SPEC 83310
Quadruplex Copper XLPE Service Drop Neutral - Messenger
Copper Conductors With Crosslinked Polyethylene Insulation.

Construction:
- Conductor:Conductors are stranded, compressed copper
- Messenger:Hard Drawn Copper
- Insulation:Cross Linked Polyethylene (XLPE)
Applications and Features:
Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Dia. Over Phase Conductor | Phase Insul. Thickness | Dia. Over Phase Insulation | Neutral Cond. Size | Neutral Strand | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | mil | inch | AWG/Kcmil | No. | inch | lb/1000ft | ||
| TBA | ATLANTA | 6 | 7 | 0.178 | 45 | 0.268 | 6 | 1 | 0.649 | 422 |
| TBA | TALLAHASSEE | 6 | 7 | 0.178 | 45 | 0.268 | 6 | 7 | 0.649 | 422 |
| 606621 | RICHMOND | 4 | 7 | 0.225 | 45 | 0.67 | 4 | 7 | 0.76 | 570 |
| TBA | BATON ROUGE | 4 | 7 | 0.225 | 45 | 0.315 | 4 | 1 | 0.762 | 666 |
| 325886 | SEATTLE | 2 | 7 | 0.283 | 45 | 0.81 | 2 | 7 | 0.9 | 889 |
| TBA | JACKSON | 2 | 7 | 0.283 | 45 | 0.373 | 2 | 1 | 0.903 | 1050 |
| TBA | NASHVILLE | 1/0 | 19 | 0.362 | 60 | 0.482 | 1/0 | 7 | 1.166 | 1674 |
| 110908 | LINCOLN | 2/0 | 19 | 0.405 | 60 | 1.15 | 2/0 | 7 | 1.27 | 1771 |
| TBA | RALEIGH | 3/0 | 19 | 0.456 | 60 | 0.576 | 3/0 | 7 | 1.394 | 2644 |
| TBA | DENVER | 4/0 | 19 | 0.512 | 60 | 0.632 | 4/0 | 7 | 1.529 | 3325 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | GMR | Allowable Ampacity In Air 75/90°C |
|---|---|---|---|---|---|---|---|
| AWG/Kcmil | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | ft | Amp | |
| ATLANTA | 6 | 1280 | 0.411 | 0.51 | 0.051 | 0.067 | 105 |
| TALLAHASSEE | 6 | 1228 | 0.411 | 0.51 | 0.051 | 0.067 | 105 |
| RICHMOND | 4 | 1938 | 0.258 | 0.32 | 0.048 | 0.084 | 140 |
| BATON ROUGE | 4 | 1970 | 0.258 | 0.32 | 0.048 | 0.084 | 140 |
| SEATTLE | 2 | 3050 | 0.162 | 0.201 | 0.045 | 0.105 | 190 |
| JACKSON | 2 | 3003 | 0.162 | 0.201 | 0.045 | 0.105 | 190 |
| NASHVILLE | 1/0 | 4752 | 0.102 | 0.127 | 0.044 | 0.139 | 260 |
| LINCOLN | 2/0 | 5926 | 0.082 | 0.102 | 0.043 | 0.156 | 300 |
| RALEIGH | 3/0 | 7366 | 0.064 | 0.079 | 0.042 | 0.175 | 350 |
| DENVER | 4/0 | 9154 | 0.051 | 0.063 | 0.041 | 0.197 | 405 |
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:09 p.m. UTC