SPEC 10026
SIMpull Barrel™ Cable Drum
The SIMpull Barrel™ Cable Drum Cable Drum is ideal for job sites with longer runs and home-run pulls. Designed to simplify branch circuit installations, the SIMpull BARREL™ Cable Drum contains up to 7 paralleled conductors per BARREL, increasing productivity and reducing the potential for injury while avoiding broken spools, excess material handling, and scrap. Easy payoff directly out of the package, requiring less setup and effort to pull vs conventional wire-pulling methods.
Construction:
- Conductor:Solid soft drawn bare copper per ASTM B3 or combination-unilay stranded soft drawn bare copper per ASTM B787
- Insulation:Heat and moisture resistant PVC insulation in various colors
- Sheath:Nylon jacket utilizing SIMpull® Technology
- For information about our SIMpull Barrel™ Cable Drum please visit us at: SIMpull Barrel™
Applications and Features:
The SIMpull BARREL™ Cable Drum reduces the physical effort associated with material handling, setup, and pulling when compared to conventional wire pulling methods. Designed to simplify branch circuit installations, the SIMpull BARREL™ Cable Drum contains up to 7 paralleled conductors per BARREL (homerun), increasing productivity and reducing the potential for injury while avoiding broken spools, excess material handling and scrap.Easier pulling with SIMpull NoLube® wire jacket. Stationary package design to further reduce pulling tension. Designed to help lower potential for lifting/handling/pulling injuries. Patented parallel construction to reduce material handling and setup. Avoid broken spools and spool over-turn.
Specifications:
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | ||
58028501◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58028601◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58028701◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58028801◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58028901◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58029101◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58029201◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58029301◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58029501◊ | 14 | 1 | Solid | 0.064 | 16 | 5 | 0.106 | 12 | 15 |
58017101◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017201◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017301◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017601◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017701◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017801◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017901◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58018001◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58018101◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58189902◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58193301◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58017001◊ | 14 | 1 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58734901◊ | 14 | 4 | 19 | 0.073 | 20 | 5 | 0.444 | 50 | 64 |
58883501◊ | 14 | 5 | 19 | 0.073 | 20 | 5 | 0.555 | 63 | 80 |
58735001◊ | 14 | 6 | 19 | 0.073 | 20 | 5 | 0.666 | 76 | 96 |
58614402◊ | 12 | 2 | Solid | 0.080 | 15 | 5 | 0.245 | 39 | 47 |
58029702◊ | 10 | 2 | Solid | 0.101 | 20 | 5 | 0.303 | 61 | 72 |
58109902◊ | 10 | 2 | 19 | 0.117 | 20 | 5 | 0.326 | 64 | 76 |
58725102◊ | 10 | 2 | 19 | 0.117 | 20 | 5 | 0.326 | 64 | 76 |
58109402◊ | 10 | 2 | 19 | 0.117 | 20 | 5 | 0.330 | 64 | 77 |
58111002◊ | 12 | 2 | Solid | 0.080 | 15 | 5 | 0.245 | 39 | 47 |
58110502◊ | 12 | 2 | Solid | 0.080 | 15 | 5 | 0.245 | 39 | 47 |
58110302◊ | 12 | 2 | Solid | 0.080 | 20 | 5 | 0.245 | 39 | 47 |
58026401◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58026501◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58026701◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58026801◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58026901◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027101◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027201◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027301◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027501◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027601◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027758◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027858◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58027958◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58028058◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58028158◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58028358◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58193101◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58456659◊ | 12 | 1 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58614502◊ | 12 | 2 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58619402◊ | 12 | 2 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536102◊ | 12 | 3 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536202◊ | 12 | 3 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536502◊ | 12 | 3 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536302◊ | 12 | 3 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536602◊ | 12 | 3 | Solid | 0.080 | 15 | 5 | 0.368 | 59 | 70 |
