SPEC 80113

ACSS/AW

Aluminum Conductor, Aluminum-Clad Steel Supported

...

Construction:

  1. Core: Stranded aluminum-clad steel core, available in AW2 normal-strength and AW3 high-strength classes
  2. Stranding: Annealed aluminum (1350-O) round wires with 63% conductivity

Applications and Features:

ACSS/AW (Aluminum Conductor, Aluminum-Clad Steel Supported) is a concentrically stranded, high-temperature overhead conductor consisting of fully annealed aluminum wires surrounding an aluminum-clad steel core. The annealed aluminum provides electrical conductivity, while the aluminum-clad steel core carries the conductor’s mechanical load.

Southwire batch anneals the completed conductor after stranding, allowing the aluminum to be fully annealed while supporting tighter stranding and verification of finished conductor properties after heat exposure.

The aluminum cladding provides additional core conductivity and corrosion protection. ACSS/AW is suitable for overhead transmission and distribution applications requiring increased ampacity, controlled thermal sag, and enhanced corrosion performance. It can be used for new construction, reconductoring, coastal environments, and other applications where an aluminum-clad steel core is preferred.

Continuous operating temperature - 250°C

Specifications:

  • ASTM B500 Standard Specification for Metallic Coated or Aluminum-Clad Stranded Steel Core for Use in Overhead Electrical Conductors
  • ASTM B502 Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B856 Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS)
  • Weights, Measurements, Electrical and Engineering Data

