SPEC 83305

Triplex Copper XLPE Service Drop Neutral - Messenger

Copper Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed copper
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:Hard Drawn Copper

Applications and Features:

Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B1 Hard-Drawn Copper
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBACOLUMBIAN8Solid0.129450.219810.473217
    TBAGARAMOND870.142450.232870.501218
    TBABODONI870.142450.232810.501218
    TBAGOTHIC670.178450.268670.579341
    110718FUTURA670.178450.489610.579271
    TBATUDOR670.178450.268810.579311
    110759CASLON470.225450.59470.68423
    TBAIONIC470.225450.315410.68537
    110734NONPAREIL470.225450.59610.68374
    324640CENTURY270.283450.716270.806661
    110775PRIMER270.283450.716470.806585
    110767MINION270.283450.716410.806582
    110791CORINTHIAN1/0190.362600.9211/071.0411053
    110809DORIC2/0190.405601.0162/071.1361318
    110825COMPOSITE4/0190.512601.2454/071.3652069
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75/90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    COLUMBIAN88260.6530.810.0520.05380
    GARAMOND87770.6530.810.0520.05380
    BODONI88260.6530.810.0520.05380
    GOTHIC612280.4110.510.0510.067105
    FUTURA612800.4110.510.0510.067105
    TUDOR68260.4110.510.0510.067105
    CASLON419380.2580.320.0480.084140
    IONIC419700.2580.320.0480.084140
    NONPAREIL412800.2580.320.0480.084140
    CENTURY230500.1620.2010.0450.105190
    PRIMER219380.1620.2010.0450.105190
    MINION219700.1620.2010.0450.105190
    CORINTHIAN1/047520.1020.1270.0440.139260
    DORIC2/059260.0820.1020.0430.156300
    COMPOSITE4/059260.0510.0630.0410.197405

    Revision: 1.000.001

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC