SPEC 13021

FPLP - Fire Alarm Solid Shielded Plenum Rated LS-PVC

300V, 75°C, Multi-Conductor, Shielded, Solid Copper as FPLP. Minimum Temperature 0ºC , Maximum Temperature 75ºC

...

Construction:

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:Low Smoke Polyvinyl Chloride LS-PVC
  3. Shield:Aluminum foil shielded with 24 AWG drain wire
  4. Rip Cord:Rip cord for ease of jacket removal
  5. Jacket: Low Smoke Polyvinyl Chloride LS-PVC, Color: RED

Applications and Features:

Fire protective signaling circuits. Also for smoke detectors, voice communications, audio control and initiating circuits. Article 760 of the NEC. For use in plenum spaces. Minimum Temperature 0ºC , Maximum Temperature 75ºC

Specifications:

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • UL 1424 Listed FPLP
  • NFPA 70 NFPA 101, NFPA 130, and NFPA 502
  • UL 13 Power-Limited Circuit Cables
  • UL 444 Communications Cables (90ºC, 300V)
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    XX AWG X/C E75610 c{UL}US CMP/CL3P/FPLP 75°C -- CMP FT6 MADE IN USA ROHS-2 COMPLIANT -- {MM/DD/YY} {HH:MM} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    G40006-1182Solid0.04010150.15211186.6698.0350.0360.9-14
    G40504-1184Solid0.04010150.18321306.6698.0350.0361.1-11
    16 AWG
    G50013-1162Solid0.05010150.17617244.1815.0370.0331.1-18
    G50369-1164Solid0.05010150.20632434.1815.0370.0331.2-14
    14 AWG
    G60025-1142Solid0.06410150.19626362.6313.1700.0581.22025
    G60346-1144Solid0.06410150.23451642.6313.1700.0581.41620
    12 AWG
    G70019-1122Solid0.08010150.23141521.6622.0020.0541.42530
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Stock NumberSize AWGConductor NumberBlackRedYellowGreen
    BlackRedYellowGreen
    G40006-1182XX
    G40504-1184XXXX
    G50013-1162XX
    G50369-1164XXXX
    G60025-1142XX
    G60346-1144XXXX
    G70019-1122XX

    Revision: 1.000.004

    Updated On: Nov. 3, 2024, 10:23 p.m. UTC