    Stock NumberCode WordConductor SizeStrandingCross-Sectional AreaLayers of AlDiameterWeightRated Breaking StrengthDC Resistance @ 20°C
    Individual StrandsAW CoreComplete Conductor
    AlTotalAlAWAlTotalAW2AW3
    kcmilAl/AWin²in²ininininlb/1000ftlb/1000ftlblbΩ/mile
    TBAPARTRIDGE/ACSS/AW266.826/70.20950.243620.10130.07880.23640.642251.2349.08,3708,8800.3170
    TBAJUNCO/ACSS/AW266.830/70.20950.258420.09430.09430.28290.660251.9392.211,20011,7000.3109
    TBAOSTRICH/ACSS/AW300.026/70.23550.273820.10740.08350.25050.680282.4392.39,4009,9700.2820
    TBAWIDGEON/ACSS/AW336.424/70.26420.298420.11840.07890.23670.710316.8414.98,8309,3400.2540
    TBALINNET/ACSS/AW336.426/70.26400.307020.11370.08840.26520.720316.6440.010,50011,2000.2515
    TBAORIOLE/ACSS/AW336.430/70.26420.325920.10590.10590.31770.741317.6494.614,20014,8000.2465
    TBABRANT/ACSS/AW397.524/70.31220.352720.12870.08580.25740.772374.4490.610,40011,0000.2149
    TBAIBIS/ACSS/AW397.526/70.31200.362820.12360.09610.28830.783374.2519.912,40013,0000.2129
    TBALARK/ACSS/AW397.530/70.31210.384920.11510.11510.34530.806375.2584.016,70017,5000.2087
    TBATOUCAN/ACSS/AW477.022/70.37440.411220.14720.08180.24540.834449.0554.610,20010,8000.1810
    TBAFLICKER/ACSS/AW477.024/70.37470.423320.14100.09400.28200.846449.4588.812,50013,0000.1791
    TBAHAWK/ACSS/AW477.026/70.37440.435420.13540.10530.31590.858449.0624.014,90015,6000.1774
    TBAHEN/ACSS/AW477.030/70.37470.462120.12610.12610.37830.883450.5701.220,10020,5000.1738
    TBAHERON/ACSS/AW500.030/70.39270.484320.12910.12910.38730.904472.1734.920,60021,5000.1658
    TBASAPSUCKER/ACSS/AW556.522/70.43680.479720.15900.08830.26490.901523.8646.911,90012,6000.1552
    TBAPARAKEET/ACSS/AW556.524/70.43720.493820.15230.10150.30450.914524.3686.714,60015,2000.1535
    TBADOVE/ACSS/AW556.526/70.43710.508320.14630.11380.34140.927524.2728.417,50018,2000.1519
    TBAEAGLE/ACSS/AW556.530/70.43710.539120.13620.13620.40860.953525.5818.122,90024,0000.1490
    TBAPEACOCK/ACSS/AW605.024/70.47530.537020.15880.10590.31770.953570.0747.015,90016,5000.1412
    TBASQUAB/ACSS/AW605.026/70.47490.552220.15250.11860.35580.966569.5791.219,00019,7000.1398
    TBAWOOD DUCK/ACSS/AW605.030/70.47510.586020.14200.14200.42600.994571.2889.324,40025,5000.1371
    TBATEAL/ACSS/AW605.030/190.47510.583420.14200.08520.42600.994571.2882.525,00026,6000.1373
    TBADUCK/ACSS/AW605.054/70.47470.536230.10580.10580.31740.952569.3745.715,90016,5000.1414
    TBATURACOS/ACSS/AW636.020/70.49940.533920.17830.07920.23760.951598.9697.910,80011,3000.1370
    TBAGOLDFINCH/ACSS/AW636.022/70.49940.548420.17000.09440.28320.963598.9739.513,60014,1000.1357
    TBAROOK/ACSS/AW636.024/70.49960.564320.16280.10850.32550.977599.1784.716,70017,3000.1343
    TBAGROSBEAK/ACSS/AW636.026/70.49950.580820.15640.12160.36480.990599.0832.219,90020,3000.1330
    TBASCOTER/ACSS/AW636.030/70.49950.616020.14560.14560.43681.019600.5934.725,10026,8000.1304
    TBAEGRET/ACSS/AW636.030/190.49950.613520.14560.08740.43701.019600.5928.226,30028,0000.1306
    TBAGOOSE/ACSS/AW636.054/70.49930.564030.10850.10850.32550.977598.8784.416,70017,3000.1344
    TBAFLAMINGO/ACSS/AW666.624/70.52380.591720.16670.11110.33331.000628.2823.017,50018,2000.1281
    TBAGANNET/ACSS/AW666.626/70.52340.608620.16010.12450.37351.014627.7872.120,90021,3000.1269
    TBAGULL/ACSS/AW666.654/70.52350.591430.11110.11110.33331.000627.8822.617,50018,2000.1282
    TBASTILT/ACSS/AW715.524/70.56220.635020.17270.11510.34531.036674.2883.018,80019,5000.1194
    TBASTARLING/ACSS/AW715.526/70.56200.653520.16590.12900.38701.051674.0936.522,00022,9000.1182
    TBAREDWING/ACSS/AW715.530/190.56170.689720.15440.09260.46301.081675.3104329,50030,8000.1162
    TBACROW/ACSS/AW715.554/70.56190.634730.11510.11510.34531.036673.9882.718,80019,5000.1194
    TBATURBIT/ACSS/AW795.020/70.62460.667820.19940.08860.26581.063749.1873.013,50014,2000.1095
    TBAPUFFIN/ACSS/AW795.022/70.62440.685720.19010.10560.31681.077748.8924.617,10017,7000.1086
    TBACUCKOO/ACSS/AW795.024/70.62440.705320.18200.12130.36391.092748.8980.920,90021,3000.1075
    TBADRAKE/ACSS/AW795.026/70.62470.726420.17490.13600.40801.108749.2104124,40025,4000.1063
    TBASKIMMER/ACSS/AW795.030/70.62450.770220.16280.16280.48841.140750.8116929,90033,5000.1043
    TBAMALLARD/ACSS/AW795.030/190.62450.766920.16280.09770.48851.140750.8116032,90034,3000.1045
    TBATERN/ACSS/AW795.045/70.62420.667430.13290.08860.26581.063748.6872.513,50014,2000.1096
    TBACONDOR/ACSS/AW795.054/70.62400.704930.12130.12130.36391.092748.3980.420,90021,3000.1075
