SPEC 60386
Alumaflex™ Riser MC™ THHN/THWN-2 Aluminum Conductor Feeder Cable
AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Binder Sheath for Continuous Conductor Support. Lightweight Aluminum Interlocked Armor.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801 or B836
- Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN-2
- Ground:Bare aluminum ground
- Binder:Mylar tape
- Polymeric Binder:Polymeric binder sheath under armor for continuous conductor support
- Armor:Aluminum Interlocked Armor
Applications and Features:
Southwire Armorlite® Type MC Riser Feeder cable is suitable for use as follows:
- Riser cable, vertical applications
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5.
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Conductors are Type THHN/THWN-2 rated 90ºC Wet and Dry. Unjacketed MC cables are not rated for wet locations.
Southwire Armorlite® Type MC Riser Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
- Riser cable, vertical applications
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5.
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Conductors are Type THHN/THWN-2 rated 90ºC Wet and Dry. Unjacketed MC cables are not rated for wet locations.
Southwire Armorlite® Type MC Riser Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE {UL} X/C XX AWG COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 THHN/THWN-2 CDRS 600V GW 1 X X AWG 3E AL TYPE MC FOR CT USE.
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Conductor Number | Color | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Ground Size | Diameter Over Armor | Overall Weight |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | mils | No. x AWG | inch | lbs/1000ft | ||||
| 583766◊ | 2/0 | 3 | BK,RD,WE | 0.364 | 19 | 60 | 1x4 | 1.750 | 1090 |
| 583913◊ | 3/0 | 3 | BK,RD,WE | 0.422 | 19 | 60 | 1x4 | 1.864 | 1245 |
| 599417 | 4/0 | 4 | BK,WE,RD,BE | 0.46 | 19 | 60 | 1x2 | 2.106 | 1811 |
| 583917◊ | 4/0 | 3 | BK,RD,WE | 0.460 | 19 | 60 | 1x2 | 1.943 | 1445 |
| 647493 | 250 | 4 | BN,OE,YW,GY | 0.52 | 22 | 70 | 1x1 | 2.243 | 2105 |
| 573432◊ | 250 | 3 | BN,OE,YW | 0.520 | 35 | 70 | 1x3/0 | 1.985 | 1693 |
| 580637◊ | 250 | 3 | BN,OE,YW | 0.520 | 35 | 70 | 1x1 | 1.985 | 1613 |
| 646549◊ | 300 | 3 | BN,OE,YW | 0.569 | 35 | 70 | 1x1 | 2.093 | 1858 |
| 677601 | 300 | 4 | BK,RD,BE,WE | 0.569 | 21 | 70 | 1x2 | 2.286 | 2296 |
| 677621◊ | 350 | 3 | BN,OE,YW | 0.615 | 35 | 70 | 1x1 | 2.192 | 2012 |
| 575252 | 350 | 4 | BN,OE,YW,GY | 0.615 | 34 | 70 | 1x1/0 | 2.397 | 2585 |
| 678297 | 350 | 4 | BK,WE,RD,BE | 0.615 | 35 | 70 | 1x1 | 2.397 | 2563 |
| 597913◊ | 400 | 3 | BN,OE,YW | 0.659 | 35 | 70 | 1x3/0 | 2.373 | 2369 |
| 677373 | 400 | 3 | BN,OE,YW | 0.659 | 35 | 70 | 1x1/0 | 2.333 | 2303 |
| 573254◊ | 500 | 3 | BN,OE,YW | 0.735 | 35 | 70 | 1x250 | 2.673 | 2818 |
| 640673 | 500 | 4 | BN,OE,YW,GY,GN | 0.735 | 34 | 70 | 1x2/0 | 2.8 | 3445 |
