SPEC 10036
UF-B Copper Cable
Underground Feeder and Branch-Circuit Cable. 600 Volt. Copper Conductors. PVC Insulation/Nylon Sheath. Sunlight, Moisture, and Fungus Resistant Overall PVC Jacket.

Construction:
- Conductor:Solid soft drawn bare copper per ASTM B3 or class B compressed stranded soft drawn bare copper per ASTM B8
- Insulation:All phases and neutral are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
- Ground:Solid soft drawn bare copper
- Jacket:Gray Polyvinyl Chloride (PVC) jacket. Sunlight, moisture and fungus resistant.
Applications and Features:
Southwire® copper UF-B cable is generally used as a feeder to outside post lamps, pumps, and other loads or apparatuses fed from a distribution point in an existing building as specified in the National Electrical Code®. UF-B cable may be used underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.
Specifications:
Sample Print Legend:
SOUTHWIRE E30445 (UL) XX AWG CU X CDR WITH XX AWG GROUND TYPE UF-B 600 VOLTS SUNLIGHT RESISTANT
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Conductor Number | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Ground Size | Jacket Thickness | Approx. OD | Copper Weight | Overall Weight | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | mils | No. x AWG | mil | inch | lbs/1000ft | lbs/1000ft | ||||||||||||
| 14 AWG | SOLID Strands | |||||||||||||||||||
| 130542◊ | 14 | 2 | 0.064 | SOLID | 16 | 1x14 | 30 | 0.168x0.423 | 37 | 71 | |||||||||
| 130575◊ | 14 | 3 | 0.064 | SOLID | 16 | 1x14 | 30 | 0.168x0.581 | 50 | 97 | |||||||||
| 12 AWG | SOLID Strands | |||||||||||||||||||
| 130492◊ | 12 | 2 | 0.081 | SOLID | 16 | 30 | 0.183x0.386 | 40 | 71 | ||||||||||
| 130559◊ | 12 | 2 | 0.081 | SOLID | 16 | 1x12 | 30 | 0.183x0.463 | 59 | 97 | |||||||||
| 130526◊ | 12 | 3 | 0.081 | SOLID | 16 | 30 | 0.183x0.581 | 59 | 110 | ||||||||||
| 130583◊ | 12 | 3 | 0.081 | SOLID | 16 | 1x12 | 30 | 0.183x0.626 | 79 | 131 | |||||||||
| 10 AWG | SOLID Strands | |||||||||||||||||||
| 130567◊ | 10 | 2 | 0.102 | SOLID | 21 | 1x10 | 30 | 0.215x0.518 | 92 | 138 | |||||||||
| 130591◊ | 10 | 3 | 0.102 | SOLID | 21 | 1x10 | 30 | 0.215x0.727 | 123 | 191 | |||||||||
| 208587◊ | 8 | 2 | 0.142 | 7 | 31 | 1x10 | 45 | 0.302x0.678 | 133 | 222 | |||||||||
| 147835◊ | 8 | 3 | 0.142 | 7 | 31 | 1x10 | 45 | 0.319x1.059 | 184 | 344 | |||||||||
| 214692◊ | 6 | 2 | 0.178 | 7 | 31 | 1x10 | 45 | 0.338x0.770 | 193 | 303 | |||||||||
| 147827◊ | 6 | 3 | 0.178 | 7 | 31 | 1x10 | 45 | 0.361x1.223 | 274 | 479 | |||||||||
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Conductor Number | Min. Bend Radius | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Inches | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |||||||||||||
| 14 AWG | SOLID Strands | |||||||||||||||||||
| 14 | 2 | 1.7 | 2.631 | 3.265 | 0.058 | 20 | 25 | ||||||||||||
| 14 | 3 | 2.3 | 2.631 | 3.265 | 0.058 | 20 | 25 | ||||||||||||
| 12 AWG | SOLID Strands | |||||||||||||||||||
| 12 | 2 | 1.5 | 1.662 | 2.063 | 0.054 | 25 | 30 | ||||||||||||
| 12 | 2 | 1.9 | 1.662 | 2.063 | 0.054 | 25 | 30 | ||||||||||||
| 12 | 3 | 2.3 | 1.662 | 2.063 | 0.054 | 25 | 30 | ||||||||||||
| 12 | 3 | 2.5 | 1.662 | 2.063 | 0.054 | 25 | 30 | ||||||||||||
| 10 AWG | SOLID Strands | |||||||||||||||||||
| 10 | 2 | 2.1 | 1.04 | 1.291 | 0.05 | 35 | 40 | ||||||||||||
| 10 | 3 | 2.9 | 1.04 | 1.291 | 0.05 | 35 | 40 | ||||||||||||
| 8 | 2 | 2.7 | 0.653 | 0.81 | 0.052 | 50 | 55 | ||||||||||||
| 8 | 3 | 5.3 | 0.653 | 0.81 | 0.052 | 50 | 55 | ||||||||||||
| 6 | 2 | 3.1 | 0.411 | 0.51 | 0.051 | 65 | 75 | ||||||||||||
| 6 | 3 | 6.1 | 0.411 | 0.51 | 0.051 | 65 | 75 | ||||||||||||
*Ampacities based upon 2023 NEC section 340.80 and Table 310.16. See Also NEC section 310.15 for additional requirements.