    TBARUDDY/ACSS/AW900.045/70.70660.755530.14140.09430.28291.131847.4987.715,30015,8000.0968
    TBACANARY/ACSS/AW900.054/70.70690.798530.12910.12910.38731.162847.7111123,20024,1000.0949
    TBACORNCRAKE/ACSS/AW954.020/70.74920.801020.21840.09710.29131.165898.5104716,20016,7000.0913
    TBAREDBIRD/ACSS/AW954.024/70.74950.846620.19940.13290.39871.196898.8117724,60025,5000.0895
    TBAMERGANSER/ACSS/AW954.030/70.74910.923920.17830.17830.53491.248900.5140235,00040,2000.0869
    TBACANVASBACK/ACSS/AW954.030/190.74910.919920.17830.10700.53501.248900.5139139,40041,1000.0871
    TBAPHOENIX/ACSS/AW954.042/70.74910.787630.15070.08370.25111.155898.4100913,60014,2000.0919
    TBARAIL/ACSS/AW954.045/70.74920.801030.14560.09710.29131.165898.5104716,20016,7000.0913
    TBATOWHEE/ACSS/AW954.048/70.74950.815730.14100.10970.32911.175898.8108919,00019,7000.0907
    TBACARDINAL/ACSS/AW954.054/70.74910.846230.13290.13290.39871.196898.4117724,60025,5000.0896
    TBASNOWBIRD/ACSS/AW1033.542/70.81210.853930.15690.08720.26161.203973.9109414,80015,4000.0847
    TBAORTOLAN/ACSS/AW1033.545/70.81120.867330.15150.10100.30301.212972.8113417,60018,1000.0843
    TBAWHOOPER/ACSS/AW1033.548/70.81130.882930.14670.11410.34231.223973.0117820,60021,3000.0838
    TBACURLEW/ACSS/AW1033.554/70.81120.916430.13830.13830.41491.245972.8127526,10027,7000.0827
    TBAAVOCET/ACSS/AW1113.042/70.87430.919230.16280.09040.27121.2481049117815,90016,3000.0787
    TBABLUEJAY/ACSS/AW1113.045/70.87450.935030.15730.10490.31471.2591049122318,90019,5000.0782
    TBABULLFINCH/ACSS/AW1113.048/70.87440.951630.15230.11850.35551.2691049127122,20023,0000.0778
    TBAFINCH/ACSS/AW1113.054/190.87460.985530.14360.08620.43101.2931054137328,80030,4000.0772
    TBAOXBIRD/ACSS/AW1192.542/70.93660.984830.16850.09360.28081.2921123126117,00017,5000.0735
    TBABUNTING/ACSS/AW1192.545/70.93671.001430.16280.10850.32551.3021123130920,30020,9000.0730
    TBACORMORANT/ACSS/AW1192.548/70.93641.019030.15760.12260.36781.3131123136023,80024,2000.0726
    TBAGRACKLE/ACSS/AW1192.554/190.93651.055230.14860.08920.44601.3381129147030,80032,6000.0721
    TBASCISSORTAIL/ACSS/AW1272.042/70.99871.050130.17400.09670.29011.3341198134518,20018,7000.0689
    TBABITTERN/ACSS/AW1272.045/70.99871.067830.16810.11210.33631.3451198139621,60022,3000.0685
    TBADIVER/ACSS/AW1272.048/70.99921.087330.16280.12660.37981.3571198145125,30025,8000.0681
    TBAPHEASANT/ACSS/AW1272.054/190.99931.125930.15350.09210.46051.3821204156832,80034,1000.0675
    TBARINGDOVE/ACSS/AW1351.542/71.06171.116330.17940.09970.29911.3761273143019,30019,9000.0648
    TBADIPPER/ACSS/AW1351.545/71.06141.134730.17330.11550.34651.3861273148323,00023,7000.0645
    TBAMARTIN/ACSS/AW1351.554/191.06141.195830.15820.09490.47451.4241279166534,90036,2000.0636
    TBAPOPINJAY/ACSS/AW1431.042/71.12411.182030.18460.10260.30781.4151348151420,50021,0000.0612
    TBABOBOLINK/ACSS/AW1431.045/71.12361.201330.17830.11890.35671.4271347157024,30025,1000.0609
    TBAWAGTAIL/ACSS/AW1431.048/71.12441.223630.17270.13430.40291.4391348163328,00029,0000.0605
    TBAPLOVER/ACSS/AW1431.054/191.12411.266530.16280.09770.48851.4651355176436,90038,4000.0600
    TBANUTHATCH/ACSS/AW1510.545/71.18621.268230.18320.12210.36631.4661423165825,70026,1000.0577
    TBAPARROT/ACSS/AW1510.554/191.18561.335730.16720.10030.50151.5051429186038,90040,4000.0569
    TBARATITE/ACSS/AW1590.042/71.24921.313430.19460.10810.32431.4921498168222,70023,4000.0551
    TBALAPWING/ACSS/AW1590.045/71.24921.335530.18800.12530.37591.5041498174627,00027,5000.0548
    TBAHORNBILL/ACSS/AW1590.048/71.24871.358930.18200.14160.42481.5171498181430,60031,7000.0545
    TBAFALCON/ACSS/AW1590.054/191.24891.407230.17160.10300.51501.5451505196041,10042,6000.0540
    TBACHUKAR/ACSS/AW1780.084/191.39861.512640.14560.08740.43701.6021685201333,60035,4000.0490
    TBAWOODPECKER/ACSS/AW1843.072/71.44761.510240.16000.10670.32011.6001745192524,00024,6000.0479
    TBASEAHAWK/ACSS/AW1869.068/71.46811.514740.16580.09210.27631.6031769190321,10021,5000.0474
    TBAMOCKINGBIRD/ACSS/AW2034.572/71.59791.667040.16810.11210.33631.6811926212426,50027,2000.0434
    TBABLUEBIRD/ACSS/AW2156.084/191.69311.830940.16020.09610.48051.7622040243640,70042,1000.0404
    TBAKIWI/ACSS/AW2167.072/71.70221.775840.17350.11570.34711.7352051226228,20029,0000.0407
    TBATHRASHER/ACSS/AW2312.076/191.81551.914440.17440.08140.40701.8022188247234,10035,6000.0380
    TBAJOREE/ACSS/AW2515.076/191.97502.082640.18190.08490.42451.8802380268937,10038,7000.0350