SPEC 85024

Multi-Conductor CU 600 V FR-XLPE Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG CU X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT SHIELDED 600V SUN RES MM/YYYY {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsmilmilinchlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA142730450.372922.6313.1700.0584.52025Black
    TBA143730450.3921122.6313.1700.0584.72025Black
    TBA144730450.4261302.6313.1700.0585.11620Black
    TBA145730450.4631542.6313.1700.0585.61620Black
    TBA146730450.5021792.6313.1700.0586.01620Black
    TBA147730450.5021972.6313.1700.0586.01417Black
    TBA148730600.5722382.6313.1700.0586.91417Black
    TBA149730600.6112652.6313.1700.0587.31417Black
    TBA1410730600.6622922.6313.1700.0587.91012Black
    TBA1412730600.6823312.6313.1700.0588.21012Black
    TBA1415730600.7543992.6313.1700.0589.01012Black
    TBA1419730600.7924782.6313.1700.0589.51012Black
    TBA1420730800.8725382.6313.1700.05810.51012Black
    TBA1425730800.9626472.6313.1700.05811.5911Black
    TBA1430730801.0157492.6313.1700.05812.2911Black
    TBA1437730801.0928932.6313.1700.05813.1810Black
    620673$14121930600.6893372.6313.1700.0588.31012Black
    12 AWG
    TBA122730450.4081171.6622.0020.0544.92530Black
    TBA123730450.4311471.6622.0020.0545.22530Black
    TBA124730450.4701721.6622.0020.0545.62024Black
    TBA125730450.5112051.6622.0020.0546.12024Black
    TBA126730600.5862561.6622.0020.0547.02024Black
    TBA127730600.5862821.6622.0020.0547.01721Black
    TBA128730600.6313171.6622.0020.0547.61721Black
    TBA1210730600.7343901.6622.0020.0548.81215Black
    625170!1212730600.7984741.6622.0020.0549.61215Black
    TBA1215730800.8795771.6622.0020.05410.51215Black
    TBA1219730800.9226931.6622.0020.05411.11215Black
    TBA1220730800.9677291.6622.0020.05411.61215Black
    TBA1225730801.0708851.6622.0020.05412.81113Black
    TBA1230730801.13010311.6622.0020.05413.61113Black
    TBA1237730801.21812351.6622.0020.05414.61012Black
    10 AWG
    606612^?102730450.4601641.0401.2530.0503.23540Black
    TBA103730450.4851991.0401.2530.0503.43540Black
    TBA105730600.6093011.0401.2530.0504.32832Black
    TBA106730600.6613521.0401.2530.0504.62832Black
    TBA107730600.6613911.0401.2530.0504.62428Black
    TBA108730600.7144401.0401.2530.0505.02428Black
    TBA109730600.7664911.0401.2530.0505.42428Black
    TBA1010730800.8745781.0401.2530.05010.51720Black
    606609^?1012730800.8996891.0401.2530.05010.81720Black
    TBA1015730800.9968041.0401.2530.05012.01720Black
    TBA1019730801.0479751.0401.2530.05012.61720Black
    TBA1020730801.10010261.0401.2530.05013.21720Black
    TBA1025730801.22012531.0401.2530.05014.61518Black
    TBA1030730801.29014671.0401.2530.05015.51518Black
    TBA1037730801.39317661.0401.2530.05016.71416Black
    619669$1041930600.5732571.0401.2530.0506.72832Black
    619870$10121930800.9246841.0401.2530.05011.11720Black
    8 AWG
    603609$8121945801.16510680.6530.7860.05213.92527Black
    6 AWG
    664167&641945600.8125630.4110.5350.0319.75260Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    $ 19 strand combination unilay conductor per ASTM B787
    ? Drain wire
    & 19 strand Class C compressed conductor per ASTM B8
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.