SPEC 60375
Armorlite® Type MC XHHW-2 Aluminum Conductor Feeder Cable. Rated 600 or 1000 Volts. Silicone Free
Aluminum XHHW-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 or 1000 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801
- Insulation:All phases are insulated with Cross Linked Polyethylene XLPE Type XHHW-2
- Ground:Bare aluminum ground
- Filler:Fillers as needed
- Binder:Mylar tape
- Armor:Aluminum Interlocked Armor
Applications and Features:
Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type XHHW-2 rated 90ºC Wet and Dry
- Per NEC (330.10), unjacketed MC cable can be used in dry location
Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type XHHW-2 rated 90ºC Wet and Dry
- Per NEC (330.10), unjacketed MC cable can be used in dry location
Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Specifications:
Sample Print Legend:
E96627 {UL} TYPE MC AWG XX XHHW-2 CDRS FOR USE IN CABLE TRAYS 600 VOLTS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Conductor Number | Color | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Ground Size | Diameter Over Armor | Overall Weight |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | mils | No. x AWG | inch | lbs/1000ft | ||||
| 890092◊ | 6 | 3 | BK,BK/RD,BK/WE | 0.169 | 7 | 45 | 1x6 | 0.844 | 242 |
| 600742◊ | 4 | 3 | BK,BK/RD,BK/WE | 0.213 | 7 | 45 | 1x6 | 1.01 | 333 |
| 557199◊ | 2 | 3 | BK,BK/RD,BK/WE | 0.268 | 6 | 45 | 1x4 | 1.056 | 430 |
| 558064◊ | 1 | 3 | BK,BK/RD,BK/WE | 0.299 | 8 | 55 | 1x4 | 1.163 | 523 |
| 641793◊ | 1/0 | 3 | BK,BK/RD,BK/WE | 0.336 | 10 | 55 | 1x4 | 1.261 | 610 |
| 641798◊ | 3/0 | 3 | BK,BK/RD,BK/WE | 0.423 | 15 | 55 | 1x4 | 1.449 | 838 |
| 641800◊ | 4/0 | 3 | BK,BK/RD,BK/WE | 0.475 | 19 | 55 | 1x2 | 1.582 | 1077 |
| 641802◊ | 250 | 3 | BK,BK/RD,BK/WE | 0.52 | 22 | 65 | 1x2 | 1.718 | 1248 |
| 641805◊ | 300 | 3 | BK,BK/RD,BK/WE | 0.57 | 21 | 65 | 1x2 | 1.826 | 1428 |
| 641807◊ | 350 | 3 | BK,BK/RD,BK/WE | 0.616 | 35 | 65 | 1x2 | 1.925 | 1603 |
| 643393◊ | 400 | 3 | BK,BK/RD,BK/WE | 0.659 | 35 | 65 | 1x1 | 2.018 | 1794 |
| 643396◊ | 500 | 3 | BK,BK/RD,BK/WE | 0.736 | 34 | 65 | 1x1 | 2.184 | 2136 |
| 643398◊ | 750 | 3 | BK,BK/RD,BK/WE | 0.908 | 58 | 80 | 1x1/0 | 2.625 | 3083 |
| 611203◊ | 6 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.169 | 7 | 45 | 1x6 | 0.928 | 294 |
| 608364◊ | 4 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.213 | 7 | 45 | 1x6 | 1.036 | 382 |
| 557249◊ | 2 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.268 | 6 | 45 | 1x4 | 1.169 | 545 |
| 559963◊ | 1 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.299 | 8 | 55 | 1x4 | 1.296 | 667 |
| 641724◊ | 2/0 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.376 | 12 | 55 | 1x4 | 1.477 | 916 |
