SPEC 83301

Duplex Copper XLPE Service Drop Neutral - Messenger

Copper Conductors With Crosslinked Polyethylene Insulation.

...

Construction:

  1. Conductor:Conductors are stranded, compressed copper
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:Hard Drawn Copper

Applications and Features:

Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications:

  • ASTM B1 Hard-Drawn Copper
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandDia. Over Phase ConductorPhase Insul. ThicknessDia. Over Phase InsulationNeutral Cond. SizeNeutral StrandApprox. ODApprox. Weight
    AWG/KcmilNo.inchmilinchAWG/KcmilNo.inchlb/1000ft
    TBAOMEGA8Solid0.129450.219810.438166
    TBATHETA870.142450.2320.464
    TBAIOTA870.142450.232810.464167
    TBAKAPPA870.142450.232870.464167
    110650SIGMA670.178450.362670.452176
    TBALAMBDA670.178450.268810.536230
    TBAOMICRON670.178450.268610.536260
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzGMRAllowable Ampacity In Air 75/90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftftAmp
    OMEGA88260.6530.810.0520.05380
    THETA80.6530.810.0520.05380
    IOTA88260.6530.810.0520.05380
    KAPPA87770.6530.810.0520.05380
    SIGMA612280.4110.510.0510.067105
    LAMBDA68260.4110.510.0510.067105
    OMICRON612800.4110.510.0510.067105

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC