SPEC 45501

CU 2000V EPR Insulation Thermoset CPE-TS Jacket. RHH/RHW-2

Power Cable 2000 Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 or class B compressed stranded tinned copper per ASTM B33 and B8
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2
  4. Overall Jacket:Cross-linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE {UL} XXXX KCMIL CU TYPE RHH OR RHW-2 XX MILS EPR XX MILS THERMOSET CPE FOR CT USE SUN RESISTANT 2000 VOLT CABLE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    TBA1470.0745150.191224
    TBA1270.08845150.2082034
    TBA1070.11345150.2333248
    TBA870.14155300.3115081
    457178670.17855300.36481126
    TBA1190.32265450.542258335
    TBA1/0190.36165450.581325409
    TBA2/0190.40565450.625410502
    TBA3/0190.45665450.676518619
    138544^4/0190.51265450.748653788
    137828250370.54275650.842771962
    TBA350370.66175650.94110811264
    459400500370.76675651.06615431793
    TBA600610.86590651.17518532111
    TBA750610.96890651.27823162600
    TBA80061190651.3124702763
    6415601000611.11790651.44930873471
    TBA20001271.583115952.00361756791
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ Tinned Copper Conductor
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA140.7332.6313.170.0582025
    TBA120.8521.6622.0020.0542530
    TBA100.9831.041.2530.053540
    TBA81.21320.6530.7860.0525055
    45717861.52090.4110.4950.0516575
    TBA12.26690.1280.1540.046130145
    TBA1/02.38440.1020.1220.044150170
    TBA2/02.510640.0810.0970.043175195
    TBA3/02.713420.0640.0780.042200225
    138544^4/02.916920.0510.0620.041230260
    1378282503.420000.0430.0530.032255290
    TBA3503.728000.0310.0390.04310350
    4594005005.340000.0220.0290.039380430
    TBA6005.848000.0180.0250.039420475
    TBA7506.360000.0140.0220.038475535
    TBA8006.564000.0130.0210.028490555
    64156010007.280000.0110.0180.037545615
    TBA200012100000.0050.0160.027665750
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.006

    Updated On: Oct. 12, 2026, 6:36 p.m. UTC