SPEC 10036

UF-B Copper Cable

Underground Feeder and Branch-Circuit Cable. 600 Volt. Copper Conductors. PVC Insulation/Nylon Sheath. Sunlight, Moisture, and Fungus Resistant Overall PVC Jacket.

...

Construction:

  1. Conductor:Solid soft drawn bare copper per ASTM B3 or class B compressed stranded soft drawn bare copper per ASTM B8
  2. Insulation:All phases and neutral are insulated with Polyvinyl Chloride (PVC) with Nylon Sheath
  3. Ground:Solid soft drawn bare copper
  4. Jacket:Gray Polyvinyl Chloride (PVC) jacket. Sunlight, moisture and fungus resistant.

Applications and Features:

Southwire® copper UF-B cable is generally used as a feeder to outside post lamps, pumps, and other loads or apparatuses fed from a distribution point in an existing building as specified in the National Electrical Code®. UF-B cable may be used underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 493 Thermoplastic-Insulated Underground Feeder and Branch-Circuit Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC National Electrical Code NFPA 70
  • Sample Print Legend:

    SOUTHWIRE E30445 (UL) XX AWG CU X CDR WITH XX AWG GROUND TYPE UF-B 600 VOLTS SUNLIGHT RESISTANT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeJacket ThicknessApprox. ODCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGmilinchlbs/1000ftlbs/1000ft
    14 AWG | Solid
    130542◊1420.064Solid201x14300.168x0.4233770
    130575◊1430.064Solid201x14300.168x0.5814997
    12 AWG | Solid
    130492◊1220.080Solid20None300.183x0.3863971
    130559◊1220.080Solid201x12300.183x0.4635996
    130526◊1230.080Solid20None300.183x0.58159109
    130583◊1230.080Solid201x12300.183x0.62679131
    10 AWG | Solid
    130567◊1020.101Solid251x10300.215x0.51891138
    130591◊1030.101Solid251x10300.215x0.727122190
    208587◊820.1417351x10450.302x0.678132222
    147835◊830.1417351x10450.319x1.059183344
    214692◊620.1777351x10450.338x0.770192303
    147827◊630.1777351x10450.361x1.223273479
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | Solid
    1421.7652.6313.1700.0582025
    1432.3982.6313.1700.0582025
    12 AWG | Solid
    1221.51041.6622.0020.0542530
    1221.91041.6622.0020.0542530
    1232.31561.6622.0020.0542530
    1232.51561.6622.0020.0542530
    10 AWG | Solid
    1022.11661.0401.2530.0503540
    1032.92491.0401.2530.0503540
    822.72640.6530.7860.0525055
    835.33960.6530.7860.0525055
    623.14190.4110.4950.0516575
    636.16290.4110.4950.0516575
    *Ampacities based upon 2023 NEC section 340.80 and Table 310.16. See Also NEC section 310.15 for additional requirements.

    Revision: 1.000.004

    Updated On: Dec. 31, 2024, 11:06 p.m. UTC

    Award Winning Patent Pending Building Wire Selector
    QR Code