58536002◊ | 12 | 3 | Solid | 0.080 | 20 | 5 | 0.368 | 59 | 70 |
58150601◊ | 12 | 4 | Solid | 0.080 | 15 | 5 | 0.491 | 79 | 94 |
58031201◊ | 12 | 4 | Solid | 0.080 | 20 | 5 | 0.491 | 79 | 94 |
58103901◊ | 12 | 5 | Solid | 0.080 | 20 | 5 | 0.614 | 98 | 117 |
58120401◊ | 12 | 6 | Solid | 0.080 | 15 | 5 | 0.712 | 115 | 135 |
58120301◊ | 12 | 6 | Solid | 0.080 | 20 | 5 | 0.736 | 118 | 141 |
58118501◊ | 12 | 7 | Solid | 0.080 | 15 | 5 | 0.859 | 138 | 164 |
58104601◊ | 12 | 7 | Solid | 0.080 | 20 | 5 | 0.859 | 138 | 164 |
58111802◊ | 12 | 2 | 19 | 0.090 | 15 | 5 | 0.260 | 40 | 48 |
58260302◊ | 12 | 2 | 19 | 0.090 | 15 | 5 | 0.260 | 40 | 48 |
58111202◊ | 12 | 2 | 19 | 0.090 | 20 | 5 | 0.260 | 40 | 48 |
58018201◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58018401◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58018501◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58018601◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58018701◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58018901◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019001◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019201◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019301◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019401◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019501◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019601◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019701◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019801◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58019901◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58020001◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58193201◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58386359◊ | 12 | 1 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58610002◊ | 12 | 2 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58610102◊ | 12 | 2 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58612002◊ | 12 | 2 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58724302◊ | 12 | 3 | 19 | 0.090 | 15 | 5 | 0.390 | 60 | 72 |
58536702◊ | 12 | 3 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58139401◊ | 12 | 4 | 19 | 0.090 | 20 | 5 | 0.390 | 60 | 72 |
58103401◊ | 12 | 4 | 19 | 0.090 | 20 | 5 | 0.512 | 80 | 96 |
58117401◊ | 12 | 5 | 19 | 0.090 | 15 | 5 | 0.650 | 100 | 121 |
58104001◊ | 12 | 5 | 19 | 0.090 | 20 | 5 | 0.650 | 100 | 121 |
58120801◊ | 12 | 6 | 19 | 0.090 | 15 | 5 | 0.780 | 121 | 145 |
58120601◊ | 12 | 6 | 19 | 0.090 | 20 | 5 | 0.780 | 121 | 145 |
58118701◊ | 12 | 7 | 19 | 0.090 | 15 | 5 | 0.910 | 141 | 170 |
58104701◊ | 12 | 7 | 19 | 0.090 | 20 | 5 | 0.910 | 141 | 170 |
58020101◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020259◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020301◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020401◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020501◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020601◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58020801◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021001◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021101◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021259◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021301◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021401◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021501◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021601◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021801◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58021901◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58022001◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58022601◊ | 10 | 1 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58105002◊ | 10 | 2 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58105502◊ | 10 | 2 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58920501◊ | 10 | 2 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58920601◊ | 10 | 2 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58920701◊ | 10 | 2 | Solid | 0.101 | 25 | 5 | 0.307 | 61 | 73 |
58317001◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.449 | 94 | 110 |
58449801◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.455 | 91 | 108 |
58379601◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.455 | 91 | 108 |
58449901◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.455 | 91 | 108 |
58379801◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.455 | 91 | 108 |
58379701◊ | 10 | 3 | Solid | 0.101 | 20 | 5 | 0.455 | 91 | 108 |
58031001◊ | 10 | 4 | Solid | 0.101 | 25 | 5 | 0.599 | 125 | 147 |
58150701◊ | 10 | 4 | Solid | 0.101 | 20 | 5 | 0.607 | 122 | 145 |
58116701◊ | 10 | 5 | Solid | 0.101 | 20 | 5 | 0.749 | 157 | 183 |
58103701◊ | 10 | 5 | Solid | 0.101 | 25 | 5 | 0.759 | 153 | 181 |
58119701◊ | 10 | 6 | Solid | 0.101 | 20 | 5 | 0.899 | 188 | 220 |
