    R40018-118270.045200.14410146.6698.0350.036
    R40048-118370.045200.15315206.6698.0350.036
    R40049-118470.045200.16620286.6698.0350.036
    R40015-118670.045200.21230416.6698.0350.036
    R40052-118870.045200.23040536.6698.0350.036
    R40054-1181070.045200.26250646.6698.0350.036
    R40024-1181270.045200.27160756.6698.0350.036
    16 AWG
    R50003-1162190.056200.17416224.1815.0370.033
    R50045-1164190.056200.21232414.1815.0370.033
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.007

    Updated On: Dec. 13, 2024, 4:49 p.m. UTC