SPEC 44080

Southwire® RenewaFLEX™ Power Cables for Battery Energy Storage Systems

Single Conductor, Copper, 2000V, XLPE insulation Type RHH/RHW-2, Flexible Power Cable.

...

Construction:

  1. Conductor:Sizes 6 - 4/0 AWG: Class K, flexible stranded, bare copper per ASTM B3 and B172.
                        Sizes 250 - 1000 kcmil: Class I, flexible stranded, bare copper per ASTM B3 and B172.
  2. Insulation: Cross Linked Polyethylene (XLPE) Type RHH/RHW-2

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in the internal wiring of Battery Energy Storage Systems (BESS), in wet and dry locations, conduits, ducts, troughs, covered trays, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Gasoline and Oil Resistant. For CT USE sizes 1/0 AWG and larger. Rated 1000 lb/ft maximum sidewall pressure.

Also available in different colors like: black, red, green, brown, yellow, etc.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • RoHS-3 Complies with European Directive 2015/863
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    For 8 - 2 AWG:
    {SQFTG} SOUTHWIRE E30117 {UL} XX AWG CU TYPE RHH OR RHW-2 XX MILS XLP PRI/II GRI/II 2000 VOLTS

    For 1/0 - 4/0 AWG:
    {SQFTG} SOUTHWIRE E30117 {UL} XX AWG CU TYPE RHH OR RHW-2 XX MILS XLP FOR CT USE PRI/II GRI/II 2000 VOLTS

    For 250 -1000 kcmil:
    {SQFTG} SOUTHWIRE E30117 {UL} XX kcmil CU TYPE RHH OR RHW-2 XX MILS XLP FOR CT USE PRI/II GRI/II 2000 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchlb/1000ft
    TBA81680.153700.29377
    66577762730.190700.338119
    66577644130.235700.383164
    66577526650.302700.448252
    6654221/010640.385900.570426
    1389232/013300.410900.620510
    1389244/021090.550900.740788
    1389252506270.5801050.825908
    1389263508930.6701050.8901242
    13892750012210.8581051.0781709
    13895060014800.9631201.2152112
    13895175018501.0941201.3462650
    TBA777.719241.0301201.2822733
    TBA100025161.1901201.4303302
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity In Raceway 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    81.21320.7150.9030.0528055
    61.42090.4190.5240.05110575
    41.53330.2630.3290.04814095
    21.85310.1650.2070.045190130
    1/02.38450.1050.1320.044260170
    2/02.510650.0840.1050.043300195
    4/03.016930.0530.0670.041405260
    2503.320000.0450.0560.041455290
    3503.628000.0320.0400.040570350
    5005.440000.0220.0290.039700430
    6006.148000.0190.0240.039780475
    7506.760000.0150.0250.038885535
    777.76.062210.0150.0250.038903¹543
    10007.180000.0110.0210.0371055615
    • Ampacities based upon 2023 NEC Table 310.16 for Raceway, Cable, or Earth and NEC Table 310.17 for single conductors in Air. • Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    1 linearly interpolated value
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmkg/km
    TBA81683.891.787.44115
    66577762734.831.788.59177
    66577644135.971.789.73244
    66577526657.671.7811.38375
    6654221/010649.782.2914.48634
    1389232/0133010.412.2915.75759
    1389244/0210913.972.2918.801173
    13892525062714.732.6720.961351
    13892635089317.022.6722.611848
    138927500122121.792.6727.382543
    138950600148024.463.0530.863143
    138951750185027.793.0534.193944
    TBA777.7192426.163.0532.564067
    TBA1000251630.233.0536.324914
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity In Raceway 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmΩ/kmAmpAmp
    830.485872.34582.960.17068055
    635.569301.37471.720.167310575
    438.1014820.86291.080.157514095
    245.7223630.54130.680.1476190130
    1/058.4237600.34450.430.1444260170
    2/063.5047390.27560.340.1411300195
    4/076.2075340.17390.220.1345405260
    25083.8289000.14760.180.1345455290
    35091.44124600.10500.130.1312570350
    500137.16178000.07220.100.1280700430
    600154.94213600.06230.080.1280780475
    750170.18267000.04920.080.1247885535
    777.7152.40276830.04920.080.1247903¹543
    1000180.34356000.03610.070.12141055615
    • Ampacities based upon 2023 NEC Table 310.16 for Raceway, Cable, or Earth and NEC Table 310.17 for single conductors in Air. • Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    1 linearly interpolated value

    Revision: 1.000.070