58119601◊ | 10 | 6 | Solid | 0.101 | 25 | 5 | 0.911 | 183 | 218 |
58118001◊ | 10 | 7 | Solid | 0.101 | 20 | 5 | 1.063 | 214 | 253 |
58104401◊ | 10 | 7 | Solid | 0.101 | 25 | 5 | 1.063 | 214 | 254 |
58546401◊ | 10 | 1 | 19 | 0.117 | 21 | 5 | 0.165 | 32 | 38 |
58547001◊ | 10 | 1 | 19 | 0.117 | 21 | 5 | 0.165 | 32 | 38 |
58546501◊ | 10 | 1 | 19 | 0.117 | 21 | 5 | 0.165 | 32 | 38 |
65312201◊ | 10 | 1 | 19 | 0.117 | 20 | 5 | 0.169 | 32 | 39 |
59917901◊ | 10 | 1 | 19 | 0.117 | 20 | 5 | 0.169 | 32 | 39 |
58109403◊ | 10 | 2 | 19 | 0.117 | 20 | 5 | 0.330 | 64 | 77 |
58109903◊ | 10 | 2 | 19 | 0.117 | 20 | 5 | 0.330 | 64 | 77 |
58020701◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58022101◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58022201◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58022301◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58022701◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025001◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025101◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025201◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025301◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025401◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025501◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025601◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025701◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58025901◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58026007◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58026107◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58026207◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58193001◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
59805001◊ | 10 | 1 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58725403◊ | 10 | 2 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58725502◊ | 10 | 2 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58725602◊ | 10 | 2 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58725702◊ | 10 | 2 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
59306202◊ | 10 | 2 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58318301◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.489 | 96 | 115 |
58711001◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.489 | 96 | 115 |
58710901◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.489 | 96 | 115 |
58711101◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.489 | 96 | 115 |
58620401◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.489 | 96 | 115 |
58114301◊ | 10 | 3 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58030401◊ | 10 | 3 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58138501◊ | 10 | 4 | 19 | 0.117 | 25 | 5 | 0.489 | 96 | 115 |
58620501◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.495 | 96 | 116 |
67188501◊ | 10 | 3 | 19 | 0.117 | 20 | 5 | 0.507 | 96 | 117 |
58115501◊ | 10 | 4 | 19 | 0.117 | 20 | 5 | 0.652 | 128 | 154 |
58031101◊ | 10 | 4 | 19 | 0.117 | 25 | 5 | 0.652 | 128 | 153 |
58103801◊ | 10 | 5 | 19 | 0.117 | 25 | 5 | 0.815 | 160 | 192 |
58120101◊ | 10 | 6 | 19 | 0.117 | 20 | 5 | 0.978 | 192 | 230 |
58120001◊ | 10 | 6 | 19 | 0.117 | 25 | 5 | 0.978 | 192 | 230 |
58118301◊ | 10 | 7 | 19 | 0.117 | 20 | 5 | 1.141 | 224 | 269 |
58104501◊ | 10 | 7 | 19 | 0.117 | 25 | 5 | 1.141 | 224 | 269 |
58526001◊ | 8 | 2 | 19 | 0.143 | 35 | 5 | 0.430 | 101 | 126 |
58524803◊ | 8 | 3 | 19 | 0.143 | 35 | 5 | 0.645 | 152 | 189 |
58384801◊ | 8 | 4 | 19 | 0.143 | 35 | 5 | 0.852 | 203 | 250 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
58028501◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58028601◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58028701◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58028801◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58028901◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58029101◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58029201◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58029301◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58029501◊ | 14 | 1 | 0.4 | 32 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017101◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017201◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017301◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017601◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017701◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017801◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017901◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58018001◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58018101◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58189902◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58193301◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58017001◊ | 14 | 1 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 20 | 25 |
58734901◊ | 14 | 4 | 1.8 | 105 | 2.631 | 3.170 | 0.058 | 16 | 20 |
58883501◊ | 14 | 5 | 2.2 | 131 | 2.631 | 3.170 | 0.058 | 16 | 20 |