| 643956 | 500 | 4 | BK,RD,BE,WE,GN | 0.735 | 34 | 70 | 1x3/0 | 2.687 | 3444 |
| 641550◊ | 600 | 3 | BN,OE,YW | 0.812 | 58 | 80 | 1x4/0 | 2.665 | 3153 |
| 674367 | 600 | 4 | BN,OE,YW,GY,GN | 0.812 | 58 | 80 | 1x2/0 | 2.907 | 3996 |
| 640676 | 600 | 4 | BN,OE,YW,GY,GN | 0.812 | 41 | 80 | 1x350 | 3.073 | 4304 |
| 562700◊ | 750 | 3 | BN,OE,YW | 0.908 | 53 | 80 | 1x3/0 | 2.870 | 3682 |
| 641914◊ | 750 | 3 | BN,OE,YW | 0.908 | 58 | 80 | 1x750 | 3.141 | 4308 |
| 649342 | 750 | 4 | BN,OE,YW,GY,GN | 0.908 | 53 | 80 | 1x3/0 | 3.198 | 4796 |
| 649354◊ | 4 | 4 | BK,RD,BE,WE | 0.204 | 7 | 50 | 1x8 CU | 1.298 | 999 |
| 643253◊ | 4 | 4 | BN,OE,YW,GY | 0.212 | 7 | 50 | 1x6 | 1.248 | 593 |
| 641362◊ | 2 | 4 | BK,RD,BE,WE | 0.268 | 7 | 50 | 1x4 | 1.398 | 775 |
| 597542◊ | 1 | 4 | BK,WE,RD,BE | 0.298 | 19 | 60 | 1x4 | 1.613 | 969 |
| 583762◊ | 1/0 | 4 | BN,OE,YW,GY | 0.324 | 19 | 60 | 1x4 | 1.818 | 1195 |
| 596279◊ | 2/0 | 4 | BK,WE,RD,BE | 0.364 | 19 | 60 | 1x4 | 1.768 | 1247 |
| 456832◊ | 2/0 | 4 | BK,RD,BE,WE | 0.376 | 12 | 60 | 1x4 | 1.82 | 1328 |
| 593349◊ | 3/0 | 4 | BK,WE,RD,BE | 0.409 | 19 | 60 | 1x4 | 2.017 | 1488 |
| 581869◊ | 4/0 | 4 | BN,OE,YW,GY | 0.460 | 19 | 60 | 1x1 | 2.103 | 1792 |
| 671853◊ | 4/0 | 4 | BK,RD,BE,WE | 0.460 | 19 | 60 | 1x1/0 | 2.158 | 1790 |
| 561133◊ | 250 | 4 | BK,RD,BE,WE | 0.520 | 35 | 70 | 1x1 | 2.151 | 1986 |
| 565212◊ | 250 | 4 | BN,OE,YW,GY | 0.520 | 35 | 70 | 1x1 | 2.151 | 1986 |
| 641535◊ | 300 | 4 | BK,RD,BE,WE | 0.569 | 35 | 70 | 1x1 | 2.272 | 2252 |
| 561135◊ | 350 | 4 | BK,WE,RD,BE | 0.615 | 35 | 70 | 1x1/0 | 2.383 | 2523 |
| 649344◊ | 350 | 4 | BN,OE,YW,GY | 0.615 | 35 | 70 | 1x2 | 2.428 | 2528 |
| 580634◊ | 400 | 4 | BN,OE,YW,GY | 0.659 | 35 | 70 | 1x3/0 | 2.487 | 2833 |
| 561136◊ | 500 | 4 | BK,RD,BE,WE | 0.735 | 35 | 70 | 1x3/0 | 2.673 | 3324 |
| 649347◊ | 500 | 4 | BN,OE,YW,GY | 0.735 | 35 | 70 | 1x1 | 2.728 | 3299 |
| 564942◊ | 500 | 4 | BN,OE,YW,GY | 0.735 | 35 | 70 | 1x3/0 | 2.673 | 3324 |
| 567308◊ | 600 | 4 | BN,OE,YW,GY | 0.812 | 58 | 80 | 1x400 | 3.138 | 4302 |
| 456861◊ | 600 | 4 | RD,BE,WE,GN | 0.812 | 58 | 80 | 1x600 | 3.205 | 4625 |
| 643618◊ | 750 | 4 | BK,RD,BE,WE | 0.908 | 58 | 80 | 1x750 | 3.450 | 5434 |
| 643936◊ | 750 | 4 | BK,RD,BE,WE | 0.908 | 58 | 80 | 1x600 | 3.450 | 5276 |
| 561137◊ | 750 | 4 | BK,RD,BE,WE | 0.908 | 58 | 80 | 1x3/0 | 3.145 | 4623 |
| 580975◊ | 900 | 4 | BN,OE,YW,GY | 0.999 | 58 | 80 | 1x250 | 3.393 | 5506 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Conductor Number | Min. Bend Radius | Max Pull Tension | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Inches | Lbs | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| 2/0 | 3 | 12.3 | 2395 | 0.081 | 0.097 | 0.043 | 135 | 150 |
| 3/0 | 3 | 13.0 | 3020 | 0.105 | 0.126 | 0.042 | 155 | 175 |
| 4/0 | 4 | 14.7 | 4062 | 0.051 | 0.061 | 0.041 | 144 | 164 |
| 4/0 | 3 | 13.6 | 3808 | 0.051 | 0.061 | 0.041 | 180 | 205 |