| 641730◊ | 3/0 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.423 | 15 | 55 | 1x4 | 1.608 | 1150 |
| 641736◊ | 4/0 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.475 | 19 | 55 | 1x2 | 1.742 | 1391 |
| 641743◊ | 250 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.52 | 22 | 65 | 1x1 | 1.897 | 1631 |
| 641750◊ | 300 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.57 | 21 | 65 | 1x1 | 2.007 | 1871 |
| 641757◊ | 350 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.616 | 35 | 65 | 1x1/0 | 2.127 | 2124 |
| 641764◊ | 400 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.659 | 35 | 65 | 1x1/0 | 2.222 | 2351 |
| 641770◊ | 500 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.736 | 34 | 65 | 1x2/0 | 2.411 | 2828 |
| 641776◊ | 750 | 4 | BK,BK/RD,BK/BE,BK/WE | 0.908 | 58 | 80 | 1x3/0 | 2.899 | 4110 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
GG - Green Ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
GG - Green Ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Conductor Number | Min. Bend Radius | Max Pull Tension | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Inches | Lbs | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| 6 | 3 | 5.9 | 472 | 0.674 | 0.84 | 0.051 | 50 | 55 |
| 4 | 3 | 7.1 | 751 | 0.424 | 0.528 | 0.048 | 65 | 75 |
| 2 | 3 | 7.4 | 1194 | 0.266 | 0.331 | 0.045 | 90 | 100 |
| 1 | 3 | 8.1 | 1506 | 0.211 | 0.263 | 0.046 | 100 | 115 |
| 1/0 | 3 | 8.8 | 1900 | 0.167 | 0.208 | 0.044 | 120 | 135 |
| 3/0 | 3 | 10.1 | 3020 | 0.105 | 0.131 | 0.042 | 155 | 175 |
| 4/0 | 3 | 11.1 | 3808 | 0.084 | 0.105 | 0.041 | 180 | 205 |
| 250 | 3 | 12 | 4500 | 0.07 | 0.087 | 0.041 | 205 | 230 |
| 300 | 3 | 12.8 | 5400 | 0.059 | 0.074 | 0.041 | 230 | 260 |
| 350 | 3 | 13.5 | 6300 | 0.051 | 0.064 | 0.04 | 250 | 280 |
| 400 | 3 | 14.1 | 7200 | 0.044 | 0.055 | 0.04 | 270 | 305 |
| 500 | 3 | 15.3 | 9000 | 0.036 | 0.045 | 0.039 | 310 | 350 |
| 750 | 3 | 18.4 | 13500 | 0.023 | 0.03 | 0.038 | 385 | 435 |
| 6 | 4 | 6.5 | 629 | 0.674 | 0.84 | 0.051 | 40 | 44 |
| 4 | 4 | 7.3 | 1001 | 0.424 | 0.528 | 0.048 | 52 | 60 |
| 2 | 4 | 8.2 | 1592 | 0.266 | 0.331 | 0.045 | 72 | 80 |
| 1 | 4 | 9.1 | 2008 | 0.211 | 0.263 | 0.046 | 80 | 92 |
| 2/0 | 4 | 10.3 | 3194 | 0.133 | 0.166 | 0.043 | 108 | 120 |
| 3/0 | 4 | 11.3 | 4027 | 0.105 | 0.131 | 0.042 | 124 | 140 |
| 4/0 | 4 | 12.2 | 5078 | 0.084 | 0.105 | 0.041 | 144 | 164 |
| 250 | 4 | 13.3 | 6000 | 0.07 | 0.087 | 0.041 | 164 | 184 |
| 300 | 4 | 14 | 7200 | 0.059 | 0.074 | 0.041 | 184 | 208 |
| 350 | 4 | 14.9 | 8400 | 0.051 | 0.064 | 0.04 | 200 | 224 |
| 400 | 4 | 15.6 | 9600 | 0.044 | 0.055 | 0.04 | 216 | 244 |
| 500 | 4 | 16.9 | 12000 | 0.036 | 0.045 | 0.039 | 248 | 280 |
| 750 | 4 | 20.3 | 18000 | 0.023 | 0.03 | 0.038 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.