SPEC 80214
MV-105 35kV AL 100% TRXLPE One-Sixth Neutral (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Sixth Copper Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture blocked 1350 H16/H26 aluminum, class B compressed or compressed unilay stranded
- Strand Shield:Semi-conducting crosslinked polyethylene
- Insulation:35kV 100% insulation level 345 mil Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable semi-conducting crosslinked polyethylene
- Concentric Neutral:Annealed copper wires helically applied one-sixth concentric neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® water swellable powder under black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® HI-DRI-PLUS® (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
| 662806 | 350 (37) | 0.661 | 1.391 | 345 | 1.501 | 7x14 | 0.463 | 75 | 1.783 | 1327 | 8.9 | 2100 |
| 663279 | 500 (37) | 0.766 | 1.519 | 345 | 1.629 | 10x14 | 0.324 | 75 | 1.911 | 1613 | 9.6 | 3000 |
| 626324 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 15x16 | 0.343 | 75 | 1.885 | 1571 | 9.4 | 3000 |
| 621584 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 10x14 | 0.324 | 75 | 1.911 | 1608 | 9.6 | 3000 |
| 623075 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 22x16 | 0.234 | 75 | 2.104 | 2069 | 12.6 | 4500 |
| 626336 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 14x14 | 0.231 | 75 | 2.13 | 2105 | 12.8 | 4500 |
| 622377^ | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 14x14 | 0.231 | 75 | 2.13 | 2104 | 12.8 | 4500 |
| 662104 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 29x16 | 0.178 | 75 | 2.253 | 2486 | 13.5 | 6000 |
| 623076 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 18x14 | 0.18 | 75 | 2.279 | 2519 | 13.7 | 6000 |
| 459249 | 1000 (61) | 1.117 | 1.863 | 345 | 2.013 | 19x14 | 0.171 | 75 | 2.291 | 2732 | 13.7 | 6000 |
| 626346 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 12x12 | 0.171 | 75 | 2.313 | 2586 | 13.9 | 6000 |
| 662112 | 1250 (61) | 1.25 | 2 | 345 | 2.14 | 23x14 | 0.141 | 75 | 2.422 | 2957 | 14.5 | 7500 |
| 626351 | 1250 (61) | 1.25 | 2 | 345 | 2.14 | 15x12 | 0.136 | 75 | 2.456 | 3012 | 14.7 | 7500 |
| 622362^ | 1250 (61) | 1.25 | 2 | 345 | 2.14 | 15x12 | 0.136 | 75 | 2.456 | 3011 | 14.7 | 7500 |
| 457742! | 1500 (61) | 1.37 | 2.119 | 345 | 2.259 | 18x12 | 0.114 | 75 | 2.575 | 3416 | 15.4 | 9000 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ HI-DRI only (no HI-DRI-PLUS® water swellable powder under the jacket)
! SuperSmooth conductor shield
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
! SuperSmooth conductor shield
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 350 (37) | 0.051 | 0.07 | 0.046 | 0.045 | 0.381+j0.226 | 0.071+j0.050 | 3625 | 315 | 375 |
| 500 (37) | 0.036 | 0.05 | 0.043 | 0.043 | 0.307+j0.143 | 0.052+j0.047 | 5178 | 380 | 435 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.318+j0.153 | 0.052+j0.047 | 4871 | 385 | 450 |
| 500 (37) | 0.036 | 0.05 | 0.041 | 0.042 | 0.307+j0.143 | 0.052+j0.047 | 5178 | 385 | 450 |
| 750 (61) | 0.023 | 0.033 | 0.035 | 0.04 | 0.238+j0.090 | 0.035+j0.045 | 7144 | 480 | 550 |
| 750 (61) | 0.023 | 0.033 | 0.035 | 0.04 | 0.235+j0.090 | 0.035+j0.045 | 7249 | 480 | 550 |
| 750 (61) | 0.023 | 0.033 | 0.035 | 0.04 | 0.235+j0.090 | 0.035+j0.045 | 7249 | 480 | 550 |
| 1000 (61) | 0.017 | 0.025 | 0.031 | 0.038 | 0.188+j0.062 | 0.028+j0.043 | 9417 | 550 | 615 |
| 1000 (61) | 0.017 | 0.025 | 0.031 | 0.038 | 0.190+j0.064 | 0.028+j0.043 | 9321 | 550 | 615 |
| 1000 (61) | 0.017 | 0.025 | 0.031 | 0.038 | 0.182+j0.060 | 0.028+j0.043 | 9838 | 550 | 615 |
| 1000 (61) | 0.017 | 0.025 | 0.031 | 0.038 | 0.182+j0.061 | 0.028+j0.043 | 9863 | 550 | 615 |
| 1250 (61) | 0.014 | 0.022 | 0.029 | 0.037 | 0.155+j0.047 | 0.026+j0.042 | 11910 | ||
