SPEC 83301
Duplex Copper XLPE Service Drop Neutral - Messenger
Copper Conductors With Crosslinked Polyethylene Insulation.

Construction:
- Conductor:Conductors are stranded, compressed copper
- Insulation:Cross Linked Polyethylene (XLPE)
- Messenger:Hard Drawn Copper
Applications and Features:
Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.
Specifications:
Table 1 – Weights and Measurements
| Stock Number | Code Word | Phase Cond. Size | Phase Strand | Dia. Over Phase Conductor | Phase Insul. Thickness | Dia. Over Phase Insulation | Neutral Cond. Size | Neutral Strand | Approx. OD | Approx. Weight | 
|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | mil | inch | AWG/Kcmil | No. | inch | lb/1000ft | ||
| TBA | Omega | 8 | Solid | 0.128 | 30 | 0.188 | 8 | 1 | 0.378 | 180 | 
| TBA | Theta | 8 | 7 | 0.141 | 30 | 0.201 | 0.404 | 131 | ||
| TBA | Iota | 8 | 7 | 0.141 | 30 | 0.201 | 8 | 1 | 0.404 | 182 | 
| TBA | Kappa | 8 | 7 | 0.141 | 30 | 0.201 | 8 | 7 | 0.404 | 182 | 
| 110650 | Sigma | 6 | 7 | 0.177 | 30 | 0.237 | 6 | 7 | 0.451 | 176 | 
| TBA | Lambda | 6 | 7 | 0.177 | 30 | 0.237 | 8 | 1 | 0.476 | 251 | 
| TBA | Omicron | 6 | 7 | 0.177 | 30 | 0.237 | 6 | 1 | 0.476 | 281 | 
All dimensions are nominal and subject to normal manufacturing tolerances
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Code Word | Phase Cond. Size | Neutral Rated Breaking Strength | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | GMR | Allowable Ampacity In Air 75/90°C | 
|---|---|---|---|---|---|---|---|
| AWG/Kcmil | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | ft | Amp | |
| Omega | 8 | 826 | 0.653 | 0.786 | 0.052 | 0.004 | 70 / 80 | 
| Theta | 8 | 0.653 | 0.786 | 0.052 | 0.004 | 70 / 80 | |
| Iota | 8 | 826 | 0.653 | 0.786 | 0.052 | 0.004 | 70 / 80 | 
| Kappa | 8 | 777 | 0.653 | 0.786 | 0.052 | 0.004 | 70 / 80 | 
| Sigma | 6 | 1228 | 0.411 | 0.495 | 0.051 | 0.005 | 95 / 105 | 
| Lambda | 6 | 826 | 0.411 | 0.495 | 0.051 | 0.005 | 95 / 105 | 
| Omicron | 6 | 1280 | 0.411 | 0.495 | 0.051 | 0.005 | 95 / 105 | 