58735001◊ | 14 | 6 | 2.7 | 157 | 2.631 | 3.170 | 0.058 | 16 | 20 |
58614402◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58029702◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58109902◊ | 10 | 2 | 1.3 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58725102◊ | 10 | 2 | 1.3 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58109402◊ | 10 | 2 | 1.3 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58111002◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58110502◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58110302◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58026401◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58026501◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58026701◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58026801◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58026901◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027101◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027201◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027301◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027501◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027601◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027758◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027858◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58027958◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58028058◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58028158◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58028358◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58193101◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58456659◊ | 12 | 1 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58614502◊ | 12 | 2 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58619402◊ | 12 | 2 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536102◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536202◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536502◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536302◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536602◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536002◊ | 12 | 3 | 1.5 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58150601◊ | 12 | 4 | 2.0 | 167 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58031201◊ | 12 | 4 | 2.0 | 167 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58103901◊ | 12 | 5 | 2.5 | 208 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58120401◊ | 12 | 6 | 2.8 | 250 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58120301◊ | 12 | 6 | 2.9 | 250 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58118501◊ | 12 | 7 | 3.4 | 292 | 1.662 | 2.002 | 0.054 | 17 | 21 |
58104601◊ | 12 | 7 | 3.4 | 292 | 1.662 | 2.002 | 0.054 | 17 | 21 |
58111802◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58260302◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58111202◊ | 12 | 2 | 1.0 | 104 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018201◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018401◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018501◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018601◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018701◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58018901◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019001◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019201◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019301◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019401◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019501◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019601◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019701◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019801◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58019901◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58020001◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58193201◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58386359◊ | 12 | 1 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58610002◊ | 12 | 2 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58610102◊ | 12 | 2 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58612002◊ | 12 | 2 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58724302◊ | 12 | 3 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58536702◊ | 12 | 3 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58139401◊ | 12 | 4 | 1.6 | 156 | 1.662 | 2.002 | 0.054 | 25 | 30 |
58103401◊ | 12 | 4 | 2.0 | 167 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58117401◊ | 12 | 5 | 2.6 | 208 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58104001◊ | 12 | 5 | 2.6 | 208 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58120801◊ | 12 | 6 | 3.1 | 250 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58120601◊ | 12 | 6 | 3.1 | 250 | 1.662 | 2.002 | 0.054 | 20 | 24 |
58118701◊ | 12 | 7 | 3.6 | 292 | 1.662 | 2.002 | 0.054 | 17 | 21 |
58104701◊ | 12 | 7 | 3.6 | 292 | 1.662 | 2.002 | 0.054 | 17 | 21 |
