SPEC 83305
Triplex Copper XLPE Service Drop Neutral - Messenger
Copper Conductors With Crosslinked Polyethylene Insulation.

Construction:
- Conductor:Conductors are stranded, compressed copper
- Insulation:Cross Linked Polyethylene (XLPE)
- Messenger:Hard Drawn Copper
Applications and Features:
Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Dia. Over Phase Conductor | Phase Insul. Thickness | Dia. Over Phase Insulation | Neutral Cond. Size | Neutral Strand | Approx. OD | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | mil | inch | AWG/Kcmil | No. | inch | lb/1000ft | ||
| TBA | COLUMBIAN | 8 | Solid | 0.129 | 45 | 0.219 | 8 | 1 | 0.473 | 217 |
| TBA | GARAMOND | 8 | 7 | 0.142 | 45 | 0.232 | 8 | 7 | 0.501 | 218 |
| TBA | BODONI | 8 | 7 | 0.142 | 45 | 0.232 | 8 | 1 | 0.501 | 218 |
| TBA | GOTHIC | 6 | 7 | 0.178 | 45 | 0.268 | 6 | 7 | 0.579 | 341 |
| 110718 | FUTURA | 6 | 7 | 0.178 | 45 | 0.489 | 6 | 1 | 0.579 | 271 |
| TBA | TUDOR | 6 | 7 | 0.178 | 45 | 0.268 | 8 | 1 | 0.579 | 311 |
| 110759 | CASLON | 4 | 7 | 0.225 | 45 | 0.59 | 4 | 7 | 0.68 | 423 |
| TBA | IONIC | 4 | 7 | 0.225 | 45 | 0.315 | 4 | 1 | 0.68 | 537 |
| 110734 | NONPAREIL | 4 | 7 | 0.225 | 45 | 0.59 | 6 | 1 | 0.68 | 374 |
| 324640 | CENTURY | 2 | 7 | 0.283 | 45 | 0.716 | 2 | 7 | 0.806 | 661 |
| 110775 | PRIMER | 2 | 7 | 0.283 | 45 | 0.716 | 4 | 7 | 0.806 | 585 |
| 110767 | MINION | 2 | 7 | 0.283 | 45 | 0.716 | 4 | 1 | 0.806 | 582 |
| 110791 | CORINTHIAN | 1/0 | 19 | 0.362 | 60 | 0.921 | 1/0 | 7 | 1.041 | 1053 |
| 110809 | DORIC | 2/0 | 19 | 0.405 | 60 | 1.016 | 2/0 | 7 | 1.136 | 1318 |
| 110825 | COMPOSITE | 4/0 | 19 | 0.512 | 60 | 1.245 | 4/0 | 7 | 1.365 | 2069 |
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | GMR | Allowable Ampacity In Air 75/90°C |
|---|---|---|---|---|---|---|---|
| AWG/Kcmil | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | ft | Amp | |
| COLUMBIAN | 8 | 826 | 0.653 | 0.81 | 0.052 | 0.053 | 80 |
| GARAMOND | 8 | 777 | 0.653 | 0.81 | 0.052 | 0.053 | 80 |
| BODONI | 8 | 826 | 0.653 | 0.81 | 0.052 | 0.053 | 80 |
| GOTHIC | 6 | 1228 | 0.411 | 0.51 | 0.051 | 0.067 | 105 |
| FUTURA | 6 | 1280 | 0.411 | 0.51 | 0.051 | 0.067 | 105 |
| TUDOR | 6 | 826 | 0.411 | 0.51 | 0.051 | 0.067 | 105 |
| CASLON | 4 | 1938 | 0.258 | 0.32 | 0.048 | 0.084 | 140 |
| IONIC | 4 | 1970 | 0.258 | 0.32 | 0.048 | 0.084 | 140 |
| NONPAREIL | 4 | 1280 | 0.258 | 0.32 | 0.048 | 0.084 | 140 |
| CENTURY | 2 | 3050 | 0.162 | 0.201 | 0.045 | 0.105 | 190 |
| PRIMER | 2 | 1938 | 0.162 | 0.201 | 0.045 | 0.105 | 190 |
| MINION | 2 | 1970 | 0.162 | 0.201 | 0.045 | 0.105 | 190 |
| CORINTHIAN | 1/0 | 4752 | 0.102 | 0.127 | 0.044 | 0.139 | 260 |
| DORIC | 2/0 | 5926 | 0.082 | 0.102 | 0.043 | 0.156 | 300 |
| COMPOSITE | 4/0 | 5926 | 0.051 | 0.063 | 0.041 | 0.197 | 405 |
Revision: 1.000.001
Updated On: Dec. 31, 2024, 11:09 p.m. UTC