| 1250 (61) | 0.014 | 0.022 | 0.029 | 0.037 | 0.151+j0.046 | 0.026+j0.042 | 12328 | ||
| 1250 (61) | 0.014 | 0.022 | 0.029 | 0.037 | 0.151+j0.046 | 0.026+j0.042 | 12328 | ||
| 1500 (61) | 0.012 | 0.02 | 0.027 | 0.036 | 0.129+j0.037 | 0.025+j0.041 | 14794 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
| 662806 | 350 (37) | 16.79 | 35.33 | 8.76 | 38.13 | 7x14 | 1.52 | 1.91 | 45.29 | 1975 | 226.06 | 9345 |
| 663279 | 500 (37) | 19.46 | 38.58 | 8.76 | 41.38 | 10x14 | 1.06 | 1.91 | 48.54 | 2400 | 243.84 | 13350 |
| 626324 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 15x16 | 1.13 | 1.91 | 47.88 | 2338 | 238.76 | 13350 |
| 621584 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 10x14 | 1.06 | 1.91 | 48.54 | 2393 | 243.84 | 13350 |
| 623075 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 22x16 | 0.77 | 1.91 | 53.44 | 3079 | 320.04 | 20025 |
| 626336 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 14x14 | 0.76 | 1.91 | 54.10 | 3133 | 325.12 | 20025 |
| 622377^ | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 14x14 | 0.76 | 1.91 | 54.10 | 3131 | 325.12 | 20025 |
| 662104 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 29x16 | 0.58 | 1.91 | 57.23 | 3700 | 342.90 | 26700 |
| 623076 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 18x14 | 0.59 | 1.91 | 57.89 | 3749 | 347.98 | 26700 |
| 459249 | 1000 (61) | 28.37 | 47.32 | 8.76 | 51.13 | 19x14 | 0.56 | 1.91 | 58.19 | 4066 | 347.98 | 26700 |
| 626346 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 12x12 | 0.56 | 1.91 | 58.75 | 3848 | 353.06 | 26700 |
| 662112 | 1250 (61) | 31.75 | 50.80 | 8.76 | 54.36 | 23x14 | 0.46 | 1.91 | 61.52 | 4401 | 368.30 | 33375 |
| 626351 | 1250 (61) | 31.75 | 50.80 | 8.76 | 54.36 | 15x12 | 0.45 | 1.91 | 62.38 | 4482 | 373.38 | 33375 |
| 622362^ | 1250 (61) | 31.75 | 50.80 | 8.76 | 54.36 | 15x12 | 0.45 | 1.91 | 62.38 | 4481 | 373.38 | 33375 |
| 457742! | 1500 (61) | 34.80 | 53.82 | 8.76 | 57.38 | 18x12 | 0.37 | 1.91 | 65.41 | 5084 | 391.16 | 40050 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ HI-DRI only (no HI-DRI-PLUS® water swellable powder under the jacket)
! SuperSmooth conductor shield
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
! SuperSmooth conductor shield
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 350 (37) | 0.1673 | 0.23 | 0.0140 | 0.1476 | 0.381+j0.226 | 0.071+j0.050 | 3625 | 315 | 375 |
| 500 (37) | 0.1181 | 0.16 | 0.0131 | 0.1411 | 0.307+j0.143 | 0.052+j0.047 | 5178 | 380 | 435 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.318+j0.153 | 0.052+j0.047 | 4871 | 385 | 450 |
| 500 (37) | 0.1181 | 0.16 | 0.0125 | 0.1378 | 0.307+j0.143 | 0.052+j0.047 | 5178 | 385 | 450 |
| 750 (61) | 0.0755 | 0.11 | 0.0107 | 0.1312 | 0.238+j0.090 | 0.035+j0.045 | 7144 | 480 | 550 |
| 750 (61) | 0.0755 | 0.11 | 0.0107 | 0.1312 | 0.235+j0.090 | 0.035+j0.045 | 7249 | 480 | 550 |
| 750 (61) | 0.0755 | 0.11 | 0.0107 | 0.1312 | 0.235+j0.090 | 0.035+j0.045 | 7249 | 480 | 550 |
| 1000 (61) | 0.0558 | 0.08 | 0.0094 | 0.1247 | 0.188+j0.062 | 0.028+j0.043 | 9417 | 550 | 615 |
| 1000 (61) | 0.0558 | 0.08 | 0.0094 | 0.1247 | 0.190+j0.064 | 0.028+j0.043 | 9321 | 550 | 615 |
| 1000 (61) | 0.0558 | 0.08 | 0.0094 | 0.1247 | 0.182+j0.060 | 0.028+j0.043 | 9838 | 550 | 615 |
| 1000 (61) | 0.0558 | 0.08 | 0.0094 | 0.1247 | 0.182+j0.061 | 0.028+j0.043 | 9863 | 550 | 615 |
| 1250 (61) | 0.0459 | 0.07 | 0.0088 | 0.1214 | 0.155+j0.047 | 0.026+j0.042 | 11910 | ||
| 1250 (61) | 0.0459 | 0.07 | 0.0088 | 0.1214 | 0.151+j0.046 | 0.026+j0.042 | 12328 | ||
| 1250 (61) | 0.0459 | 0.07 | 0.0088 | 0.1214 | 0.151+j0.046 | 0.026+j0.042 | 12328 | ||
| 1500 (61) | 0.0394 | 0.07 | 0.0082 | 0.1181 | 0.129+j0.037 | 0.025+j0.041 | 14794 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.023
Updated On: Oct. 15, 2026, 2:57 p.m. UTC
Concentric Neutral Calculator


