SPEC 45501

CU 2000V EPR Insulation Thermoset CPE-TS Jacket. RHH/RHW-2

Power Cable 2000 Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8, ASTM B33
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2
  4. Overall Jacket:Cross-linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE {UL} XXXX KCMIL CU TYPE RHH OR RHW-2 XX MILS EPR XX MILS THERMOSET CPE FOR CT USE SUN RESISTANT 2000 VOLT CABLE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorMin. Avg. Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    TBA14170.07045150.1901224
    TBA12170.08845150.2082034
    TBA10170.11345150.2333248
    TBA8170.14155300.3115081
    4571786170.17855300.36481126
    TBA11190.32265450.542258335
    TBA1/01190.36165450.581325409
    TBA2/01190.40565450.625410502
    TBA3/01190.45665450.676518619
    138544^4/01190.51265450.748653788
    TBA2501370.55875650.838771930
    TBA3501370.66175650.94110811264
    6792915000370.78975651.08915431799
    TBA6001610.86590651.17518532111
    TBA7501610.96890651.27823162600
    TBA8001611.00090651.31024702763
    64156010001611.11790651.44930873471
    TBA200011271.583115952.00361756791
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Tinned Copper Conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA1410.7332.6313.1700.0582025
    TBA1210.8521.6622.0020.0542530
    TBA1010.9831.0401.2530.0503540
    TBA811.21320.6530.7860.0525055
    457178611.52090.4110.4950.0516575
    TBA112.26690.1280.1540.046130145
    TBA1/012.38440.1020.1220.044150170
    TBA2/012.510640.0810.0970.043175195
    TBA3/012.713420.0640.0780.042200225
    138544^4/012.916920.0510.0620.041230260
    TBA25013.320000.0430.0530.041255290
    TBA35013.728000.0310.0390.040310350
    67929150005.440000.0220.0290.039380430
    TBA60015.848000.0180.0250.039420475
    TBA75016.360000.0140.0220.038475535
    TBA80016.564000.0130.0210.028490555
    641560100017.280000.0110.0180.037545615
    TBA2000112.0100000.0050.0160.027665750
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.005

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC