SPEC 85024

Multi-Conductor CU 600 V FR-XLPE Shielded Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mil copper Helically-Applied Tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG CU X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT SHIELDED 600V SUN RES MM/YYYY {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA14270.07130450.358701062.6313.2650.0582.52025BK
    TBA14370.07130450.379861282.6313.2650.0582.72025BK
    TBA14470.07130450.4131051552.6313.2650.0582.91620BK
    TBA14570.07130450.451231822.6313.2650.0583.21620BK
    TBA14670.07130450.4891412082.6313.2650.0583.41620BK
    TBA14770.07130450.4891542272.6313.2650.0583.41418BK
    TBA14870.07130600.561732692.6313.2650.0583.91418BK
    TBA14970.07130600.5991922972.6313.2650.0584.21418BK
    TBA141070.07130600.652123282.6313.2650.0584.61012BK
    TBA141270.07130600.6712423712.6313.2650.0584.71012BK
    TBA141570.07130600.7432914442.6313.2650.0585.21012BK
    TBA141970.07130600.7813485262.6313.2650.0585.51012BK
    TBA142070.07130600.8223685562.6313.2650.0585.81012BK
    TBA142570.07130800.9524457022.6313.2650.0586.7911BK
    TBA143070.07130801.0065198112.6313.2650.0587911BK
    TBA143770.07130801.0836229632.6313.2650.0587.6810BK
    620673$1412190.07330600.7121943492.6313.2650.05851012BK
    12 AWG
    TBA12270.08930450.394891301.6622.0630.0542.82530BK
    TBA12370.08930450.4181141631.6622.0630.0542.92530BK
    TBA12470.08930450.4571391971.6622.0630.0543.22024BK
    TBA12570.08930450.4981652331.6622.0630.0543.52024BK
    TBA12670.08930600.5731912831.6622.0630.05442024BK
    TBA12770.08930600.5732113091.6622.0630.05441821BK
    TBA12870.08930600.6192383481.6622.0630.0544.31821BK
    TBA121070.08930600.7222934261.6622.0630.0545.11215BK
    625170!121270.08930600.82994791.6622.0630.0545.61215BK
    TBA121570.08930800.8684096151.6622.0630.0546.11215BK
    TBA121970.08930800.9114967331.6622.0630.0546.41215BK
    TBA122070.08930800.9575227731.6622.0630.0546.71215BK
    TBA122570.08930801.066389341.6622.0630.0547.41114BK
    TBA123070.08930801.12174710841.6622.0630.0547.81114BK
    TBA123770.08930801.20990012941.6622.0630.0548.51012BK
    10 AWG
    TBA10370.11330450.471572141.041.2910.053.33540BK
    606612^?10270.11330450.4721041671.041.2910.053.33540BK
    TBA10570.11330600.5932353291.041.2910.054.22832BK
    TBA10670.11330600.6452743821.041.2910.054.52832BK
    TBA10770.11330600.6453064211.041.2910.054.52428BK
    TBA10870.11330600.6993474761.041.2910.054.92428BK
    TBA10970.11330600.7513865271.041.2910.055.32428BK
    TBA101070.11330600.8184275831.041.2910.055.71820BK
    606609^?101270.11330800.9294537021.041.2910.056.51820BK
    TBA101570.11330800.9816078481.041.2910.056.91820BK
    TBA101970.11330801.03174310211.041.2910.057.21820BK
    TBA102070.11330801.08578210761.041.2910.057.61820BK
    TBA102570.11330801.20496113101.041.2910.058.41618BK
    TBA103070.11330801.275113315301.041.2910.058.91618BK
    TBA103770.11330801.377137318371.041.2910.059.61416BK
    619669$104190.11730600.5731612581.041.2910.0542832BK
    619870$1012190.11730800.9244476851.041.2910.056.51820BK
    8 AWG
    603609$812190.14345801.16570810680.6530.810.0528.22528BK
    6 AWG
    664167&64190.17945600.8123765630.4110.510.0515.75260BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    $ 19 strand combination unilay conductor per ASTM B787
    ? Drain wire
    & 19 strand Class C compressed conductor per ASTM B8
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.006

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC