SPEC 80214
35kV AL 100% TRXLPE One-Sixth Neutral (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Sixth Copper Concentric Neutrals. XLPE Jacket

Construction:
- Conductor:Moisture blocked 1350 H16/H26 aluminum, class B compressed or compressed unilay stranded
- Strand Shield:Semi-conducting crosslinked polyethylene
- Insulation:35kV 100% insulation level 345 mil Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable semi-conducting crosslinked polyethylene
- Concentric Neutral:Annealed copper wires helically applied one-sixth concentric neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® water swellable powder under black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® HI-DRI-PLUS® (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
662806 | 350 (37) | 0.661 | 1.391 | 345 | 1.501 | 7x14 | 0.375 | 75 | 1.783 | 1328 | 14.3 | 2100 |
663279 | 500 (37) | 0.766 | 1.519 | 345 | 1.629 | 10x14 | 0.263 | 75 | 1.911 | 1614 | 15.3 | 3000 |
626324 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 15x16 | 0.278 | 75 | 1.884 | 1571 | 15.1 | 3000 |
621584 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 10x14 | 0.263 | 75 | 1.911 | 1609 | 15.3 | 3000 |
623075 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 22x16 | 0.190 | 75 | 2.103 | 2068 | 17.0 | 4500 |
622377^ | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 14x14 | 0.187 | 75 | 2.130 | 2105 | 17.0 | 4500 |
626336 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 14x14 | 0.187 | 75 | 2.130 | 2106 | 17.0 | 4500 |
662104 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 29x16 | 0.144 | 75 | 2.252 | 2485 | 18.0 | 6000 |
620742 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 19x14 | 0.138 | 75 | 2.279 | 2533 | 18.2 | 6000 |
623076 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 18x14 | 0.146 | 75 | 2.279 | 2521 | 18.2 | 6000 |
626346 | 1000 (61) | 1.117 | 1.857 | 345 | 1.997 | 12x12 | 0.138 | 75 | 2.312 | 2588 | 18.5 | 6000 |
662112 | 1250 (91) | 1.250 | 2.000 | 345 | 2.140 | 23x14 | 0.114 | 75 | 2.422 | 2942 | 19.4 | 7500 |
622362^ | 1250 (91) | 1.250 | 2.000 | 345 | 2.140 | 15x12 | 0.110 | 75 | 2.455 | 2996 | 19.6 | 7500 |
626351 | 1250 (91) | 1.250 | 2.000 | 345 | 2.140 | 15x12 | 0.110 | 75 | 2.455 | 2997 | 19.6 | 7500 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ HI-DRI only (no HI-DRI-PLUS® water swellable powder under the jacket)
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | A/1000ft | W/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
350 (37) | 0.050 | 0.065 | 0.048 | 0.045 | 0.420 | 2.5 | 0.119 + j0.719 | 0.065 + j0.046 | 3621 | 315 | 375 |
500 (37) | 0.035 | 0.046 | 0.042 | 0.043 | 0.474 | 2.9 | 0.100 + j0.714 | 0.046 + j0.043 | 5173 | 380 | 435 |
500 (37) | 0.035 | 0.046 | 0.045 | 0.042 | 0.474 | 2.9 | 0.100 + j0.714 | 0.046 + j0.042 | 4918 | 385 | 450 |
500 (37) | 0.035 | 0.046 | 0.042 | 0.043 | 0.474 | 2.9 | 0.100 + j0.714 | 0.046 + j0.043 | 5173 | 385 | 450 |
750 (61) | 0.024 | 0.033 | 0.036 | 0.041 | 0.549 | 3.3 | 0.088 + j0.776 | 0.033 + j0.129 | 6903 | 480 | 550 |
750 (61) | 0.024 | 0.033 | 0.034 | 0.040 | 0.580 | 3.5 | 0.087 + j0.705 | 0.033 + j0.040 | 7242 | 480 | 550 |
750 (61) | 0.024 | 0.033 | 0.036 | 0.041 | 0.549 | 3.3 | 0.087 + j0.706 | 0.033 + j0.041 | 7242 | 480 | 550 |
1000 (61) | 0.018 | 0.026 | 0.031 | 0.038 | 0.646 | 3.9 | 0.081 + j0.761 | 0.027 + j0.103 | 9099 | 550 | 615 |
1000 (61) | 0.018 | 0.026 | 0.031 | 0.038 | 0.646 | 3.9 | 0.080 + j0.699 | 0.026 + j0.039 | 9828 | 550 | 615 |
1000 (61) | 0.018 | 0.026 | 0.031 | 0.038 | 0.646 | 3.9 | 0.080 + j0.699 | 0.026 + j0.039 | 9311 | 550 | 615 |
1000 (61) | 0.018 | 0.026 | 0.033 | 0.039 | 0.608 | 3.7 | 0.080 + j0.699 | 0.026 + j0.039 | 9862 | 550 | 615 |
1250 (91) | 0.014 | 0.023 | 0.030 | 0.038 | 0.656 | 4.0 | 0.077 + j0.695 | 0.023 + j0.038 | 11898 | ||
