SPEC 60138

Duraclad® Type MC 120/208V Colors

14 AWG through 10 AWG Copper THHN/THWN Insulated Singles. Green Copper THHN Insulated Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Steel Interlocked Armor. Also available in Blue Steel Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3, class B or C compressed copper and ASTM B3 and B8, or 19-strand combination unilay copper per ASTM B3 and B787
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape with print legend wrapped around assembly
  5. Armor:Light weight galvanized steel interlocked armor

Applications and Features:

Southwire Duraclad® Type MC Cable is suitable for use as follows:
• Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC Article 645
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Type THHN/THWN rated 90ºC dry
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Anti-Short bushing not required

Southwire Duraclad® Type MC Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    14 AWG | SOLID Strands
    551715142BK,WE0.064SOLID151x140.45138124
    551728143BK,RD,WE0.064SOLID151x140.47850145
    551733144BK,RD,BE,WE0.064SOLID151x140.50863219
    12 AWG | SOLID Strands
    551716122BK,WE0.081SOLID151x120.48460154
    552739122RD,WE,GN0.081SOLID151x120.48460154
    556802122BK,WE,GN0.081SOLID151x120.5360164
    582167122BK,RD,GN0.081SOLID151x120.48460154
    571107122BE,WE,GN0.081SOLID151x120.48460154
    552740122BE,WE,GN0.081SOLID151x120.48460154
    551729123BK,RD,WE0.081SOLID151x120.51580184
    571115123BK,BE,WE,GN0.081SOLID151x120.51580184
    555051123BK,BE,WE,GN0.081SOLID151x120.51580184
    571114123BE,RD,WE,GN0.081SOLID151x120.51580184
    555053123BE,RD,WE,GN0.081SOLID151x120.51580184
    551734124BK,RD,BE,WE0.081SOLID151x120.55100278
    555199124BK,WE,RD,WE/RD,GN0.081SOLID151x120.55100278
    12 AWG | 7 Strands
    641926122BK,WE,GN0.0897301x120.5361176
    12 AWG | 19 Strands
    562229122BE,WE,GN0.08919151x120.50560160
    556436122BK,WE,GN0.08919151x120.50560160
    562227122RD,WE,GN0.08919151x120.50560160
    568060122BK,RD,GN0.08919151x120.51561163
    571029122BK,WE,GN0.08919151x120.51561163
    12 AWG | 7 Strands
    649636123BK,RD,WE,GN0.0897301x120.58581211
    12 AWG | 19 Strands
    568067123BK,RD,BE,GN0.08919151x120.5382193
    553632123BK,WE,RD,GN0.08919151x120.53980194
    568065124BK,RD,BE,YW,GN0.08919151x120.585102297
    568061124BK,RD,BE,WE,GN0.08919151x120.585102297
    10 AWG | SOLID Strands
    588904102RD,BE,GN0.102SOLID201x100.5593205
    579357102BK,RD,GN0.102SOLID201x100.5593205
    579360102BK,BE,GN0.102SOLID201x100.5593205
    553269102BE,WE,GN0.102SOLID201x100.5593205
    553268102RD,WE,GN0.102SOLID201x100.5593205
    551717102BK,WE0.102SOLID201x100.55193270
    551730103BK,RD,WE0.102SOLID201x100.59124323
    551735104BK,WE,RD,BE,GN0.102SOLID201x100.634155374
    10 AWG | 19 Strands
    677596102BK,RD,GN0.11319201x100.5897220
    553967102BK,WE,GN0.11319201x100.58497222
    677598102BK,WE,GN0.11319201x100.5897220
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | SOLID Strands
    1423.22.6313.2650.0582025
    1433.32.6313.2650.0582025
    1443.52.6313.2650.0581620
    12 AWG | SOLID Strands
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.71.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1233.61.6622.0630.0542530
    1243.91.6622.0630.0542024
    1243.91.6622.0630.0542024
    12 AWG | 7 Strands
    1223.71.6622.0630.0542530
    12 AWG | 19 Strands
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    1223.61.6622.0630.0542530
    1223.61.6622.0630.0542530
    12 AWG | 7 Strands
    1234.11.6622.0630.0542530
    12 AWG | 19 Strands
    1233.71.6622.0630.0542530
    1233.81.6622.0630.0542530
    1244.11.6622.0630.0542024
    1244.11.6622.0630.0542024
    10 AWG | SOLID Strands
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1034.11.041.2910.053540
    1044.41.041.2910.052832
    10 AWG | 19 Strands
    1024.11.041.2910.053540
    1024.11.041.2910.053540
    1024.11.041.2910.053540
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.008

    Updated On: Jan. 13, 2026, 3:32 p.m. UTC