| 250 | 4 | 15.7 | 6000 | 0.071 | 0.086 | 0.041 | 164 | 184 |
| 250 | 3 | 13.0 | 4500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
| 250 | 3 | 13.0 | 4500 | 0.071 | 0.086 | 0.041 | 205 | 230 |
| 300 | 3 | 13.7 | 5400 | 0.059 | 0.071 | 0.041 | 230 | 260 |
| 300 | 4 | 16 | 7200 | 0.059 | 0.071 | 0.04 | 184 | 208 |
| 350 | 3 | 14.4 | 6300 | 0.050 | 0.062 | 0.040 | 250 | 280 |
| 350 | 4 | 16.8 | 8400 | 0.05 | 0.062 | 0.04 | 200 | 224 |
| 350 | 4 | 16.8 | 8400 | 0.05 | 0.062 | 0.04 | 200 | 224 |
| 400 | 3 | 15.1 | 7200 | 0.044 | 0.054 | 0.040 | 270 | 305 |
| 400 | 3 | 16.3 | 7200 | 0.044 | 0.054 | 0.04 | 270 | 305 |
| 500 | 3 | 16.3 | 9000 | 0.035 | 0.044 | 0.039 | 310 | 350 |
| 500 | 4 | 19.6 | 12000 | 0.022 | 0.029 | 0.039 | 248 | 280 |
| 500 | 4 | 18.8 | 12000 | 0.022 | 0.029 | 0.039 | 248 | 280 |
| 600 | 3 | 17.9 | 10800 | 0.029 | 0.037 | 0.039 | 340 | 385 |
| 600 | 4 | 20.3 | 14400 | 0.029 | 0.037 | 0.039 | 272 | 308 |
| 600 | 4 | 21.5 | 14400 | 0.029 | 0.037 | 0.039 | 272 | 308 |
| 750 | 3 | 20.2 | 13500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
| 750 | 3 | 19.4 | 13500 | 0.024 | 0.031 | 0.038 | 385 | 435 |
| 750 | 4 | 22.4 | 18000 | 0.024 | 0.031 | 0.038 | 308 | 348 |
| 4 | 4 | 9.1 | 801 | 0.258 | 0.310 | 0.048 | 52 | 60 |
| 4 | 4 | 8.7 | 801 | 0.424 | 0.510 | 0.048 | 52 | 60 |
| 2 | 4 | 9.8 | 1274 | 0.267 | 0.321 | 0.045 | 72 | 80 |
| 1 | 4 | 11.3 | 1606 | 0.211 | 0.254 | 0.046 | 80 | 92 |
| 1/0 | 4 | 12.7 | 2027 | 0.102 | 0.122 | 0.044 | 96 | 108 |
| 2/0 | 4 | 12.4 | 2555 | 0.081 | 0.097 | 0.043 | 108 | 120 |
| 2/0 | 4 | 12.7 | 2555 | 0.133 | 0.16 | 0.043 | 108 | 120 |
| 3/0 | 4 | 14.1 | 3221 | 0.064 | 0.077 | 0.042 | 124 | 140 |
| 4/0 | 4 | 14.7 | 4062 | 0.051 | 0.061 | 0.041 | 144 | 164 |
| 4/0 | 4 | 15.1 | 4062 | 0.051 | 0.061 | 0.041 | 144 | 164 |
| 250 | 4 | 14.2 | 4800 | 0.071 | 0.086 | 0.041 | 164 | 184 |
| 250 | 4 | 14.2 | 4800 | 0.071 | 0.086 | 0.041 | 164 | 184 |
| 300 | 4 | 15.0 | 5760 | 0.059 | 0.071 | 0.041 | 184 | 208 |
| 350 | 4 | 15.8 | 6720 | 0.050 | 0.062 | 0.040 | 200 | 224 |
| 350 | 4 | 15.8 | 6720 | 0.050 | 0.062 | 0.040 | 200 | 224 |
| 400 | 4 | 16.6 | 7680 | 0.044 | 0.054 | 0.040 | 216 | 244 |
| 500 | 4 | 18.1 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
| 500 | 4 | 18.1 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
| 500 | 4 | 18.1 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
| 600 | 4 | 19.7 | 11520 | 0.029 | 0.037 | 0.039 | 272 | 308 |
| 600 | 4 | 22.4 | 11520 | 0.029 | 0.037 | 0.039 | 272 | 308 |
| 750 | 4 | 21.3 | 14400 | 0.024 | 0.031 | 0.038 | 308 | 348 |
| 750 | 4 | 21.3 | 14400 | 0.024 | 0.031 | 0.038 | 308 | 348 |
| 750 | 4 | 21.3 | 14400 | 0.024 | 0.031 | 0.038 | 308 | 348 |
| 900 | 4 | 23.0 | 17280 | 0.020 | 0.027 | 0.037 | 340 | 384 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.008
Updated On: Dec. 31, 2024, 11:08 p.m. UTC

