SPEC 60200

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Multi Circuits

Copper THHN/THWN Insulated Singles. Multiple Circuits Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable - Multi-Circuit is suitable for use as follow:
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire Armorlite® Type MC Cable - Multi-Circuit meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS WITH X X XX AWG NEUTRAL FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | Solid
    555951125BK,RD,BE,WE,WE/BK,GN0.080Solid201x122x120.577119187
    690057126See Table0.080Solid201x122x120.577139211
    563324126See Table0.080Solid201x121x120.577139211
    690065128See Table0.080Solid201x122x120.652179266
    596437128See Table0.080Solid201x120.661179266
    586407129See Table0.080Solid201x124x120.709199294
    6900731212See Table0.080Solid201x123x120.810259401
    10 AWG | Solid
    552970106See Table0.101Solid251x102x100.671216311
    690081106See Table0.101Solid251x102x100.759278417
    587714106BK,RD,BE,OE,PK,PE,GN0.101Solid251x100.680216311
    5529861012See Table0.101Solid251x103x100.947402587
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = Phase conductors plus neutrals. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberNeutral StrandingMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | Solid
    12524.11.6622.0020.0542024
    12624.11.6622.0020.0542024
    12614.11.6622.0020.0542024
    12824.61.6622.0020.0541721
    1284.61.6622.0020.0541721
    12945.01.6622.0020.0541721
    121235.71.6622.0020.0541215
    10 AWG | Solid
    10624.81.0401.2530.0502832
    10625.31.0401.2530.0502428
    1064.81.0401.2530.0502832
    101236.61.0401.2530.0501720
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table conductor number does not include green ground. ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond. NumStock CodeColor
    12 (Solid)5555951BK, RD, BE, WE, WE/BK, GN
    12 (Solid)6690057BK, BK/WE, WE, WE/BK, RD, RD/WE, GN
    12 (Solid)6563324BK, BK/WE, RD, RD/WE, BE, WE, GN
    12 (Solid)8690065BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    12 (Solid)8596437BK, RD, BE, BK/WE, RD/WE, BE/WE, RD/BK, BK/RD, GN
    12 (Solid)9586407OE, GY/OE, BK, WE/BK, RD, WE/RD, BE, BK/WE, GN, WE
    12 (Solid)12690073BK, BK/WE, BK/RD, RD, RD/WE, RD/BK, BE, BE/WE, BE/RD, WE, WE/BK, WE/RD, GN
    10 (Solid)6552970BK, RD, BK/WE, RD/WE, WE, WE/BK, GN
    10 (Solid)6690081BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    10 (Solid)6587714BK, RD, BE, OE, PK, PE, GN
    10 (Solid)12552986BK, BK/WE, BK/RD, WE, WE/BK, WE/RD, RD, RD/WE, RD/BE, BE, BE/WE, BE/RD, GN

    Revision: 1.000.011