SPEC 60200

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Multi Circuits

Copper THHN/THWN Insulated Singles. Multiple Circuits Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strand class C compressed copper and ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Multi-Circuit Cable is suitable for use as follow:
• Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Type THHN/THWN rated 90ºC dry

Southwire Armorlite® Type MC Multi-Circuit Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS WITH X X XX AWG NEUTRAL FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | SOLID Strands
    555951125BK,RD,BE,WE,WE/BK,GN0.081SOLID151x122x120.577120187
    690057126SEE TABLE0.081SOLID151x122x120.578140210
    587820126BN,BN/GY,OE,OE/GY,GY,GY/BN,GN0.081SOLID151x122x120.577140211
    580743126BK,BK/WE,RD,RD/WE,BE,BE/WE,GN0.081SOLID151x120.577140211
    641929126BK,BK,RD,RD,BE,BE,GN0.081SOLID151x120.577140211
    563324126SEE TABLE0.081SOLID151x121x120.577140211
    690065128SEE TABLE0.081SOLID151x122x120.653180265
    596437128SEE TABLE0.081SOLID151x120.661180266
    644479129BK1,RD1,WE1,BK2,RD2,WE2,BK3,RD3,WE30.081SOLID151x123x120.844201338
    586407129SEE TABLE0.081SOLID151x124x120.709200294
    5891221210SEE TABLE0.081SOLID151x124x120.7220317
    6900731212SEE TABLE0.081SOLID151x123x120.81259401
    6793701216SEE TABLE0.081SOLID151x126x120.886339508
    12 AWG | 19 Strands
    591220126BK,RD,BE,WE,PK,PK/WE,GN0.08919151x121x120.607141220
    551354128BK,BK/WE,WE,WE/BK,RD,RD/WE,BE,GN,BE/WE0.08919151x122x120.688181277
    551353126SEE TABLE0.0919151x122x120.607141219
    10 AWG | SOLID Strands
    587714106BK,RD,BE,OE,PK,PE,GN0.102SOLID201x100.68217311
    552970106SEE TABLE0.102SOLID201x102x100.671217311
    587191106BK,RD,BE,OE,GN,GN/YW,WE,WE/RD0.102SOLID202x102x100.777248383
    690081108SEE TABLE0.102SOLID201x102x100.824278426
    5980311010SEE TABLE0.102SOLID201x104x100.884340506
    5529861012SEE TABLE0.102SOLID201x103x100.947402591
    6791551012RD,WT/RD,BE,WT/BE,BK/WT,WT/BK,RD/YW,WT/YW,BE/BK,BK0.102SOLID201x105x100.951402591
    6791611016SEE TABLE0.102SOLID201x106x101.042528754
    10 AWG | 19 Strands
    674430106BK,RD,BK/BE,RD/BE,WE,WE/BE,GN0.11319201x102x100.776226366
    679451109BK,BK,RD,RD,BE,BE,WT/BK,WT/RD,WT/BE,GN0.11319201x103x100.945324505
    5979361012BK,BK,RD,RD,BE,BE,WT,WT,WT,WT,WT,WT,GN0.11319201x106x101.014421633
    6778361012BK,RD,BE,WT,BK,RD,BE,WT,BK,RD,WT,WT,GN0.11319201x104x101.014421633
    674737106SEE TABLE0.11719201x102x100.776226366
    551356108SEE TABLE0.11719201x102x100.879291457
    640523109SEE TABLE0.11719201x104x100.945324504
    58364288SEE TABLE0.14319301x83x81.049463696
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | SOLID Strands
    12541.6622.0630.0542024
    12641.6622.0630.0542024
    12641.6622.0630.0542024
    12641.6622.0630.0542024
    12641.6622.0630.0542024
    12641.6622.0630.0542024
    1284.61.6622.0630.0541821
    1284.61.6622.0630.0541821
    1295.91.6622.0630.0541821
    12951.6622.0630.0541821
    12104.91.6622.0630.0541215
    12125.71.6622.0630.0541215
    12166.21.6622.0630.0541215
    12 AWG | 19 Strands
    1264.21.6622.0630.0542024
    1284.81.6622.0630.0541821
    1264.21.6622.0630.0542024
    10 AWG | SOLID Strands
    1064.81.041.2910.052832
    1064.71.041.2910.052832
    1065.41.041.2910.052832
    1085.81.041.2910.052428
    10106.21.041.2910.051820
    10126.71.041.2910.051820
    10126.71.041.2910.051820
    10167.31.041.2910.051820
    10 AWG | 19 Strands
    1065.41.041.2910.052832
    1096.61.041.2910.052428
    10127.11.041.2910.051820
    10127.11.041.2910.051820
    1065.41.041.2910.052832
    1086.21.041.2910.052428
    1096.61.041.2910.052428
    887.30.6530.810.0523538
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond. NumStock CodeColor
    12 (Solid)5555951BK, RD, BE, WE, WE/BK, GN
    12 (Solid)6690057BK, BK/WE, WE, WE/BK, RD, RD/WE, GN
    12 (Solid)6589122BK, RD, BE, BK/WE, RD/WE, BE/WE, WE, WE/BK, WE/RD, WE/BE, GN
    12 (Solid)6563324BK, BK/WE, RD, RD/WE, BE, WE, GN
    12 (Solid)8690065BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    12 (Solid)8596437BK, RD, BE, BK/WE, RD/WE, BE/WE, RD/BK, BK/RD, GN
    12 (Solid)9586407OE, GY/OE, BK, WE/BK, RD, WE/RD, BE, BK/WE, GN, WE
    12 (Solid)12690073BK, BK/WE, BK/RD, RD, RD/WE, RD/BK, BE, BE/WE, BE/RD, WE, WE/BK, WE/RD, GN
    12 (Solid)16679370BK, RD, BK/RD, RD/BK, BE/RD, BK 1, BK 2, BK/WE, RD/WE, BE/WE, WE/BK, WE/BE, WE/RD, WE, WE 1, WE 2, GN
    12 (19)4551353BK, BK/WE, WE, WE/BK, RD, GN, RD/WE
    10 (Solid)6552970BK, RD, BK/WE, RD/WE, WE, WE/BK, GN
    10 (Solid)6690081BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, BE/WE, GN
    10 (Solid)6587714BK, RD, BE, OE, PK, PE, GN
    10 (Solid)10598031BK, RD, BE, BK/WE, RD/WE, BE/WE, WE, WE/BK, WE/RD, WE/BE, GN
    10 (Solid)12552986BK, BK/WE, BK/RD, WE, WE/BK, WE/RD, RD, RD/WE, RD/BE, BE, BE/WE, BE/RD, GN
    10 (Solid)16679161BK, WE, RD, WE/RD, BE, WE/BE, BK/WE, WE/BK, RD/YW, WE/YW, BE/OE, WE/OE, PE, PE/WE, PK, PK/WE, GN
    10 (19)4674737BK, BK/WE, RD, RD/WE, WE, WE/BK, GN
    10 (19)5640523BK, RD, BE, OE, YW, WE/BK, WE/RD, WE/OE, WE/YW, GN
    10 (19)8551356BK, BK/WE, WE, WE/BK, RD, RD/WE, BE, GN, BE/WE
    8 (19)8583642BK, BK/WE, RD, RD/WE, BE, WE, WE/BK, WE/RD, GN

    Revision: 1.000.023

    Updated On: Oct. 19, 2026, 6:21 p.m. UTC