1250 (91) | 0.014 | 0.023 | 0.028 | 0.037 | 0.701 | 4.2 | 0.077 + j0.692 | 0.023 + j0.038 | 12328 | ||
1250 (91) | 0.014 | 0.023 | 0.030 | 0.038 | 0.656 | 4.0 | 0.077 + j0.694 | 0.023 + j0.038 | 12328 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
662806 | 350 (37) | 16.79 | 35.33 | 8.76 | 38.13 | 7x14 | 1.23 | 1.91 | 45.29 | 1976 | 363.22 | 9345 |
663279 | 500 (37) | 19.46 | 38.58 | 8.76 | 41.38 | 10x14 | 0.86 | 1.91 | 48.54 | 2402 | 388.62 | 13350 |
626324 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 15x16 | 0.91 | 1.91 | 47.85 | 2338 | 383.54 | 13350 |
621584 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 10x14 | 0.86 | 1.91 | 48.54 | 2394 | 388.62 | 13350 |
623075 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 22x16 | 0.62 | 1.91 | 53.42 | 3078 | 431.80 | 20025 |
622377^ | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 14x14 | 0.61 | 1.91 | 54.10 | 3133 | 431.80 | 20025 |
626336 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 14x14 | 0.61 | 1.91 | 54.10 | 3134 | 431.80 | 20025 |
662104 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 29x16 | 0.47 | 1.91 | 57.20 | 3698 | 457.20 | 26700 |
620742 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 19x14 | 0.45 | 1.91 | 57.89 | 3770 | 462.28 | 26700 |
623076 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 18x14 | 0.48 | 1.91 | 57.89 | 3752 | 462.28 | 26700 |
626346 | 1000 (61) | 28.37 | 47.17 | 8.76 | 50.72 | 12x12 | 0.45 | 1.91 | 58.72 | 3851 | 469.90 | 26700 |
662112 | 1250 (91) | 31.75 | 50.80 | 8.76 | 54.36 | 23x14 | 0.37 | 1.91 | 61.52 | 4378 | 492.76 | 33375 |
622362^ | 1250 (91) | 31.75 | 50.80 | 8.76 | 54.36 | 15x12 | 0.36 | 1.91 | 62.36 | 4459 | 497.84 | 33375 |
626351 | 1250 (91) | 31.75 | 50.80 | 8.76 | 54.36 | 15x12 | 0.36 | 1.91 | 62.36 | 4460 | 497.84 | 33375 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ HI-DRI only (no HI-DRI-PLUS® water swellable powder under the jacket)
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | A/km | W/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
350 (37) | 0.1640 | 0.21 | 0.0146 | 0.1476 | 1.378 | 8.2021 | 0.119 + j0.719 | 0.065 + j0.046 | 3621 | 315 | 375 |
500 (37) | 0.1148 | 0.15 | 0.0128 | 0.1411 | 1.555 | 9.5144 | 0.100 + j0.714 | 0.046 + j0.043 | 5173 | 380 | 435 |
500 (37) | 0.1148 | 0.15 | 0.0137 | 0.1378 | 1.555 | 9.5144 | 0.100 + j0.714 | 0.046 + j0.042 | 4918 | 385 | 450 |
500 (37) | 0.1148 | 0.15 | 0.0128 | 0.1411 | 1.555 | 9.5144 | 0.100 + j0.714 | 0.046 + j0.043 | 5173 | 385 | 450 |
750 (61) | 0.0787 | 0.11 | 0.0110 | 0.1345 | 1.801 | 10.8268 | 0.088 + j0.776 | 0.033 + j0.129 | 6903 | 480 | 550 |
750 (61) | 0.0787 | 0.11 | 0.0104 | 0.1312 | 1.903 | 11.4829 | 0.087 + j0.705 | 0.033 + j0.040 | 7242 | 480 | 550 |
750 (61) | 0.0787 | 0.11 | 0.0110 | 0.1345 | 1.801 | 10.8268 | 0.087 + j0.706 | 0.033 + j0.041 | 7242 | 480 | 550 |
1000 (61) | 0.0591 | 0.09 | 0.0094 | 0.1247 | 2.119 | 12.7953 | 0.081 + j0.761 | 0.027 + j0.103 | 9099 | 550 | 615 |
1000 (61) | 0.0591 | 0.09 | 0.0094 | 0.1247 | 2.119 | 12.7953 | 0.080 + j0.699 | 0.026 + j0.039 | 9828 | 550 | 615 |
1000 (61) | 0.0591 | 0.09 | 0.0094 | 0.1247 | 2.119 | 12.7953 | 0.080 + j0.699 | 0.026 + j0.039 | 9311 | 550 | 615 |
1000 (61) | 0.0591 | 0.09 | 0.0101 | 0.1280 | 1.995 | 12.1391 | 0.080 + j0.699 | 0.026 + j0.039 | 9862 | 550 | 615 |
1250 (91) | 0.0459 | 0.08 | 0.0091 | 0.1247 | 2.152 | 13.1234 | 0.077 + j0.695 | 0.023 + j0.038 | 11898 | ||
1250 (91) | 0.0459 | 0.08 | 0.0085 | 0.1214 | 2.300 | 13.7795 | 0.077 + j0.692 | 0.023 + j0.038 | 12328 | ||
1250 (91) | 0.0459 | 0.08 | 0.0091 | 0.1247 | 2.152 | 13.1234 | 0.077 + j0.694 | 0.023 + j0.038 | 12328 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.020
Updated On: Jan. 29, 2025, 9:58 p.m. UTC
Concentric Neutral Calculator