SPEC 83305

Triplex Copper XLPE Service Drop Neutral - Messenger

Copper Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed copper
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:Hard Drawn Copper

Applications and Features:

Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B1 Hard-Drawn Copper
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBAColumbian8Solid0.128300.188810.408237
    TBAGaramond870.141300.201870.436240
    TBABodoni870.141300.201810.436240
    TBAGothic670.177300.237670.514370
    TBATudor670.177300.237810.514340
    110718Futura670.177300.237610.578270
    TBAIonic470.225300.285410.618577
    110759Caslon470.225300.285470.680423
    110734Nonpareil470.225300.285610.680373
    324640Century270.282450.372270.805660
    110775Primer270.282450.372470.805584
    110767Minion270.282450.372410.805582
    110791Corinthian1/0190.361600.4811/071.0411053
    110809Doric2/0190.405600.5252/071.1361317
    110825Composite4/0190.512600.6324/071.3652069
    All dimensions are nominal and subject to normal manufacturing tolerances
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    Columbian88260.6530.7860.0520.00470 / 80
    Garamond87770.6530.7860.0520.00470 / 80
    Bodoni88260.6530.7860.0520.00470 / 80
    Gothic612280.4110.4950.0510.00595 / 105
    Tudor68260.4110.4950.0510.00595 / 105
    Futura612800.4110.4950.0510.00595 / 105
    Ionic419700.2580.3100.0480.007125 / 140
    Caslon419380.2580.3100.0480.007125 / 140
    Nonpareil412800.2580.3100.0480.007125 / 140
    Century230500.1620.1950.0450.008170 / 190
    Primer219380.1620.1950.0450.008170 / 190
    Minion219700.1620.1950.0450.008170 / 190
    Corinthian1/047520.1020.1220.0440.011230 / 260
    Doric2/059260.0810.0970.0430.013265 / 300
    Composite4/059260.0510.0620.0410.016360 / 405