SPEC 60386

Alumaflex™ Riser MC™ THHN/THWN-2 Aluminum Conductor Feeder Cable

AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Binder Sheath for Continuous Conductor Support. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801 or B836
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN-2
  3. Ground:Bare aluminum ground
  4. Binder:Mylar tape
  5. Polymeric Binder:Polymeric binder sheath under armor for continuous conductor support
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Riser Feeder cable is suitable for use as follows:
- Riser cable, vertical applications
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5.
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Conductors are Type THHN/THWN-2 rated 90ºC Wet and Dry. Unjacketed MC cables are not rated for wet locations.

Southwire Armorlite® Type MC Riser Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE {UL} X/C XX AWG COMPACT 8000 AL. --- TRIPLE E ALLOY AA8176 THHN/THWN-2 CDRS 600V GW 1 X X AWG 3E AL TYPE MC FOR CT USE.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    583766◊2/03BK,RD,WE0.3761501x41.7651105
    583913◊3/03BK,RD,WE0.42318501x41.8791261
    583917◊4/03BK,RD,WE0.4751501x21.9431457
    5994174/04BK,WE,RD,BE0.4751501x22.1061811
    573432◊2503BN,OE,YW0.521601x3/01.9981708
    580637◊2503BN,OE,YW0.521601x11.9981628
    6474932504BN,OE,YW,GY0.521601x12.2432106
    646549◊3003BN,OE,YW0.571601x12.1061875
    6776013004BK,RD,BE,WE0.571601x22.2872295
    677621◊3503BN,OE,YW0.6161601x12.2052028
    5752523504BN,OE,YW,GY0.6161601x1/02.3982584
    6782973504BK,WE,RD,BE0.6161601x12.3982563
    597913◊4003BN,OE,YW0.6591601x3/02.3732387
    6773734003BN,OE,YW0.6591601x1/02.3342303
    573254◊5003BN,OE,YW0.7361601x2502.6882878
    6406735004BN,OE,YW,GY,GN0.7361601x2/02.83444
    6439565004BK,RD,BE,WE,GN0.7361601x3/02.6883444
    641550◊6003BN,OE,YW0.8131701x4/02.6613173
    6743676004BN,OE,YW,GY,GN0.8131701x2/02.9073995
    6406766004BN,OE,YW,GY,GN0.8131701x3503.0734303
    562700◊7503BN,OE,YW0.90853701x3/02.8843682
    641914◊7503BN,OE,YW0.9081701x7503.1564404
    6493427504BN,OE,YW,GY,GN0.9081701x3/03.1984797
    643253◊44BN,OE,YW,GY0.21318401x61.248604
    649354◊44BK,RD,BE,WE0.2131401x81.2981021
    641362◊24BK,RD,BE,WE0.26818401x41.398786
    597542◊14BK,WE,RD,BE0.29918501x41.6131000
    583762◊1/04BN,OE,YW,GY0.3361501x41.8181206
    596279◊2/04BK,WE,RD,BE0.3761501x41.7681278
    456832◊2/04BK,RD,BE,WE0.3761501x41.821329
    593349◊3/04BK,WE,RD,BE0.4231501x42.0341537
    671853◊4/04BK,RD,BE,WE0.4751501x1/02.1741842
    581869◊4/05BN,OE,YW,GY0.4751501x12.0921859
    561133◊2504BK,RD,BE,WE0.521601x12.1662038
    565212◊2504BN,OE,YW,GY0.521601x12.1662051
    641535◊3004BK,RD,BE,WE0.571601x12.2872329
    561135◊3504BK,WE,RD,BE0.6161601x1/02.3982600
    649344◊3504BN,OE,YW,GY0.6161601x22.4282588
    580634◊4004BN,OE,YW,GY0.6591601x3/02.5022897
    561136◊5004BK,RD,BE,WE0.7361601x3/02.6883420
    649347◊5004BN,OE,YW,GY0.7361601x12.7283362
    564942◊5004BN,OE,YW,GY0.7361601x3/02.6883420
    567308◊6004BN,OE,YW,GY0.8131701x4003.114372
    456861◊6004RD,BE,WE,GN0.8131701x6003.2064626
    643618◊7504BK,RD,BE,WE0.9081701x7503.4665635
    643936◊7504BK,RD,BE,WE0.9081701x6003.455409
    561137◊7504BK,RD,BE,WE0.9081701x3/03.164748
    580975◊9004BN,OE,YW,GY0.9991701x2503.3935595
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    2/0312.423950.1330.1660.043135150
    3/0313.230200.1050.1310.042155175
    4/0313.638080.0840.1050.041180205
    4/0414.750780.0840.1050.041144164
    25031445000.070.0870.041205230
    25031445000.070.0870.041205230
    250415.760000.070.0870.041164184
    300314.754000.0590.0740.041230260
    30041672000.0590.0740.041184208
    350315.463000.0510.0640.04250280
    350416.884000.0510.0640.04200224
    350416.884000.0510.0640.04200224
    400316.672000.0440.0550.04270305
    400316.372000.0440.0550.04270305
    500318.890000.0360.0450.039310350
    500419.6120000.0360.0450.039248280
    500418.8120000.0360.0450.039248280
    600318.6108000.030.0380.039340385
    600420.3144000.030.0380.039272308
    600421.5144000.030.0380.039272308
    750320.2135000.0230.030.038385435
    750322.1135000.0230.030.038385435
    750422.4180000.0230.030.038308348
    448.710010.4240.5280.0485260
    449.110010.4240.5280.0485260
    249.815920.2660.3310.0457280
    1411.320080.2110.2630.0468092
    1/0412.725340.1670.2080.04496108
    2/0412.431940.1330.1660.043108120
    2/0412.731940.1330.1660.043108120
    3/0414.240270.1050.1310.042124140
    4/0415.250780.0840.1050.041144164
    4/0514.663480.0840.1050.041144164
    250415.260000.070.0870.041164184
    250415.260000.070.0870.041164184
    30041672000.0590.0740.041184208
    350416.884000.0510.0640.04200224
    35041784000.0510.0640.04200224
    400417.596000.0440.0550.04216244
    500418.8120000.0360.0450.039248280
    500419.1120000.0360.0450.039248280
    500418.8120000.0360.0450.039248280
    600421.8144000.030.0380.039272308
    600422.4144000.030.0380.039272308
    750424.3180000.0230.030.038308348
    750424.2180000.0230.030.038308348
    750422.1180000.0230.030.038308348
    900423.8216000.0190.0250.037340384
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.