58020101◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020259◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020301◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020401◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020501◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020601◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020801◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021001◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021101◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021259◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021301◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021401◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021501◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021601◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021801◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58021901◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022001◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022601◊ | 10 | 1 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58105002◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58105502◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58920501◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58920601◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58920701◊ | 10 | 2 | 1.2 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58317001◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58449801◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58379601◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58449901◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58379801◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58379701◊ | 10 | 3 | 1.8 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58031001◊ | 10 | 4 | 2.4 | 265 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58150701◊ | 10 | 4 | 2.4 | 265 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58116701◊ | 10 | 5 | 3.0 | 332 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58103701◊ | 10 | 5 | 3.0 | 332 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58119701◊ | 10 | 6 | 3.6 | 398 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58119601◊ | 10 | 6 | 3.6 | 398 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58118001◊ | 10 | 7 | 5.3 | 465 | 1.040 | 1.253 | 0.050 | 24 | 28 |
58104401◊ | 10 | 7 | 5.3 | 465 | 1.040 | 1.253 | 0.050 | 24 | 28 |
58546401◊ | 10 | 1 | 0.7 | 83 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58547001◊ | 10 | 1 | 0.7 | 83 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58546501◊ | 10 | 1 | 0.7 | 83 | 1.040 | 1.253 | 0.050 | 35 | 40 |
65312201◊ | 10 | 1 | 0.7 | 83 | 1.040 | 1.253 | 0.050 | 35 | 40 |
59917901◊ | 10 | 1 | 0.7 | 83 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58109403◊ | 10 | 2 | 1.3 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58109903◊ | 10 | 2 | 1.3 | 166 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58020701◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022101◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022201◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022301◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58022701◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025001◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025101◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025201◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025301◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025401◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025501◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025601◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025701◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58025901◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58026007◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58026107◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58026207◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58193001◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
59805001◊ | 10 | 1 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58725403◊ | 10 | 2 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58725502◊ | 10 | 2 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58725602◊ | 10 | 2 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58725702◊ | 10 | 2 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
59306202◊ | 10 | 2 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58318301◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58711001◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58710901◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58711101◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58620401◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58114301◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58030401◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58138501◊ | 10 | 4 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58620501◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
67188501◊ | 10 | 3 | 2.0 | 249 | 1.040 | 1.253 | 0.050 | 35 | 40 |
58115501◊ | 10 | 4 | 2.6 | 265 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58031101◊ | 10 | 4 | 2.6 | 265 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58103801◊ | 10 | 5 | 3.3 | 332 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58120101◊ | 10 | 6 | 3.9 | 398 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58120001◊ | 10 | 6 | 3.9 | 398 | 1.040 | 1.253 | 0.050 | 28 | 32 |
58118301◊ | 10 | 7 | 5.7 | 465 | 1.040 | 1.253 | 0.050 | 24 | 28 |
58104501◊ | 10 | 7 | 5.7 | 465 | 1.040 | 1.253 | 0.050 | 24 | 28 |
58526001◊ | 8 | 2 | 1.7 | 264 | 0.653 | 0.786 | 0.052 | 50 | 55 |
58524803◊ | 8 | 3 | 2.6 | 396 | 0.653 | 0.786 | 0.052 | 50 | 55 |
58384801◊ | 8 | 4 | 3.4 | 422 | 0.653 | 0.786 | 0.052 | 40 | 44 |
*Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
Table 3 - One Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Blue | Blue/Brown | Black | Brown | Green | Green/Yellow | Gray | Gray/Brown | Gray/Orange | Gray/Purple | Gray/Yellow |
14 (Solid) | 1 | 58028701 | 58028501 | 58028801 | 58029101 | 58028901 | ||||||
14 (19) | 1 | 58017101 | 58017001 | 58017201 | 58017601 | 58017301 | ||||||
12 (Solid) | 1 | 58026701 | 58026501 | 58026801 | 58027101 | 58456659 | 58026901 | 58027758 | 58027858 | 58027958 | ||
12 (19) | 1 | 58018401 | 58018201 | 58018501 | 58019501 | 58386359 | 58018601 | 58018701 | 58018901 | 58019001 | ||
10 (Solid) | 1 | 58020401 | 58020301 | 58020501 | 58021101 | 58021259 | 58020601 | 58022601 | 58020801 | 58020101 | 58021001 | |
10 (19) | 1 | 58022201 | 65312201 | 58022101 | 58022301 | 58546401 | 58025001 | 58020701 | 58025701 | 58022701 | 58025901 |
Table 3 Cont. - One Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Orange | Purple | Pink | Red | Red/Yellow | Tan | White | White/Blue | White/Black | White/Red | Yellow |
14 (Solid) | 1 | 58029201 | 58028601 | 58029301 | 58029405 | 58029501 | ||||||
14 (19) | 1 | 58017701 | 58017801 | 58193301 | 58017901 | 58018001 | 58189902 | 58018101 | ||||
12 (Solid) | 1 | 58027201 | 58026401 | 58193101 | 58027301 | 58027501 | 58028158 | 58028058 | 58028358 | 58027601 | ||
12 (19) | 1 | 58019601 | 58019701 | 58193201 | 58019801 | 58019901 | 58019301 | 58019201 | 58019401 | 58020001 | ||
10 (Solid) | 1 | 58021301 | 58020259 | 58021401 | 58021501 | 58021801 | 58021601 | 58021901 | 58022001 | |||
10 (19) | 1 | 58025201 | 58025301 | 58193001 | 58025401 | 59917901 | 59805001 | 58025501 | 58026107 | 58026007 | 58026207 | 58547001 |
Table 4 - Two Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Black, White | Blue, White/Blue | Black, Red | Black, White/Black | Brown, Gray/Brown | Orange, Gray/Orange | Red, White/Red | Yellow, Gray/Yellow |
12 (Solid) | 2 | 58614502 | 58619402 | 58110302 | 58110502 | 58614402 | 58111002 | ||
12 (19) | 2 | 58111202 | 58260302 | 58612002 | 58610002 | 58111802 | 58610102 | ||
10 (Solid) | 2 | 58105002 | 58029702 | 58920501 | 58920701 | 58105502 | 58920601 | ||
10 (19) | 2 | 58725403 | 59306202 | 58725102 | 58725702 | 58725502 | 58109903 | 58725602 | |
8 (19) | 2 | 58526001 |
Table 5 - Three Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Blue, White/Blue, Green | Black, White/Black, Green | Brown, Gray/Brown, Green | Brown, Orange, Yellow | Orange, Gray/Orange, Green | Purple, Gray/Purple, Green | Red, White/Red, Green |
12 (Solid) | 3 | 58536102 | 58536002 | 58536202 | 58536302 | 58536502 | ||
12 (19) | 3 | 58536702 | 58724302 | |||||
10 (Solid) | 3 | 58449901 | 58317001 | 58379601 | 58379701 | 58449801 | ||
10 (19) | 3 | 58620501 | 58318301 | 58710901 | 58114301 | 58711001 | 67188501 | 58620401 |
8 (19) | 3 | 58524803 |
Table 6 - Four and Five Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Black, Red, Blue, White | Black, White, Red, Blue | Brown, Orange, Yellow, GN | Brown, Orange, Yellow, Gray | Red, Red, Red, Red | Black, Red, Blue, White, Green | Brown, Orange, Yellow, Gray, Green | Red, Red, Red, Red, Red |
14 (19) | 4 | 58734901 | |||||||
12 (Solid) | 4 | 58031201 | 58150601 | ||||||
12 (19) | 4 | 58103401 | 58139401 | ||||||
10 (Solid) | 4 | 58031001 | 58150701 | ||||||
10 (19) | 4 | 58031101 | 58138501 | 58115501 | |||||
8 (19) | 4 | 58384801 | |||||||
14 (19) | 5 | 58883501 | |||||||
12 (Solid) | 5 | 58103901 | |||||||
12 (19) | 5 | 58104001 | 58117401 | ||||||
10 (Solid) | 5 | 58103701 | 58116701 | ||||||
10 (19) | 5 | 58103801 |
Table 7 - Six and Seven Conductor Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)
Size (Strand) | Cond. Number | Black, Red, Blue, White/Black, White/Red, White/Blue | Black, Red, Blue, White/Black, White/Red, White/Blue, Green | Brown, Orange, Yellow, Gray/Brown, Gray/OE, Gray/Yellow | Brown, Orange, Yellow, Gray/Brown, Gray/OE, Gray/Yellow, Green | Red, Red, Red, Red, Red, Red |
14 (19) | 6 | 58735001 | ||||
12 (Solid) | 6 | 58120301 | 58120401 | |||
12 (19) | 6 | 58120801 | 58120601 | |||
10 (Solid) | 6 | 58119601 | 58119701 | |||
10 (19) | 6 | 58120101 | 58120001 | |||
12 (Solid) | 7 | 58104601 | 58118501 | |||
12 (19) | 7 | 58118701 | 58104701 | |||
10 (Solid) | 7 | 58104401 | 58118001 | |||
10 (19) | 7 | 58118301 | 58104501 |